Plan Review Details - Permit 19021240
Plan Review Stops For Permit 19021240
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-03-21 Cont ID  
Sent By dbattles Date 2019-03-21 Time 08:57 Rev Time 0.00
Received By dbattles Date 2019-03-21 Time 08:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-01 Cont ID  
Sent By dbattles Date 2019-03-01 Time 08:29 Rev Time 0.00
Received By dbattles Date 2019-02-28 Time 11:23 Sent To  
Notes
2019-03-01 08:30:31****CORRECTIONS****
 W.P.B. PERMIT: 19021240
 REVIEWED: MARCH 1, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 202.3 FBC[A] ALTERATIONS. WHERE EXISTING ELEMENTS OR
 SPACES OR COMMON AREAS ARE ALTERED, EACH ALTERED
 ELEMENT, SPACE OR AREA SHALL COMPLY WITH THE APPLICABLE
 REQUIREMENTS OF CHAPTER 2 AND SECTION 201.1.1. SEE
 SECTION 208.1 FOR EXISTING PARKING. EXCEPTIONS:
 1. UNLESS REQUIRED BY 202.4, WHERE ELEMENTS OR SPACES
 ARE ALTERED AND THE CIRCULATION PATH TO THE ALTERED
 ELEMENT OR SPACE IS NOT ALTERED, AN ACCESSIBLE ROUTE
 SHALL NOT BE REQUIRED.
 2. IN ALTERATIONS, WHERE COMPLIANCE WITH APPLICABLE
 REQUIREMENTS IS TECHNICALLY INFEASIBLE, THE ALTERATION
 SHALL COMPLY WITH THE REQUIREMENTS TO THE MAXIMUM
 EXTENT FEASIBLE.
  
 -SHEETS ADA 1.0 ? 1.2 SHOW GENERAL DETAILS FOR ADA
 COMPLIANCE. DO ANY OF THESE DETAILS APPLY TO THIS
 PROJECT?
 SEE SECTION 202.3 (2) THAT APPLIES TO ALTERATIONS.
 PLEASE STATE HOW COMPLIANCE ISN?T TECHNICALLY FEASIBLE
 AND WHAT YOU ARE ABLE TO DO TO ACHIEVE THE MAXIMUM
 EXTENT FEASIBLE.
 -SHOW CLEAR SCACES AS APPLICABLE.
 -SHOW AND GRAB BARS THAT ARE BEING INSTALLED AND NOTES
 IF BLOCKING IS BEING INSTALLED.
  
 2) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 FENESTRATION IN-FILL AT RESIDENT ROOMS, OR INDICATE
 THAT YOU WOULD LIKE THEM DEFERED.
  
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS.
 FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE
 REQUIRED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-03-07 Cont ID  
Sent By jpearson Date 2019-03-07 Time 15:49 Rev Time 0.00
Received By jpearson Date 2019-03-07 Time 15:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-03-05 Cont ID  
Sent By pleduc Date 2019-03-05 Time   Rev Time 0.00
Received By pleduc Date 2019-03-05 Time 15:38 Sent To  
Notes
2019-03-05 15:42:36THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET LS 1 - THERE ARE INCORRECT EDITIONS TO THE
 ADOPTED FLORIDA FIRE PREVENTION CODE, NFPA 220 AND 101B
 ARE NOT ADOPTED NOR APPLICABLE FOR THIS REVIEW.
  
 PROPOSED PROJECTS SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101.
  
 THE BELOW LIST ARE THE MOST COMMON REFERENCED CODES:
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2013 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2013 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2013 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2013 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND ADJUST YOUR
 RECORDS.
  
 SHOULD REVISIONS BE NECESSARY PLEASE REVISE WHERE
 APPLICABLE.
  
  
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS.
  
  
  
 3) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-21 Cont ID  
Sent By dbattles Date 2019-03-21 Time 08:58 Rev Time 0.00
Received By dbattles Date 2019-03-19 Time 13:12 Sent To  
Notes
2019-03-20 13:13:08RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-11 Cont ID  
Sent By thunt Date 2019-03-11 Time 10:09 Rev Time 0.00
Received By thunt Date 2019-02-26 Time 16:28 Sent To  
Notes
2019-03-11 08:32:013/11 TO T.HUNT DESK / S.HILL
  
2019-02-27 16:28:12B21

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2019-03-01 Cont ID  
Sent By dbattles Date 2019-03-01 Time 08:30 Rev Time 0.00
Received By dbattles Date 2019-03-01 Time 08:30 Sent To  
Notes
2019-03-01 08:31:17NO INCREASE IN AREA AND NO CHANGE OF OCCUPANCY.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-03-05 Cont ID  
Sent By ccole Date 2019-03-05 Time 10:29 Rev Time 0.00
Received By ccole Date 2019-03-05 Time 09:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-03-20 Cont ID  
Sent By thunt Date 2019-03-20 Time 15:10 Rev Time 0.00
Received By thunt Date 2019-03-20 Time 14:52 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-11 Cont ID  
Sent By thunt Date 2019-03-11 Time 10:09 Rev Time 0.00
Received By thunt Date 2019-03-11 Time 09:16 Sent To I
Notes
2019-03-11 10:09:29PLUMBING 1ST REVIEW**DENIED**
  
 1) THE FOLLOWING SHHETS MUST BE SIGNED AND SEALED. ADA
 1.0, 1.1, 1.2 PER. F.A.C 61G1-16
  
 2) PROVIDE OVERALL DISTANCE FROM WATER HEATER TO NEW
 SINKS. IF THE TOTAL DEVELOPED LENGTH IS OVER 50' A
 RECIRCUATION LINE MUST BE ADDED . INSULATION OF BOTH
 THE RETURN LINE AND HOT WATER LINE IN 1" WOULD BE
 REQUIRED AS CALLED OUT ON SHT.P-0 NOTE #10
  
 3) SHT.ADA 1.2 SHOW'STOILET ROOMS AND ACCESSIBLE
 ACCESSORIES. SHOW ON PLAN WHICH OF THE EXISTING ROOMS
 THIS WILL APPLY TOO. FBC 107.3.5
  
 4) SHOW ON PLAN THE APPROCH AND CLEAR FLOOR SPACE FOR
 THE 3 NEW SINKS AND ANY AND ALL PLUMBING ELEMENTS THAT
 WILL COMPLY WITH FLORIDA ACCESSIBILITY 107.3.5
  
 TIM HUNT
 PLUMBING INSPECTOR/ PLANS EXAMINER
  
 561-805-6711 SAMANTHA HILL*CHIEF PLANS EXAMINER
  
 561-805-6724 GEORGE JOHNSON* PLUMBING PLANS EXAMINER
  

Review Stop Z ZONING
Rev No 1 Status P Date 2019-03-04 Cont ID  
Sent By llouie Date 2019-03-04 Time   Rev Time  
Received By llouie Date 2019-03-01 Time   Sent To  
Notes
2019-03-04 11:26:00- INTERIOR MODIFICATIONS ONLY.
  
 - NO CHANGE TO THE NUMBER OF EXISTING RESIDENT ROOMS.
  
 - SCOPE OF WORK DOES NOT EXCEED 50% OF THE VALUE OF THE
 STRUCTURE.
  
 Z = CS