Plan Review Details - Permit 19021376
Plan Review Stops For Permit 19021376
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-03-11 Cont ID  
Sent By cthroop Date 2019-03-11 Time 09:25 Rev Time 0.00
Received By cthroop Date 2019-03-08 Time 17:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-07-22 Cont ID  
Sent By jleahy Date 2019-07-22 Time 11:50 Rev Time 0.00
Received By jleahy Date 2019-07-22 Time 11:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-06-26 Cont ID  
Sent By jpearson Date 2019-06-26 Time 13:13 Rev Time 0.00
Received By jpearson Date 2019-06-26 Time 13:13 Sent To  
Notes
2019-06-26 13:02:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SCOPE OF WORK PROVIDED DOES NOT MATCH WHAT IS SHOWN
 ON PLAN. IT APPEARS THE WHOLE HOUSE IS BEING RE-WIRED.
 PROVIDE CLARIFICATION AND/OR CORRECTIONS AS NEEDED. WPB
 FBC 107.2.1
 2. WHEN UPLOADING PLAN SHEETS, EACH SHEET MUST BE A
 SEPARATE UPLOAD. ALSO, DO NOT UPLOAD PICTURES. THE
 PANEL SCHEDULE WAS UPLOADED TO SUPPORTING DOCS FOLDER
 AND SHOULD BE IN THE DRAWINGS FOLDER. WPB FBC 107.2
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 4. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 5. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 6. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
 7. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION FOR GUEST BATH. NEC 210.11(C)(3),
 210.52(D); FBC RE E3703.4, E3901.6
 8. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN
 KITCHEN REQUIRE GFCI PROTECTION. PROVIDE CORRECTION.
 NEC 210.8; FBC RE E3902.6
 9. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-04-03 Cont ID  
Sent By ppetty Date 2019-04-03 Time 09:02 Rev Time 0.00
Received By ppetty Date 2019-04-03 Time 09:02 Sent To  
Notes
2019-04-03 09:03:13NO ELECTRICAL ON PLAN NO REVIEW. PP

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-07 Cont ID  
Sent By ppetty Date 2019-03-07 Time 13:37 Rev Time 0.00
Received By ppetty Date 2019-03-07 Time 13:37 Sent To  
Notes
2019-03-07 13:38:32NO ELECTRICAL ON PLAN NO REVIEW PP

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-06-26 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-05 Time 10:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-03 Cont ID  
Sent By ppetty Date 2019-04-03 Time 09:05 Rev Time 0.00
Received By ppetty Date 2019-03-25 Time 16:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-11 Cont ID  
Sent By cthroop Date 2019-03-11 Time 09:26 Rev Time 0.00
Received By cthroop Date 2019-03-04 Time 08:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-03-11 Cont ID  
Sent By cthroop Date 2019-03-11 Time 09:25 Rev Time 0.00
Received By cthroop Date 2019-03-08 Time 17:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-07-25 Cont ID  
Sent By dbattles Date 2019-07-25 Time 16:22 Rev Time 0.00
Received By dbattles Date 2019-07-25 Time 16:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2019-06-26 Cont ID  
Sent By jpearson Date 2019-06-26 Time 13:13 Rev Time 0.00
Received By jpearson Date 2019-06-26 Time 13:13 Sent To  
Notes
2019-06-26 13:13:43SIGNATURES ARE FINE BUT NEED TO BE CHECKED ON NEXT
 REVIEW. MAKE SURE EACH PAGE IS UPLOADED SEPARATELY AND
 THAT THEY EACH HACE A SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. FS 481.229; WPB FBC 107.1,
 107.2.1, 107.3.5.1.2

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-04-03 Cont ID  
Sent By ppetty Date 2019-04-03 Time 09:04 Rev Time 0.00
Received By ppetty Date 2019-04-03 Time 09:04 Sent To  
Notes
2019-04-03 09:04:55PLAN NOT SIGNED BY ELECTRICAL CONTRACTOR.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-03-11 Cont ID  
Sent By cthroop Date 2019-03-11 Time 09:25 Rev Time 0.00
Received By cthroop Date 2019-03-08 Time 17:04 Sent To  
Notes
2019-03-11 09:26:48ELECTRICAL PLAN SHALL HAVE CONTRACTORS NAME AND
 SIGNATURE. CT


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved