Plan Review Details - Permit 19021354
Plan Review Stops For Permit 19021354
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-04-15 Cont ID  
Sent By jduprey Date 2019-04-15 Time 16:30 Rev Time 0.00
Received By jduprey Date 2019-04-15 Time 15:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-12 Cont ID  
Sent By jwitmer Date 2019-03-12 Time 08:55 Rev Time 0.00
Received By jwitmer Date 2019-03-11 Time 15:06 Sent To  
Notes
2019-03-12 08:55:402017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19021354
 ADD: 831 VILLAGE BLVD. SUITE: 307
 CONT: SIZ CONSTRUCTION CORP.
 TEL: 305-303-8111
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 12/ 2019
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS ARE NOT SIGNED AND SEALED BY A
 DESIGN PROFESSIONAL. UNDER THE PROJECT DIRECTORY IT
 STATES:
 ARCHITECT:
 ARCHIDEZIGNS, LLC / LICENSE FOR ARCHITECT BUSINESS
 AA26002029
 1585 NE 26TH ST.
 WILTON MANORS, FL 33305
 954-934-9076
 ARCHITECTS: FLORIDA ADMINISTRATIVE CODE 61G1-16.005.
 PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR
 ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 MEP ENGINEERS
 B & K ENGINEERING GROUP CERTIFICATE OF AUTHORIZATION
 31989
 11731 NW 39TH PLACE
 SUNRISE, FL 33323
 561-716-7120
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2) THE JOBSITE VALUE OF THIS PROJECT IS $93,000.00
 DOLLARS IN VALUE. PLEASE REVIEW WHERE UP TO $18,600.00
 DOLLARS IN VALUE (0.20% X $93,000.00= $18,600.00) WILL
 BE SPENT ON ACCESSIBLE UPGRADES OVER AND BEYOND THE
 COST OF THE JOB TO MAKE THIS TENANT SPACE FULLY
 ACCESSIBLE. PLEASE REVIEW IN ORDER OF HOW THE FUNDS ARE
 TO BE SPENT. 2017 FBC-ACCESS. CODE SECTION:
 202.4.1 DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COSTS THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COSTS
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (II) COSTS
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COSTS ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COSTS ASSOCIATED WITH RELOCATING AN INACCESSIBLE
 DRINKING FOUNTAIN.
 EITHER THE DESIGN PROFESSIONAL OR THE CONTRACTOR CAN
 CREATE ON THEIR LETTERHEAD A LETTER IN THE ORDER OF
 ALTERED AREAS HOW THE FUNDS WILL BE SPENT TO MAKE THIS
 PROJECT CODE COMPLIANT AS MUCH AS POSSIBLE WITHOUT
 GOING OVER THE DISPROPORTIONATE COST OF $18,600.00 IN
 VALUE FOR ACCESSIBILITY.
  
 3) SHEET 005-A-141 IS SHOWN AS THE LIFE SAFETY SHEET.
  
 3A) CAPACITY OF EXITS. THE PLAN STATES THE MINIMUM
 REQUIRED DOOR WIDTH IS 32 INCHES. PLEASE REVIEW THE
 2017 FBC-B:
 1010.1.1 SIZE OF DOORS. THE REQUIRED CAPACITY OF EACH
 DOOR OPENING SHALL BE SUFFICIENT FOR THE OCCUPANT LOAD
 THEREOF AND SHALL PROVIDE A MINIMUM CLEAR WIDTH OF 32
 INCHES. CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS
 SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE
 STOP, WITH THE DOOR OPEN 90 DEGREES).
 2017 FBC-ACCESSIBILITY CODE 404.2.3 CLEAR WIDTH. DOOR
 OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES
 MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS
 SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE
 STOP, WITH THE DOOR OPEN 90 DEGREES.
  
 3B) THE LIFE SAFETY SHEET SHOWS 2 EXISTING RESTROOMS,
 BOTH SHOW A CIRCLE WITHIN BOTH, NOT DIMENSIONED, ON
 SHEET 002-A-101 THE DIMENSION PLAN DOES NOT SHOW
 DIMENSIONS TO THE EXISTING RESTROOMS. COMPLIANCE WITH
 THE 2017 FBC-ACCESSIBILITY CODE 213.2 NOR 603 CANNOT BE
 DETERMINED.
  
 3C) THIS SHEET SHOWS CUSTOMER SEATING AND TABLES BUT
 DOES NOT GIVE THE HEIGHT OF THE ACCESSIBLE TABLE? SHOW
 COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE SECTION
 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4A) SHEET 010-A-401 DETAIL 1 SHOWS ONE OF THE EXISTING
 RESTROOMS AND STATES FOR REFERENCE ONLY. THIS DETAIL
 DOES NOT INDICATE THAT THIS IS SUPPOSED TO BE AN
 ACCESSIBLE RESTROOM ALTHOUGH THERE IS A CIRCLE WITHIN
 THE RESTROOM POSSIBLY REPRESENTING 5 FOOT DIAMETER AND
 COMPLIANCE WITH ACCESS. CODE 304.3.1 THE CIRCLE NOR
 DOES THE ROOM SHOW ANY DIMENSIONS INDICATING CODE
 COMPLIANCE.
  
 4B) WITHIN THIS SAME RESTROOM THE PLAN DOES SHOW THE
 CLEAR FLOOR SPACE REQUIRED BY 604.3.1 BUT DOES NOT MEET
 THE OVERLAP REQUIREMENTS OF 604.3.2 OF THE ACCESS.
 CODE.
  
 4C) PLEASE SEE THE ELEVATIONS FOR THE GRAB BARS, DETAIL
 4 ELEVATIONS, THE GRAB BARS ARE DIMENSIONED FROM THE
 CENTERLINE OF THE GARB BAR, UNDER THE 2017
 FBC-ACCESSIBILITY CODE YOU WOULD MEASURE FROM THE TOP
 OF THE BAR.
  
 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF
 GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 4D) IN THE ELEVATION 4 DETAIL 1 ELEVATION THE BACK GRAB
 BAR WOULD APPEAR NOT TO MEET THE REQUIREMENTS OF
 604.5.2ACCESS. CODE FOR THE REAR WALL, COMPLIANCE
 CANNOT BE DETERMINED SINCE THERE ARE NO DIMENSIONS.
  
 5) SHEET 011-A-402: THE LOCATION OF GRAB BARS AGAIN IS
 TAKEN FROM THE CENTERLINE NOT THE TOP OF THE GRIPPING
 SURFACE. 2017 FBC-ACCESSIBILITY CODE SECTION 609.4
 POSITION OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN
 A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, NOT CENTERLINE.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-04-17 Cont ID  
Sent By jleahy Date 2019-04-17 Time 16:03 Rev Time 0.00
Received By jleahy Date 2019-04-17 Time 16:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-04-09 Cont ID  
Sent By jpearson Date 2019-04-09 Time 15:00 Rev Time 0.00
Received By jpearson Date 2019-04-09 Time 15:00 Sent To  
Notes
2019-04-09 15:00:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO ELECTRICAL ISSUES. CANNOT STAMP THE PLAN UNTIL
 THE SIGNED/SEALED PLAN IS RECIEVED. WPB FBC 107.1,
 107.2; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-05 Cont ID  
Sent By jpearson Date 2019-03-05 Time 14:10 Rev Time 0.00
Received By jpearson Date 2019-03-05 Time 10:34 Sent To  
Notes
2019-03-05 14:10:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ALL RECEPTACLES WITHIN 6 FEET OF A SINK REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8
 2. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-04-08 Cont ID  
Sent By pleduc Date 2019-04-08 Time   Rev Time 0.00
Received By pleduc Date 2019-04-08 Time 13:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-03-05 Cont ID  
Sent By pleduc Date 2019-03-05 Time   Rev Time 0.00
Received By pleduc Date 2019-03-05 Time 13:19 Sent To  
Notes
2019-03-05 13:29:42THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A 001 - UNDER GENERAL NOTES # 1 THERE IS AN
 INDICATION TO THE CITY OF OKEECHOBEE. THIS PROJECT
 APPEARS TO BE IN WEST PALM BEACH.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 2) SHEET A 001 - AT THE TOP OF THE PAGE UNDET TENANT
 IMPROVEMENT IS OKEECHOBEE FL.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 3) SHEET A 001 - THERE IS A CONFLICT INDICATED UNDER
 APPLICABLE CODES: FLORIDA FIRE PREVENTION CODE 2018 VS
 FFPC 2012.
  
 THE CORRECT EDITION WAS APPROVED ON DEC. 31, 2018,
 WHICH INCLUDES NFPA 1, 2015 ED & NFPA 101, 2015 ED,
 WITH FL AMENDMENTS.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 4) SHEET E 1.1 - THERE ARE NO INDICATIONS OF FIRE ALARM
 DEVICES OR EQUIPMENT.
  
 THERE SHOULD BE A FIRE ALARM NOTIFICATION DEVICE IN
 THIS SUITE FOR FIRE SPRINKLER ACTIVATION NOTIFICATION.
  
 PLEASE REVIEW AND ENSURE ANY FIRE ALARM WORK IS UNDER
 SEPARATE SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-15 Cont ID  
Sent By jduprey Date 2019-04-15 Time 16:34 Rev Time 0.00
Received By jduprey Date 2019-04-05 Time 15:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-05 Cont ID  
Sent By thunt Date 2019-03-19 Time 15:14 Rev Time  
Received By cpuell Date 2019-02-27 Time 08:46 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-03-12 Cont ID  
Sent By jwitmer Date 2019-03-12 Time 08:55 Rev Time 0.00
Received By jwitmer Date 2019-03-11 Time 15:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-04-15 Cont ID  
Sent By hmoser Date 2019-04-15 Time 15:16 Rev Time 0.00
Received By hmoser Date 2019-04-15 Time 14:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-03-06 Cont ID  
Sent By ccole Date 2019-03-06 Time 11:12 Rev Time 0.00
Received By ccole Date 2019-03-06 Time 11:12 Sent To  
Notes
2019-03-06 11:23:031ST REVIEW FBC-2017 MECHANICAL
 PERMIT #190121354
 3/6/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLANS SHOW A TYPE II HEAT HOOD IS TO BE
 INSTALLED HOWEVER NO DRAWINGS, DETAILS, AND
 SPECIFICATIONS HAVE BEEN PROVIDED. PLEASE NOTE BECAUSE
 IT IS NOT A TYPE 1 GREASE HOOD, THE INSTALLATION CAN BE
 DONE UNDER THIS PERMIT OR SEPARATE PERMIT. PLEASE
 CLARIFY IF THE VALUE OF THE HOOD- LABOR, MATERIALS,
 EQUIPMENT- ARE INCLUDED IN THE TOAL JOB VALUE OF THIS
 PERMIT, AND IF THE SAME MECHANICAL SUB-CONTRACTOR DOING
 THE HVAC SYSTEM WORK WILL ALSO BE DOING THE HOOD
 INSTALLATION. THE SECOND OPTION IS TO PROVIDE A
 SEPARATE PRIMARY PERMIT AND PLANS. PLEASE CLARIFY.
  
 2) A SEPARATE PERMIT IS REQUIRED FOR THE WALK-IN
 FREEZER. PLEASE PLACE A NOTE ON THE PLANS- SECTION
 107.2.1 WPB.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 CONVECTION OVEN AND ANY OTHER COOKING APPLIANCES TO BE
 LOCATED UNDER THE HOOD- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-11 Cont ID  
Sent By gjohnson Date 2019-04-11 Time 08:10 Rev Time 0.00
Received By gjohnson Date 2019-04-10 Time 16:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-19 Cont ID  
Sent By thunt Date 2019-03-19 Time 13:44 Rev Time 0.00
Received By thunt Date 2019-03-18 Time 17:14 Sent To I
Notes
2019-03-20 13:53:10PLUMBING 1ST REVIEW**DENIED**
  
 1) PROVIDE MANUFACTURES INSTALLATION MANUAL FOR THE NEW
 GREASE INTERCEPTOR. ALSO NOTE ON PLANS A SEPERATE
 PERMIT FOR THE INTERCEPTOR IS REQUIRED. FBC 107.2.1
  
 2) PLEASE RESUBMIT SHT.A-402 AS MOST ALL PRINT IS NOT
 READABLE. FBC 107.3.5
  
 3) THE GRAB BAR ON SHT. A-402 IS SHOWING 33"-36" TO THE
 CENTER. FBC-A 604.5.2 STATES THE 33"-36" IS TO THE
 GRIPPING SURFACE OR TOP/
  
 4) ALL PAGES OF THE PLANS ARE SUBBMITTED ELECTRONICALLY
 ARE REQUIRED TO BE DIGITAL SIGNED BY DESIGNER OF
 RECORED. F.A.C 61G15-23.003. NON EOF THE PLUMBING PAGES
 ARE SIGNED AT ALL.
  
 5) YOUR EXISTING RESTROOMS SHOW CLEAR FLOOR SPACE'S BUT
 THE SINK ENCROACHES INTO THE TOILETS CLEAR FLOOR SPACE
 WHICH IS NOT PERMITTED. FBC-A604.3.2. IS IT YOUR INTENT
 TO MAKE ALL FIXTURES MEET ADA/ FLORIDA ACCESSIBILITY?
  
 6) THE USAGE OF THIS SPACE BEFORE WAS A RESTAURANT
 WHICH IS EXEMPT FROM THE REQUIRED OF HAVE A HI-LOW
 DRINKING FOUNTAIN UNDER FBC-P 410.4. PLEASE PROVIDE A
 HI-LOW DRINKING FOUNTAIN TO COMPLY WITH FBC-P 410.3
  
 7) PROVIDE INSTALLATION MANUAL FOR THE NEW WATER
 HEATER. FBC 107.2.1.
  
 8) WHAT IS THE TOTAL DEVELOPED LENGHT OF HOT WATER
 PIPING FROM THE WATER HEATER TO THE LAST FIXTURE? IT
 OVER 50' A HOT WATER RETURN SYSTEM WOULD BE REQUIRED.
 FBC-P 607.2
  
  
 TIM HUNT
 PLUMBING INSPECTOR/PLUMBING PLAN EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
  
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status P Date 2019-04-26 Cont ID  
Sent By gjohnson Date 2019-04-26 Time 09:48 Rev Time 0.00
Received By gjohnson Date 2019-04-26 Time 09:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-04-17 Cont ID  
Sent By shill Date 2019-04-17 Time 15:57 Rev Time 0.00
Received By shill Date 2019-04-17 Time 15:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-04-15 Cont ID  
Sent By shill Date 2019-04-15 Time 14:34 Rev Time 0.00
Received By shill Date 2019-04-15 Time 14:34 Sent To  
Notes
2019-04-15 14:39:18****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. AFTER ALL REVIEWS HAVE PASSED, ONE PAPER ORIGINAL
 NEEDS TO BE REVIEWED. AS DISCUSSED, THIS CANNOT BE DONE
 UNTIL ALL REVIEWS HAVE PASSED.
  
 ARCH, MECH, ELEC SHEETS - NOT DIGITALLY SIGNED
  
 PLUMBING SHEETS - OK
  
  
  
2019-04-11 08:11:544/11/19 DIG. SIG. ON PLUMB SHT. ARE OK/GPJ
2019-04-09 14:56:09ELECTRICAL PLANS NOT DIGITALLY SIGNED/SEALED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-03-05 Cont ID  
Sent By jpearson Date 2019-03-05 Time 12:04 Rev Time 0.00
Received By jpearson Date 2019-03-05 Time 12:04 Sent To  
Notes
2019-03-06 11:26:53MECHANICAL PLANS NOT ELECTRONICALLY SIGNED AND SEALED
 AS REQUIRED BY SECTION 61G15-23.005 FAC.
2019-03-05 12:04:20EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. AS AN ALTERNATIVE, A PAPER COPY
 SIGNED AND SEALED MAY BE PROVIDED. THE PAPER COPY
 PROVIDE THIS CYCLE IS MISSING SIGNATURE/SEAL ON SEVERAL
 SHEETS. PROVIDE CORRECTION. WPB FBC 107.1; FS 471/481
  
  
2019-02-27 15:14:262/27/19 HARD COPIES OF PLANS IN LIBRARY. LEM

Review Stop Z ZONING
Rev No 2 Status P Date 2019-04-10 Cont ID  
Sent By eschneid Date 2019-04-10 Time 16:58 Rev Time 0.25
Received By eschneid Date 2019-04-10 Time 16:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-03-07 Cont ID  
Sent By eschneid Date 2019-03-07 Time 14:45 Rev Time 0.75
Received By eschneid Date 2019-03-07 Time 14:45 Sent To  
Notes
2019-03-07 14:46:16THE SIGN VISIBLE FROM THE EXTERIOR REQUIRES A SEPARATE
 PERMIT WITH PLANS.