| 2020-06-30 11:15:26 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT 19021420 |
| | 6/30/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) A NEW LANDSCAPE PLAN WAS SUBMITTED HOWEVER THE 1ST |
| | REVIEW PLUMBING COMMENTS PRINTED BELOW ABOUT THE |
| | IRRIGATION SYSTEM WERE NOT ADDRESSED. PLEASE NOTE THAT |
| | A SEPARATE PERMIT IS REQUIRED FOR LANDSCAPING. |
| | |
| | PLUMBING 1ST REVIEW**DENIED** |
| | |
| | 1) PERMIT APPLICATION CALLS OUT TEMP SYSTEM. PLEASE |
| | CLARIFY HOW LONG THIS TIME SYSTEM WILL BE IN PLACE AND |
| | PROVIDE SECTIONS ON PLAN WHICH AREA WILL BE TEMP. FBC |
| | 107.2.1 |
| | 2) SHT. 2 CALL OUT A PVB BACKFLOW. PER THE CITY OF WPB |
| | CROSS CONNECTION MANUAL ALL COMMERCIAL PROPERTIES |
| | IRRIGATION SYSTEM BE PROTECTED BY AN RPZ BACKFLOW PIPED |
| | FROM THE METER IN MIN TYPE (L) COPPER. INSTALLED OF THE |
| | DEVICE IS ONLY TO BY DONE BY LICENSE PLUMBER (F.S 489 |
| | AND CROSS CONNECTION MANUAL) AND REQUIRES SEPARATE |
| | PERMIT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | PLUMBING 1ST REVIEW**DENIED** |
| | |
| | 1) PERMIT APPLICATION CALLS OUT TEMP SYSTEM. PLEASE |
| | CLARIFY HOW LONG THIS TIME SYSTEM WILL BE IN PLACE AND |
| | PROVIDE SECTIONS ON PLAN WHICH AREA WILL BE TEMP. FBC |
| | 107.2.1 |
| | 2) SHT. 2 CALL OUT A PVB BACKFLOW. PER THE CITY OF WPB |
| | CROSS CONNECTION MANUAL ALL COMMERCIAL PROPERTIES |
| | IRRIGATION SYSTEM BE PROTECTED BY AN RPZ BACKFLOW PIPED |
| | FROM THE METER IN MIN TYPE (L) COPPER. INSTALLED OF THE |
| | DEVICE IS ONLY TO BY DONE BY LICENSE PLUMBER (F.S 489 |
| | AND CROSS CONNECTION MANUAL) AND REQUIRES SEPARATE |
| | PERMIT. |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH (CGA SOLUTIONS) |
| | [email protected] |
| | 561-248-2703 |
| | |