Plan Review Details - Permit 19021315
Plan Review Stops For Permit 19021315
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-08 Cont ID  
Sent By jduprey Date 2019-05-08 Time 16:50 Rev Time 0.00
Received By jduprey Date 2019-05-08 Time 11:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-21 Cont ID  
Sent By cthroop Date 2019-03-21 Time 08:32 Rev Time 0.00
Received By cthroop Date 2019-03-20 Time 15:36 Sent To  
Notes
2019-03-21 08:52:32BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CORRECT CODE INFO ON PAGE G-101 TO STATE FBC 6TH ED.
 2017.
  
 2. PROPOSED SQ. FT'G. ON PAGE G-101 STATES 250 SQ. FT.
 PLAN PAGE A101 STATES 298 SQ. FT. PLEASE CLARIFY.
  
 3. PROVIDE DETAIL FOR NEW CMU WALL ATTACHMENT TO
 EXISTING COLUMNS.
  
 4. PROVIDE DETAIL OF NEW WINDOW OPENINGS. INCLUDE ROUGH
 OPENINGS - R.O.
  
 5. DESIGNATE USE OF NEW ROOM. IF A BEDROOM, IDENTIFY
 EMERGENCY EGRESS.
  
 6. PROVIDE FRAMING DETAIL FOR NEW SHOWER PANS.
  
 7. PROVIDE LOCATION AND SIZE OF ATTIC SCUTTLE.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-05-10 Cont ID  
Sent By jleahy Date 2019-05-10 Time 16:05 Rev Time 0.00
Received By jleahy Date 2019-05-10 Time 16:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-05-03 Cont ID  
Sent By ppetty Date 2019-05-03 Time 10:15 Rev Time 0.00
Received By ppetty Date 2019-05-03 Time 10:14 Sent To  
Notes
2019-05-03 10:14:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 (S)
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-20 Cont ID  
Sent By jpearson Date 2019-03-20 Time 08:00 Rev Time 0.00
Received By jpearson Date 2019-03-20 Time 07:39 Sent To  
Notes
2019-03-20 08:00:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 (S)
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-04-24 Cont ID  
Sent By thunt Date 2019-04-24 Time 18:10 Rev Time 0.00
Received By thunt Date 2019-04-24 Time 18:10 Sent To  
Notes
2019-04-24 18:10:48SUB GAS PERMIT REQUIRED

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-03-19 Cont ID  
Sent By thunt Date 2019-03-19 Time 07:02 Rev Time 0.00
Received By thunt Date 2019-03-19 Time 07:02 Sent To  
Notes
2019-03-19 07:05:18GAS 1ST REVIEW**DENIED**NOTE - A COMPREHENSIVE REVIEW
 COULD NOT BE DONE AT THIS TIME AND ADDITIONAL PLAN
 REVIEW COMMENTS MAY BE GENERATED UPON THE RE-REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1) YOU SHOW A NEW GAS TANKLESS WATER HEATER BUT DID NOT
 SUBMIT ANY PLANS OR SUPPORTING DOCUMENTS FOR A GAS
 REVIEW. I HAVE INCLUDED A CHECK LIST OF WHAT IS
 REQUIRED TO SUBMIT FOR A GAS REVIEW. FBC 107.3.5
  
  
  
 TIM HUNT
 PLUMBING INSPECTOR/PLUMBING PLAN EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-05-02 Cont ID  
Sent By aborngra Date 2019-05-02 Time 09:59 Rev Time 0.00
Received By aborngra Date 2019-05-02 Time 09:59 Sent To PC
Notes
2019-05-02 09:59:49THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING
 CONDITION(S):
  
 1. ALL WINDOWS SHALL HAVE CLEAR GLASS OR LOW-E GLASS.
 2. ALL DOORS SHALL HAVE CLEAR GLASS OR LOW-E GLASS.
  
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected]
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2019-03-07 Cont ID  
Sent By aborngra Date 2019-03-07 Time 14:07 Rev Time 0.00
Received By aborngra Date 2019-03-07 Time 13:49 Sent To PC
Notes
2019-03-07 14:07:28THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 1. A CERTIFICATE OF APPROPRIATENESS APPLICATION IS
 REQUIRED TO BE SUBMITTED. THE CASE SHALL BE HEARD BY
 THE HISTORIC PRESERVATION BOARD.
  
 A CERTIFICATE OF APPROPRIATENESS IS A SEPARATE PROCESS
 FROM THE BUILDING PERMIT PROCESS. PLEASE VISIT - HTTP:/
 /WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/PLANNING/FORM
 S TO OBTAIN A COPY OF THE CERTIFICATE OF
 APPROPRIATENESS APPLICATION. PLEASE INCLUDE ALL
 INFORMATION REQUIRED UNDER ?ALL OTHER ADDITIONS? ON
 PAGE 2. A $100.00 APPLICATION FEE WILL ALSO BE
 REQUIRED. THE DEADLINES FOR THE HISTORIC PRESERVATION
 BOARD MEETING CAN BE FOUND ON PAGE 3. THE PROPERTY
 OWNER MAY BE INTERESTED IN APPLYING FOR AN AD VALOREM
 TAX EXEMPTION (APPLICATION AVAILABLE AT THE URL ABOVE).
 THE AD VALOREM TAX EXEMPTION PROGRAM ALLOWS THE
 EXEMPTION OF UP TO 100 PERCENT OF THE ASSESSED VALUE OF
 ALL IMPROVEMENTS (INTERIOR AND EXTERIOR) TO HISTORIC
 PROPERTIES RESULTING FROM RENOVATION, RESTORATION, OR
 REHABILITATION OF SUCH PROPERTIES. THE EXEMPTION
 APPLIES ONLY TO CITY AND COUNTY PROPERTY TAXES. ALL
 OTHER TAXING AUTHORITIES LINE ITEMS WILL GO UP.
  
 PLEASE CONTACT STAFF TO DISCUSS PROPOSED ALTERATIONS
 AND ADDITIONS.
  
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-09 Cont ID  
Sent By cthroop Date 2019-05-09 Time 09:42 Rev Time 0.00
Received By cthroop Date 2019-04-16 Time 14:04 Sent To  
Notes
2019-04-17 14:04:47R32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-21 Cont ID  
Sent By cthroop Date 2019-03-21 Time 09:07 Rev Time 0.00
Received By cthroop Date 2019-02-27 Time 15:32 Sent To  
Notes
2019-02-28 15:32:52R03

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-05-10 Cont ID  
Sent By cthroop Date 2019-05-10 Time 15:45 Rev Time 0.00
Received By cthroop Date 2019-05-10 Time 15:45 Sent To  
Notes
2019-05-10 15:46:40MU-2019-014557-000. CT

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-03-21 Cont ID  
Sent By cthroop Date 2019-03-21 Time 08:31 Rev Time 0.00
Received By cthroop Date 2019-03-20 Time 15:36 Sent To  
Notes
2019-03-21 08:32:46PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-05-09 Cont ID  
Sent By cthroop Date 2019-05-09 Time 09:42 Rev Time 0.00
Received By cthroop Date 2019-05-09 Time 09:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-03-21 Cont ID  
Sent By cthroop Date 2019-03-21 Time 08:52 Rev Time 0.00
Received By cthroop Date 2019-03-20 Time 15:36 Sent To  
Notes
2019-03-21 09:07:49MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE EQUIPTMENT MAKE AND MODEL ON PLANS.
 2. PROVIDE EQUIPMENT MAKE, MODEL AND SPECIFICATIONS ON
 MANUAL J ENERGY CALCULATIONS.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 2. IDENTIFY ACCESS TO ATTIC EQUIPMENT.
  
 M1305.1.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 20 FEET (6096 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE NOT LESS THAN 30 INCHES (762 MM) DEEP AND 30
 INCHES (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES
 OF THE APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR
 ACCESS OPENING DIMENSIONS SHALL BE NOT LESS THAN OF 20
 INCHES BY 30 INCHES (508 MM BY 762 MM), AND LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-24 Cont ID  
Sent By thunt Date 2019-04-24 Time 18:10 Rev Time 0.00
Received By thunt Date 2019-04-24 Time 18:10 Sent To  
Notes
2019-04-24 18:11:19SUB PLUMBING PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-03-19 Cont ID  
Sent By thunt Date 2019-03-19 Time 07:02 Rev Time 0.00
Received By thunt Date 2019-03-19 Time 07:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-05-02 Cont ID  
Sent By aborngra Date 2019-05-02 Time 09:59 Rev Time 0.00
Received By aborngra Date 2019-05-02 Time 09:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-03-07 Cont ID  
Sent By aborngra Date 2019-03-07 Time 13:49 Rev Time 0.00
Received By aborngra Date 2019-03-07 Time 13:49 Sent To PC
Notes
2019-03-07 13:49:50PLEASE SEE HISTORIC COMMENTS.