| 2019-03-06 16:52:41 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 19021325 |
| | REVIEWED: MARCH 6, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1) 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION, |
| | CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL |
| | EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS |
| | LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED |
| | BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3 |
| | SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER. |
| | WHICH METHOD IS BEING USED FOR COMPLIANCE? |
| | (PRESCRIPTIVE,WORK AREA OR PERFORMANCE) |
| | |
| | 2) 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR |
| | WORK BEING PERFORMED. |
| | THE PLANS STATE LEVEL 1, BUT THIS WOULD BE A LEVEL 2 |
| | DUE TO THE RE-ARRANGEMENT OF SPACES AND POSSIBLE A |
| | LEVEL 3 IF OVER 50 % OF THE BUILDING IS INCLUDED IN THE |
| | WORK. PLEASE REVIEW AND REVISE TO MEET DEFINITION THAT |
| | APPLIES. |
| | |
| | 3) 1004.1 FBC[B] DESIGN OCCUPANT LOAD. IN DETERMINING |
| | MEANS OF EGRESS REQUIREMENTS, THE NUMBER OF OCCUPANTS |
| | FOR WHOM MEANS OF EGRESS FACILITIES ARE PROVIDED SHALL |
| | BE DETERMINED IN ACCORDANCE WITH THIS SECTION. |
| | ADD OCCUPANT LOAD ON SHEET L1.01 |
| | |
| | 4) 302 FBC[B] WHAT IS THE EXISTING OCCUPANCY AND WHAT |
| | IS THE PROPOSED OCCUPANCY? |
| | PLEASE ADD TO SHEET L1.01 |
| | |
| | 5) 402.1 FBC[A] PROVIDE ACCESSIBLE ROUTE FROM PARKING |
| | LOT. IN ADDITION TO ACCESSIBLE ENTRANCES REQUIRED BY |
| | SECTIONS 1105.1.1 THROUGH 1105.1.7 (PARKING GARAGE |
| | ENTRANCES, ENTRANCES FROM TUNNELS OR ELEVATED WALKWAYS, |
| | RESTRICTED ENTRANCES, ENTRANCES FOR INMATES OR |
| | DETAINEES, SERVICE ENTRANCES AND ENTRANCES TO TENANT |
| | SPACES, DWELLING UNITS AND SLEEPING UNITS), AT LEAST 60 |
| | PERCENT OF ALL PUBLIC ENTRANCES SHALL BE ACCESSIBLE. |
| | SEE THE EXCEPTIONS FOR ENTRANCES TO AREAS NOT REQUIRED |
| | TO BE ACCESSIBLE AND LOADING/SERVICE ENTRANCES THAT ARE |
| | NOT THE ONLY TENANT SPACE ENTRANCE. SHEET L1.01 SHOWS 4 |
| | INCH STEP DOWN AT EACH EXIT. HOW IS ACCESSBLE ROUTE TO |
| | BE PROVIDED, OR WHAT EXEMPTION ALLOWS FOR NO ACCESSIBLE |
| | PATH TO BE PROVIDED? |
| | |
| | 6) 1013.1 FBC[B] SHEET L1.01 SHOWS AN EGRESS PATH GOING |
| | THROUGH TWO EXISTING DOORS AND OUT THE BACK. |
| | PLEASE USE EXIT SIGNS TO INDICATE EGRESS PATH. |
| | |
| | 7) 1017.2 FBC[B] LIMITATIONS. EXIT ACCESS TRAVEL |
| | DISTANCE SHALL NOT EXCEED THE VALUES GIVEN IN TABLE |
| | 1017.2. |
| | |
| | 8) 1017.3 FBC[B] MEASUREMENT. EXIT ACCESS TRAVEL |
| | DISTANCE SHALL BE MEASURED FROM THE MOST REMOTE POINT |
| | WITHIN A STORY ALONG THE NATURAL AND UNOBSTRUCTED PATH |
| | OF HORIZONTAL AND VERTICAL EGRESS TRAVEL TO THE |
| | ENTRANCE TO AN EXIT. |
| | SHOW TRAVEL DISTANCE FROM THE MOST REMOTE POINT. |
| | |
| | 9) 107.3.5 FBC[AMENDED] SHOW THE EXISTING BATHROOMS ON |
| | PLANS AND LABEL ROOMS ACCORDINGLY. |
| | ALSO, SHOW ANY ADA COMPLIANCE THAT IS PROVIDED IN THE |
| | BATHROOMS. |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS. |
| | FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE |
| | REQUIRED. |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |