Plan Review Details - Permit 19021265
Plan Review Stops For Permit 19021265
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-05-09 Cont ID  
Sent By pvalenti Date 2019-05-09 Time 08:00 Rev Time 0.00
Received By pvalenti Date 2019-05-09 Time 08:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-04-30 Cont ID  
Sent By pvalenti Date 2019-04-30 Time 17:09 Rev Time 0.00
Received By pvalenti Date 2019-04-30 Time 15:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-03 Cont ID  
Sent By jwitmer Date 2019-04-03 Time 09:38 Rev Time 0.00
Received By jwitmer Date 2019-04-02 Time 11:29 Sent To  
Notes
2019-04-03 09:38:072017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19021265
 ADD: 1851 OKEECHOBEE ROAD
 CONT: THORTON & THORTON
 TEL: 321-229-3406
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. APRIL 03/ 2019
 ACTION: DENIED
  
 1) THE COVERSHEET A00 UNDER THE HEADING OF TYPE OF
 CONSTRUCTION LIST THE BUILDING CONSTRUCTION TYPE AS
 III-B. PLEASE NOTE THE ORIGINAL BUILDING WAS BUILT
 UNDER THE 2001 FBC-B. THE BUILDING WAS DESIGNED AS A
 SHELL, OCCUPANCY TYPE F1 AND THE CONSTRUCTION TYPE IV
 PROTECTED, THIS WAS WHEN THERE WAS 6 BUILDING TYPE
 CLASSIFICATIONS. UNDER THE 2017 CODE THE COMPARISON
 WOULD BE CONSTRUCTION TYPE II-A. PLEASE REVISE THE
 BUILDING TYPE AS IT PERTAINS TO TODAYS BUILDING CODE.
  
 2) THE DEMOLITION PLAN A0-0 HAS A NOTE ON THE EXTERIOR
 WALL, REMOVE CONCRETE WALL AS REQUIRED FOR NEW DOOR.
 THERE IS NO REFERENCE IN THE ARCHITECTURAL PLANS FOR
 THE DESIGN CRITERIA FOR THE NEW DOOR. THIS SHEET
 REFERENCES THE REMOVAL OF THE CONCRETE WALL AS
 REQUIRED. THE PERMIT THIS BUILDING WAS BUILT UNDER
 (03010432) SHOWS IN THE STRUCTURAL SHEETS, THIS IS A
 TILT PANEL WALL SYSTEM, PLEASE PROVIDE ENGINEERING FOR
 THE NEW DOOR OPENING IN THE TILT WALL PANEL. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) THE DEMOLITION PLAN A0-0 HAS A NOTE ( E ) FOR THE
 REMOVAL AND DISCARDING OF AN OVERHEAD DOOR. THE FLOOR
 PLAN A1.0 DOES SHOW WHERE THE OVERHEAD DOOR WAS LOCATED
 AND THE NEW SIDE DOOR POSITIVE AND NEGATIVE PRESSURES.
 THE PLAN DOES NOT GIVE THE MEAN ROOF HEIGHT NOR ANY
 OTHER WIND DESIGN CRITERIA AS TO HOW THESE PRESSURES
 WERE DERIVED? IF THEY ARE VULT OR VASD?
  
 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 3.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
 3.2. RISK CATEGORY.
 3.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
 3.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 4) COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
  
 5) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 7) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 8) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 9) THE SHEET A0-0 DEMOLITION PLAN NOTE ( E ) INDICATES
 THE REMOVAL AND DISCARDING OF AN OVERHEAD DOOR.
 SHEET A1-2 DETAIL 4 DOES PROVIDE A DETAIL OF A NEW
 INSET EXTERIOR WALL AND CEILING SYSTEM:
  
 9A) THE DETAIL INDICATES ANCHORING OF A 6 INCH STEEL
 BOTTOM PLATE TO THE CONCRETE BUT THE PLAN DOES NOT
 INDICATE HOW TO SEAL FROM WATER INTRUSION FROM THE
 RAIN.
 2017 FBC-B 1403.2 WEATHER PROTECTION. EXTERIOR WALLS
 SHALL PROVIDE THE BUILDING WITH A WEATHER-RESISTANT
 EXTERIOR WALL ENVELOPE. THE EXTERIOR WALL ENVELOPE
 SHALL INCLUDE FLASHING, AS DESCRIBED IN SECTION 1405.4.
  
 9B) IN THIS SAME DETAIL THE PLAN INDICATES THE
 INSTALLATION OF HORIZONTAL ROOF / CEILING FRAMING OF A
 NEW VESTIBULE. THE PLAN INDICATES THE USE OF 6 INCH
 STRUCTURAL STUDS AT 16 INCHES ON CENTER. THE DETAIL
 DOES NOT PROVIDE THE GAUGE OF THE STUD NOR THE DESIGN
 STIFFENING LIP LENGTH. THE VERTICAL WALLS BELOW ONLY
 STATES METAL STUDS NO DESIGN CRITERIA. PLEASE SHOW
 COMPLIANCE WITH 2017 FBC-B TABLE 2506.2 ASTM C955,
 SECTION 8.
  
 9C) THE DETAIL ALSO INDICATES THE USE OF 5/8 INCH
 SHEATHING, AND DECKING PLEASE REMEMBER THE BUILDING
 TYPE IS A II-A REQUIRING FIRE RETARDANT TREATED
 PLYWOOD. SEE 2017 FBC-B 603.1.1.2.
  
 9D) THE PLANS IN THIS SAME DETAIL INDICATE THE USE OF
 7/8 INCH STUCCO ON PAPER BACKED LATH. SHOW COMPLIANCE
 WITH 2017 FBC-B SECTION 2510.6 WATER-RESISTIVE
 BARRIERS. WATER-RESISTIVE BARRIERS SHALL BE INSTALLED
 AS REQUIRED IN SECTION 1404.2 AND, WHERE APPLIED OVER
 WOOD-BASED SHEATHING, SHALL INCLUDE A WATER-RESISTIVE
 VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST
 EQUIVALENT TO TWO LAYERS OF WATER-RESISTIVE BARRIER
 COMPLYING WITH ASTM E2556, TYPE I. THE INDIVIDUAL
 LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH THAT EACH
 LAYER PROVIDES A SEPARATE CONTINUOUS PLANE AND ANY
 FLASHING (INSTALLED IN ACCORDANCE WITH SECTION 1405.4)
 INTENDED TO DRAIN TO THE WATER-RESISTIVE BARRIER IS
 DIRECTED BETWEEN THE LAYERS.
  
 9E) WITH THE PLYWOOD DECKING AT THE NEW ENTRY IF THIS
 AREA IS TO BE USED FOR STORAGE, PLEASE PROVIDE THE
 DESIGN FOR THE LOADING, AND THE CALCULATIONS FOR THE
 STRUCTURAL WALLS AND DECKING ABOVE. IF NOT A PLACARD
 WILL BE REQUIRED STATING NO STORAGE.
  
 FBC-B TABLE 1607.1 ( 31) LIGHT 125/ HEAVY 250 POUNDS
 PER SQUARE FOOT.
  
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION
 106.1 LIVE LOADS POSTED. WHERE THE LIVE LOADS FOR WHICH
 EACH FLOOR OR PORTION THEREOF OF A
 COMMERCIAL OR INDUSTRIAL BUILDING IS OR HAS BEEN
 DESIGNED TO EXCEED 50 PSF , SUCH
 DESIGN LIVE LOADS SHALL BE CONSPICUOUSLY POSTED BY THE
 OWNER IN THAT PART OF EACH STORY IN WHICH
 THEY APPLY, USING DURABLE SIGNS. IT SHALL BE UNLAWFUL
 TO REMOVE OR DEFACE SUCH NOTICES.
  
 106.2 ISSUANCE OF CERTIFICATE OF OCCUPANCY. A
 CERTIFICATE OF OCCUPANCY REQUIRED BY SECTION 111
 SHALL NOT BE ISSUED UNTIL THE FLOOR LOAD SIGNS,
 REQUIRED BY SECTION 106.1, HAVE BEEN INSTALLED.
  
 106.3 RESTRICTIONS ON LOADING. IT SHALL BE UNLAWFUL TO
 PLACE, OR CAUSE OR PERMIT TO BE PLACED, ON ANY
 FLOOR OR ROOF OF A BUILDING, STRUCTURE OR PORTION
 THEREOF, A LOAD GREATER THAN IS PERMITTED BY THIS CODE.
  
 10) SHEET A1-0 & A1-2 BOTH SHOW NEW 1 HOUR FIRE RATED
 WALLS, THE DETAIL OF THE 1 HOUR FIRE RATED WALLS SHOW
 THE STUD THICKNESS TO BE A 3 ? INCH STUD AT 16 INCHES
 ON CENTER. PLEASE PROVIDE THE HEIGHT OF THE STUDS TO BE
 INSTALLED IN THIS AREA? THE MAXIMUM HEIGHT OF THE
 TESTED ASSEMBLY IS NOT GIVEN. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 11) SHEET A1-0 SHOWS THE NEW EXIT DOORWAY, EXTERIOR
 LANDING AND NOTE THAT THE FUTURE SIDEWALK IS TO CONNECT
 TO THE STREET. PLEASE PROVIDE THE DISTANCE AND THE
 HEIGHT VARIATION TO THE STREET LEVEL. THE SLOPE MAY
 QUALIFY AS A RAMP AND NEED TO MEET ALL OF THE
 ACCESSIBILITY REQUIREMENTS FOUND UNDER THE 2017
 FBC-ACCESSIBILITY CODE SECTIONS 405. 1-10.
  
 12) SHEET A-10 IN THE NEW 1 HOUR FIRE RATED WALL THE
 PLANS SHOW A NEW OVERHEAD FIRE SHUTTER WITH FUSIBLE
 LINK. FIRE SHUTTERS ARE NORMALLY USED INSTEAD OF A
 DOOR, CREATING THE FIRE RATING OF THE OPENING AS
 REQUIRED BY FBC-B TABLE 716.5. THE ISSUE WITH THIS
 CONFIGURATION WITH THE DOORS BENEATH THE FIRE SHUTTER
 THE FUSIBLE LINK MELTS AND THE SHUTTER STARTS IT
 DOWNWARD DECENT JUST AS SOMEONE STARTS TO GO THROUGH
 THE DOORS BELOW, THE FIRE SHUTTER WILL GET STUCK
 STICKING THE TOP OF THE DOOR ENABLING THE SHUTTER TO
 CLOSE AND NOT PROTECTING THE OPENING.
  
 13) SHEET E2 THE EXISTING EXIT DOOR IN THE WAREHOUSE
 AREA CLOSE TO THE FIRE SPRINKLER ROOM IS MISSING THE
 EXIT SIGN ABOVE THE DOOR. 2017 FBC-B 1013.1 EXIT SIGNS
 WHERE REQUIRED.
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER19030471
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-30 Cont ID  
Sent By jpearson Date 2019-04-30 Time 15:25 Rev Time 0.00
Received By jpearson Date 2019-04-30 Time 14:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-04-08 Cont ID  
Sent By jpearson Date 2019-04-08 Time 14:30 Rev Time 0.00
Received By jpearson Date 2019-04-08 Time 12:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-05-01 Cont ID  
Sent By pleduc Date 2019-05-01 Time   Rev Time 0.00
Received By pleduc Date 2019-05-01 Time 10:54 Sent To  
Notes
2019-05-01 10:56:50THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY AND ALL WORK ON THE FIRE SPRINKLER OR FIRE ALARM
 SYSTEM SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-03-01 Cont ID  
Sent By pleduc Date 2019-03-01 Time   Rev Time 0.00
Received By pleduc Date 2019-03-01 Time 11:08 Sent To  
Notes
2019-03-01 11:50:11THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEETS A 1.0 & A 1.2 - THERE ARE DOORS INDICATED
 WITHIN THE FIRE WALL, 112 & 107B, THAT THE DOOR
 SCHEDULE DOES NOT INDICATE WITH A REQUIRED RATING.
  
 THE DOOR ARE REQUIRED TO HAVE A 1 HOUR FIRE RATING PER
 NFPA 101
  
 8.3.3 FIRE DOORS AND WINDOWS.
 8.3.3.1 OPENINGS REQUIRED TO HAVE A FIRE PROTECTION
 RATING BY TABLE
 8.3.4.2 SHALL BE PROTECTED BY APPROVED, LISTED, LABELED
 FIRE DOOR
 ASSEMBLIES AND FIRE WINDOW ASSEMBLIES AND THEIR
 ACCOMPANYING
 HARDWARE, INCLUDING ALL FRAMES, CLOSING DEVICES,
 ANCHORAGE, AND
 SILLS IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 80,
 STANDARD
 FOR FIRE DOORS AND OTHER OPENING PROTECTIVES, EXCEPT AS
 OTHERWISE SPECIFIED IN THIS CODE.
 8.3.3.1.1 FIRE RESISTANCE?RATED GLAZING TESTED IN
 ACCORDANCE WITH
 ASTM E 119, STANDARD TEST METHODS FOR FIRE TESTS OF
 BUILDING
 CONSTRUCTION AND MATERIALS, OR ANSI/UL 263, STANDARD
 FOR FIRE
 TESTS OF BUILDING CONSTRUCTION AND MATERIALS, SHALL BE
 PERMITTED
 IN FIRE DOOR ASSEMBLIES AND FIRE WINDOW ASSEMBLIES
 WHERE TESTED
 AND INSTALLED IN ACCORDANCE WITH THEIR LISTINGS.
 8.3.3.1.2 NEW FIRE RESISTANCE?RATED GLAZING SHALL BE
 MARKED IN
 ACCORDANCE WITH TABLE 8.3.3.12 AND TABLE 8.3.4.2. SUCH
 MARKING
 SHALL BE PERMANENTLY AFFIXED.
  
 PLEASE REVIEW AND PROVIDE FOR THE REQUIRED FIRE RATING
 AT EACH DOOR.
  
  
  
 2) SHEETS A 1.0 & A 1.2 - THERE IS AN INDICATION OF A
 ROLL-UP DOOR OVER DOUBLE DOOR 101B WITHIN THE FIRE
 WALL. THE DOOR SCHEDULE DOES NOT IDENTIFY A FIRE RATING
 FOR THIS DOUBLE DOOR NOR THE ROLL-UP DOOR.
  
 ONE OR THE OTHER IS REQUIRED TO HAVE THE REQUIRED
 RATING PER THE ABOVE CCODE REFERNECE.
  
 PLEASE REVIEW AND PROVIDE FOR THE REQUIRED FIRE RATING
 FOR ONE OR THE OTHER DOOR.
  
  
  
  
 3) SHEET E 1 - THERE IS NO INDICATION OF A FIRE ALARM
 WORK.
  
 ANY FIRE ALARM WORK, DEMO OR NEW INSTALL SHALL BE UNDER
 SEPARATE SHOP DRAWINGS BY A CERTIFIED FIRE ALARM
 CONTRACTOR.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE.
  
  
  
  
 4) SHEET A 0.0 & A0.1 - THE IS NO INDICATIONS REGARDING
 THE CONTINUE MAINTENANCE AND FUNCTION OF THE FIRE
 SPRINKLER SYSTEM AND FIRE ALARM SYSTEMS.
  
 THESE SYSTEMS SHALL BE MAINTAINED THROUGHOUT DEMO AND
 NEW CONSTRUCTION.
  
 PLEASE REVIEW AND PROVICE AN APPLICABLE NOTE.
  
  
  
 5) SHEET A 1.0 - THE IS AN INDICATION OF A NEW FIRE
 WALL. THIS WALL SHALL BE PROPERLY IDENTIFIED PER NFPA
 101
  
 8.3.2.4 EACH NEW FIRE WALL, FIRE BARRIER, FIRE
 PARTITION, SMOKE
 BARRIER, SMOKE PARTITION, OR ANY OTHER NEW WALL
 REQUIRED TO HAVE
 PROTECTED OPENINGS SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR
 STENCILING ABOVE ANY DECORATIVE CEILING AND IN
 CONCEALED SPACES
 WITH THE WORDING, ?FIRE AND SMOKE BARRIER ? PROTECT
 ALL OPENINGS,? OR SIMILAR LANGUAGE. SUCH SIGNS OR
 STENCILING
 SHALL BE IN 4 INCH HIGH LETTERS, ? INCH STROKE, AND NOT
 MORE THAN 15
 FEET ON-CENTER.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE.
  
  
  
 6) SHEET E 2 - THERE IS AN INDICATION OF AN EXIT SIGN
 OVER DOOR 101B. THIS DOOR IS INDICATED AS HAVING A
 ROLL-UP DOOR OVER IT ON A FUSIBLE LINK.
  
 SHOULD THIS LIND ACTIVATE, THE DOOR WOULD CLOSE AND NOT
 FUNCTION AS AN EXIT. THERE IS AN EXIT DOOR RIGHT NEXT
 TO THIS DOOR.
  
 THE EXIT SIGN OVER THE 101B NEEDS TO BE REMOVED AND
 THIS DOOR WILL REMIAN A CONVENIENCE DOOR.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES AND NARRATIVE.
  
  
  
  
 7) SHEET E 2 - THERE IS A DOOR ON THE SIDE OF THE
 WAREHOUSE THAT IS NOT MARKED AS AN EXIT. THERE ARE NO
 TRAVEL DISTANCES INDICATED WITHIN THE SPACE VERIFYING
 THAT ONLY ONE EXIT IS REQUIRED.
  
  
 PER NFPA 101
  
 42.2.4 NUMBER OF MEANS OF EGRESS. THE NUMBER OF MEANS
 OF
 EGRESS SHALL COMPLY WITH 42.2.4.1 THROUGH 42.2.4.3.
 (SEE ALSO
 SECTION 7.4.)
 42.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL COMPLY
 WITH ANY OF
 THE FOLLOWING:
 (1) IN LOW HAZARD STORAGE OCCUPANCIES, A SINGLE MEANS
 OF EGRESS
 SHALL BE PERMITTED FROM ANY STORY OR SECTION.
 (2) IN ORDINARY HAZARD STORAGE OCCUPANCIES, A SINGLE
 MEANS OF
 EGRESS SHALL BE PERMITTED FROM ANY STORY OR SECTION,
 PROVIDED
 THAT THE EXIT CAN BE REACHED WITHIN THE DISTANCE
 PERMITTED AS A
 COMMON PATH OF TRAVEL.
 (3) ALL BUILDINGS OR STRUCTURES NOT COMPLYING WITH
 42.2.4.1(1) OR
 42.2.4.1(2) AND USED FOR STORAGE, AND EVERY SECTION
 THEREOF
 CONSIDERED SEPARATELY, SHALL HAVE NOT LESS THAN TWO
 SEPARATE
 MEANS OF EGRESS AS REMOTELY LOCATED FROM EACH OTHER AS
 PRACTICABLE.
  
 42.2.5 ARRANGEMENT OF MEANS OF EGRESS. MEANS OF EGRESS,
 ARRANGED IN ACCORDANCE WITH SECTION 7.5, SHALL NOT
 EXCEED THAT
 PROVIDED BY TABLE 42.2.5.
 42.2.6* TRAVEL DISTANCE TO EXITS. TRAVEL DISTANCE,
 MEASURED IN
 ACCORDANCE WITH SECTION 7.6, SHALL NOT EXCEED THAT
 PROVIDED BY
 TABLE 42.2.6.
  
 PLEASE PROVICE TRAVEL DISTANCES TO THE SINGLE EXIT OF
 PROVIDE AN EXIT SIGN OVER THIS DOOR.
  
  
  
  
 8) SHEET A 1.1 - THERE ARE INDICATIONS OF RACKS WITHIN
 THE WAREHOUSE. THE INSTALLATION OF RACKS SHALL BE UNDER
 SEPARATE SHOP DRAWINGS THAT INCLUDE MANUFACTURES SPECS,
 HEIGHT, FASTENING, AND A FIRE SPRINKLER REVIEW OF THE
 STORAGE COMMODITY WRAPPING AND PALLET TYPE.
  
 PLEASE BE SURE A REVIEW IS PROVIDED REGARDING IN-RACK
 FIRE SPRINKLERS REQUIREMENTS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE.
  
  
  
  
 9) SHEET E 2 - WITH THE INSTALLATION OF RACKS THE PATH
 TO THE EXIT(S) MAY NOT BE CLEAR, DIRECTED OR PROPERLY
 ILLUMINATED PER THE CODE.
  
 PER NFPA 101
  
 42.2.8 ILLUMINATION OF MEANS OF EGRESS.
 42.2.8.1 MEANS OF EGRESS SHALL BE ILLUMINATED IN
 ACCORDANCE WITH
 SECTION 7.8.
 42.2.8.2 IN STRUCTURES OCCUPIED ONLY DURING DAYLIGHT
 HOURS, MEANS
 OF EGRESS SHALL BE PERMITTED TO BE ILLUMINATED WITH
 WINDOWS
 ARRANGED TO PROVIDE THE REQUIRED LEVEL OF ILLUMINATION
 ON ALL
 PORTIONS OF THE MEANS OF EGRESS DURING SUCH HOURS, WHEN
 APPROVED
 BY THE AUTHORITY HAVING JURISDICTION.
 42.2.9 EMERGENCY LIGHTING. EMERGENCY LIGHTING SHALL BE
 PROVIDED IN NORMALLY OCCUPIED STORAGE OCCUPANCIES IN
 ACCORDANCE
 WITH SECTION 7.9, EXCEPT FOR SPACES OCCUPIED ONLY
 DURING DAYLIGHT
 HOURS WITH NATURAL ILLUMINATION IN ACCORDANCE WITH
 42.2.8.2.
 42.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL
 HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10.
  
 PLEASE REVIEW AND MAKE CORRECTIONS AS APPLICABLE.
  
  
  
 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-09 Cont ID  
Sent By pvalenti Date 2019-05-09 Time 08:01 Rev Time 0.00
Received By pvalenti Date 2019-05-07 Time 15:25 Sent To  
Notes
2019-05-08 15:26:09RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-06 Cont ID  
Sent By shill Date 2019-05-02 Time 06:40 Rev Time 0.00
Received By shill Date 2019-04-16 Time 14:20 Sent To  
Notes
2019-04-17 14:20:33C09

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-04-09 Time   Rev Time 0.00
Received By lmarchan Date 2019-02-26 Time 16:21 Sent To  
Notes
2019-02-27 16:21:44C13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-04-03 Cont ID  
Sent By jwitmer Date 2019-04-03 Time 09:37 Rev Time 0.00
Received By jwitmer Date 2019-04-02 Time 11:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-04-25 Cont ID  
Sent By ccole Date 2019-04-25 Time 16:33 Rev Time 0.00
Received By ccole Date 2019-04-25 Time 16:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-04-09 Cont ID  
Sent By ccole Date 2019-04-09 Time 15:14 Rev Time 0.00
Received By ccole Date 2019-04-09 Time 15:02 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-05-08 Cont ID  
Sent By thunt Date 2019-05-08 Time 16:50 Rev Time 0.00
Received By thunt Date 2019-05-08 Time 16:50 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-04-24 Cont ID  
Sent By thunt Date 2019-04-24 Time 13:29 Rev Time 0.00
Received By thunt Date 2019-04-24 Time 13:29 Sent To  
Notes
2019-05-06 07:11:18PLUMBING 2ND REVIEW**DENIED**
  
 1) ANSWERED**
  
 2) NOT ADDRESSED**MENS TOILET COMPARTMENT IS MISSING
 THE SINK WITH-IN. SHT'S. A1-1, A2, A3.0 ALL SHOW A
 TOILET COMPARTMENT WITH IN THE TOILET ROOM. ALL TOILET
 COMPARTMENTS SHALL HAVE AN ACCESSIBLE TOILET WITH IN IT
 FBC-A 604.8.1.6
  
 3) NOT ADDRESSED** PROVIDE ALL REQUIRED CLEAR FLOOR
 SPACE AND TURNING SPACE FOR EACH FIXTURE LESS THE MOP
 SINK. BOTH THE DRINKING FOUNTAIN AND BREAK SINK SHALL
 HAVE THE CLEAR FLOOR SPACE PROVIDED.FBC-A 603.2.1,
 606.2, 305, 306
  
 4) ANSWERED**
  
 5) ANSWERED**
  
 7) ANSWERED**
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-05 Cont ID  
Sent By thunt Date 2019-04-05 Time 11:42 Rev Time 0.00
Received By thunt Date 2019-04-05 Time 10:58 Sent To  
Notes
2019-04-05 11:42:42PLUMBING 1ST REVIEW**DENIED**
  
 1) PROVIDE OCCUPANCY LOAD. FBC 107.3.5
  
 2) MENS TOILET COMPARTMENT IS MISSING THE SINK WITH-IN.
 FBC-A 604.8.1.6
  
 3) PROVIDE ALL REQUIRED CLEAR FLOOR SPACE AND TURNING
 SPACE FOR EACH FIXTURE LESS THE MOP SINK. FBC-A
 603.2.1, 606.2, 305, 306
  
 4) PROVIDE MEASUREMENT SHOWING MIRROR WITH BE MAX 40"
 TO THE REFLECTIVE SURFACE.
  
 5) SHT.P1.0 CALLS OUT FOR THE TOILET 18" MIN FROM SIDE
 WALL. THE TOILET SHALL BE 16"-18" FROM SIDE WALL. 18"
 WOULD BE THE MAX ALLOWED. FBC-A 604.2
  
 6) SHT,P1.0 CALLS OUT FOR THE GRAB BARS TO BE MOUNTED
 33"-36" TO THE CENTER. FBC-A 609.4 CALLS FOR THE
 MEASUREMENT TO BE TO THE TOP OF THE GRIPPING SURFACE.
  
 7) PROVIDE MORE DETAIL ON THE DESIGN OF THE SHELF THE
 WATER HEATER IS TO BE STORED ON. LIST MAX WEIGHT THIS
 DESIGN IS CAPABLE OF HANDLING WITH THE HEATER BEING
 FULL OF WATER. FBC 107.2.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2019-05-02 Time   Rev Time 0.00
Received By pgreilic Date 2019-05-02 Time 13:12 Sent To  
Notes
2019-05-02 13:13:35PAUL GREILICH, SENIOR PLANNER
 [email protected]
 561-822-1443

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By pgreilic Date 2019-03-05 Time   Rev Time 0.00
Received By pgreilic Date 2019-03-05 Time 14:14 Sent To  
Notes
2019-03-05 14:23:15PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]