Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-04-02 Cont ID  
Sent By dbattles Date 2019-04-02 Time 15:08 Rev Time 0.00
Received By dbattles Date 2019-04-02 Time 15:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-03-21 Cont ID  
Sent By dbattles Date 2019-03-21 Time 10:16 Rev Time 0.00
Received By dbattles Date 2019-03-21 Time 10:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-27 Cont ID  
Sent By dbattles Date 2019-02-27 Time 16:50 Rev Time 0.00
Received By dbattles Date 2019-02-27 Time 14:51 Sent To  
Notes
2019-02-27 16:51:33****CORRECTIONS****
 W.P.B. PERMIT: 19021148
 REVIEWED: FEBRUARY 27, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1. 61G1-16.004 FLORIDA ADMINISTRATIVE CODE. TITLE
 BLOCK. A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL
 OR INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS THAT ARE REQUIRED TO BE SIGNED
 AND SEALED. THE TITLE BLOCK MUST, AT A MINIMUM, CONTAIN
 THE FOLLOWING INFORMATION:
 PLEASE RE-PRINT THE COVER PAGE TO INCLUDE THE TITLE
 BLOCK.
  
 2. 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR
 WORK BEING PERFORMED.
  
 3. 501 FBC[EXISTING] PROVIDE EXISTING OCCUPANCY.
 IF NO CHANGE IN OCCUPANCY, PLEASE STATE OCCUPANCY AS NO
 CHANGE FROM PREVIOUS. THIS WILL SATISFY THE IMPACT STOP
 THAT WAS INCLUDED WITH THIS PERMIT REVIEW.
  
 4. 107.5.3 FBC[AMENDED] SHEET A-1 IN CODE INFORMATION
 THAT IT IS USING 2017 FBC 5TH EDITION. PLEASE CHANGE TO
 6TH EDITION. PLEASE ADD LEVEL OF ALTERATION TO DESIGN
 DATA.
  
 5. 107.5.3 FBC[AMENDED] IS THE BUILDING SPRINKLERED OR
 NON SPRINKLERED?
  
 6. 107.3.5 FBC[B] REMOVE NOTE #4 IN SCOPE OF ON SHEET
 A-1 THAT STATES NO CHANGE IN A/C CONFIGURATION.
  
 7. 1005.1 FBC[B] GENERAL. ALL PORTIONS OF THE MEANS OF
 EGRESS SYSTEM SHALL BE SIZED IN ACCORDANCE WITH THIS
 SECTION.
  
 8. 1004.1 FBC[B] SHEET A-1 SHOWS 2248 SF @ 1/80 = 74.8
 PERSONS. PLEASE REVIEW THIS AS THE OCCUPANT LOAD
 DOESN'T MATCH WHAT IS PROVIDED IN TABLE 1004.1.2 OR IN
 NFPA 101.
  
 9. 1004.1 FBC[B] SHEET A-1 IN AREA STATES 1050 SQ. FT
 AND OCCUPANT LOAD STATES 2248 SQ. FT. PLEASE CLARIFY
 THE SQ. FOOTAGE AND IF 1050 IS THE AREA OF WORK STATE
 AS SUCH WITH THE LEVEL OF ALTERATION.
  
 10. 1004.1 FBC[B] PROVIDE LIFE SAFETY TO SHOW NUMBER OF
 EXITS AND COMMON PATH OF TRAVEL.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS.
 FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE
 REQUIRED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-04-02 Cont ID  
Sent By jpearson Date 2019-04-02 Time 14:45 Rev Time 0.00
Received By jpearson Date 2019-04-02 Time 14:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-03-16 Cont ID  
Sent By jpearson Date 2019-03-16 Time 08:51 Rev Time 0.00
Received By jpearson Date 2019-03-16 Time 08:51 Sent To  
Notes
2019-03-16 08:51:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. SCOPE OF WPRK NOT CLEAR ON PLAN. MARK WHAT IS
 EXISTING AND WHAT IS NEW. IF ANY LOAD IS BEING ADDED,
 PROVIDE LOAD CALCULATION TO CONFIRM SERVICE IS
 ADEQUATE. IF NO LOAD IS BEING ADDED, STATE THAT ON
 PLAN. NOTE 5 STATES ALL LIGHTS EXCEPT BATHROOMS TO BE
 SWITCHED FROM PANEL. IF THERE ARE LIGHTING CHANGES,
 AUTOMATIC CONTROL OF LIGHT FIXTURES IS REQUIRED PER
 ENERGY CODE. PROVIDE CLARIFICATION AND/OR CORRECTIONS
 AS NEEDED. WPB FBC 107.2.1; NEC 220; FBC EC C405.2
 (CONFLICT EXIST BETWEEN LETTER PROVIDED AND PLAN.
 LETTER STATES THAT THE CHANDELIERS ARE BEING ADDED, BUT
 THE PLAN SHOWS THEM AS EXISTING. PROVIDE CLARIFICATION
 AND/OR CORRECTION. SHOW LOCATION OF ALL EXISTING ITEMS
 AS WELL AS NEW ITEMS.)
  
 NEW COMMENTS:
  
 2. LOAD CALCULATION PROVIDED IS NOT ACCURATE. THE LOAD
 CALCULATION SHOULD INCLUDE EXISTING AND NEW LOADS TO
 CONFIRM CAPACITY OF SERVICE IS ADEQUATE. PLAN STATES AC
 IS EXISTING, BUT NO LOAD IS SHOWN FOR THAT. INCLUDE ALL
 LOADS. NEC 215.2, 220, 408.30
 3. SWITCHIHNG OF LIGHT FIXTURES NOT SHOWN. PROVIDE
 CORRECTION. WPB FBC 107.2.1
 4. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-28 Cont ID  
Sent By jpearson Date 2019-02-28 Time 07:55 Rev Time 0.00
Received By jpearson Date 2019-02-28 Time 07:35 Sent To  
Notes
2019-02-28 07:55:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SCOPE OF WPRK NOT CLEAR ON PLAN. MARK WHAT IS
 EXISTING AND WHAT IS NEW. IF ANY LOAD IS BEING ADDED,
 PROVIDE LOAD CALCULATION TO CONFIRM SERVICE IS
 ADEQUATE. IF NO LOAD IS BEING ADDED, STATE THAT ON
 PLAN. NOTE 5 STATES ALL LIGHTS EXCEPT BATHROOMS TO BE
 SWITCHED FROM PANEL. IF THERE ARE LIGHTING CHANGES,
 AUTOMATIC CONTROL OF LIGHT FIXTURES IS REQUIRED PER
 ENERGY CODE. PROVIDE CLARIFICATION AND/OR CORRECTIONS
 AS NEEDED. WPB FBC 107.2.1; NEC 220; FBC EC C405.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-04-02 Cont ID  
Sent By pleduc Date 2019-04-02 Time   Rev Time 0.00
Received By pleduc Date 2019-04-02 Time 13:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-03-14 Cont ID  
Sent By pleduc Date 2019-03-14 Time   Rev Time 0.00
Received By pleduc Date 2019-03-14 Time 12:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-02-27 Cont ID  
Sent By pleduc Date 2019-02-27 Time   Rev Time 0.00
Received By pleduc Date 2019-02-27 Time 11:10 Sent To  
Notes
2019-02-27 11:32:39THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET 1 OF 4 - THERE IS NO ADDRESS OF THE OCCUPANCY
 ON THIS SHEET.
  
 PLEASE PROVIDE THE OCCUPANCY ADDRESS ON THIS SHEET.
  
  
  
 2) SHEET 1 OF 4 - THERE IS AN INDICATION OF THIS SHEET,
 1 OF 4; HOWEVER, THERE ARE ONLY THREE SHEETS SUBMITTED
 AND ARE INDICATED AS 2 OF 3 AND 3 OF 3.
  
 PLEASE CORRECT TO THE APPLICABLE PAGE(S) SUBMITTED.
  
  
  
 3) THERE IS NO REFERNCE TO A FIRE CODE INDICATED ON ANY
 SHEET.
  
 PROPOSED PROJECTS SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101.
  
  
 PLEASE REIVE AND ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE UNDER CODE INFORMATION.
  
  
  
 3) SHEET 1 OF 4 - THERE IS AN INDICATION OF THE
 OCCUPANCY CLASSIFICATION AS "B" (BUSINESS); HOWEVER,
 UNDER THE OCCUPANCY LOAD THERE IS AN INDICATION 1/80.
  
 PER THE FFPC, NFPA 101, CH 7, TABLE 7.3.1.2, A BUSINESS
 OCCUPANCY SHALL CALCULATE AT 1/100.
  
 ADDITIONALLY, A STORAGE/OFFICE IS INDICATED AND BASED
 ON THE INTENDED USE MAY CLACULATE AT 1/200.
  
 PLEASE REVIEW AMD CORRECT AS APPLICABLE.
  
  
  
 4) SHEET 2 OF 3 - THERE ARE NO EXITS SIGNS INDICATED
 BUT WILL BE VERIFIED ON INSPECTION IF THEY ARE
 EXISTING.
  
 PER NFPA 101, CH 7
  
 7.10 MARKING OF MEANS OF EGRESS.
 7.10.1 GENERAL.
 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE
 MARKED IN
 ACCORDANCE WITH SECTION 7.10 WHERE REQUIRED IN CHAPTERS
 11
 THROUGH 43.
  
 PLEASE ENSURE THAT EXITS ARE PROPERLY MARKED.
  
  
  
 5) SHEET 2 OF 3 - A REAR DOOR LEADING INTO A
 STORAGE/OFFICE SPACE WITH AN EXTERIOR DOOR LEADING OUT
 OF THE BUILDING IS INDICATED.
  
 PER NFPA 101 CH 7
  
 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND
 7.2.1.5.
 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH
 KITCHENS,
 STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS 36 AND
 37,
 RESTROOMS, CLOSETS, BEDROOMS OR SIMILAR SPACES, OR
 OTHER ROOMS OR
 SPACES SUBJECT TO LOCKING, UNLESS PASSAGE THROUGH SUCH
 ROOMS OR
 SPACES IS PERMITTED FOR THE OCCUPANCY BY CHAPTER 18,
 19, 22, OR 23.
  
 AN EXIT SIGN OVER THIS STORAGE/OFFICE DOOR WOULD NOT BE
 APPLICABLE IF THE ROOM IS USED FOR GENERAL STORAGE.
  
 AN EXIT SIGN OVER THE EXTERIOR DOOR WOULD BE
 APPLICABLE.
  
  
  
 6) SHEET 1 OF 4 - THERE IS AN INDICATION LABELD "AREA"
 1050 S.F. A/C; HOWEVER, THERE IS A SQ 2248 INDICATED
 FOR OCCUPANCY.
  
 PLEASE REVIEW AND CORRECT OR JUSITFY WHAT THE SQ IS.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-04-02 Time   Rev Time 0.00
Received By lmarchan Date 2019-03-29 Time 13:26 Sent To  
Notes
2019-04-01 13:26:09B22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-21 Cont ID  
Sent By dbattles Date 2019-03-21 Time 10:17 Rev Time 0.00
Received By dbattles Date 2019-03-11 Time 11:01 Sent To  
Notes
2019-03-12 11:05:43B17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-03-01 Time   Rev Time 0.00
Received By lmarchan Date 2019-02-25 Time 14:11 Sent To  
Notes
2019-02-26 14:11:57B18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2019-03-21 Cont ID  
Sent By dbattles Date 2019-03-21 Time 10:17 Rev Time 0.00
Received By dbattles Date 2019-03-21 Time 10:17 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-02-27 Cont ID  
Sent By dbattles Date 2019-02-27 Time 16:52 Rev Time 0.00
Received By dbattles Date 2019-02-27 Time 16:52 Sent To  
Notes
2019-02-27 16:53:16IF NO CHANGE IN OCCUPANCY, THERE WILL BE NO IMPACT
 FEES.
 SEE COMMENT IN BUILDING TO SUPPLY EXISTING OCCUPANCY.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-04-02 Cont ID  
Sent By ccole Date 2019-04-02 Time 16:46 Rev Time 0.00
Received By ccole Date 2019-04-02 Time 16:19 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-03-15 Cont ID  
Sent By ccole Date 2019-03-15 Time 16:19 Rev Time 0.00
Received By ccole Date 2019-03-15 Time 16:14 Sent To  
Notes
2019-03-15 16:24:412ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19021148
 3/15/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A3: 2ND REQUEST FOR RETURN AIR FROM THE STUDIOS-
 SECTION 601.6 FBC M
  
 2) A3: 2ND REQUEST FOR A DUCT SMOKE DETECTOR TO BE
 INSTALLED IN THE SUPPLY SYSTEM OF THE 5 TON AC SYSTEM.
 PROVIDE A SYMBOL TO SHOW THE LOCATION- SECTION 606.2.1
 FBC M.
  
 3) A3: SHOW THE NEW DRESSING ROOM EXHAUST DUCT RUNS AND
 TERMINATION LOCATIONS- SECTION 501.3 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-03-01 Cont ID  
Sent By ccole Date 2019-03-01 Time 10:43 Rev Time 0.00
Received By ccole Date 2019-03-01 Time 10:40 Sent To  
Notes
2019-03-01 10:56:571ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19021148
 3/1/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1: REFER TO SECTION 301.1 FBC EX AND INDICATE
 ON THE PLAN WHICH METHOD OF COMPLIANCE WILL BE USED FOR
 THE PROPOSED PROJECT.
  
 2) A3: PROVIDE THE TYPES AND SIZES OF NEW DUCTWORK
 SUPPLYING AIR TO THE STUDIOS AND DRESSING ROOMS-
 SECTION 603 FBC M.
  
 3) A3: PROVIDE RETURN AIR FROM THE STUDIOS- SECTION
 601.6 FBC M
  
 4) A3: PROVIDE EXHAUST FOR THE DRESSING ROOMS AT A RATE
 OF .25 CFMS PER SF.- SEE TABLE 403.3.1.1 FBC M.
  
 5) A3: A DUCT SMOKE DETECTOR IS REQUIRED IN THE SUPPLY
 AIR SYSTEM OF THE 5-TON AC SYSTEM PER SECTION 606.2.1.
 PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE
 MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS ARE NOT
 CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  