Plan Review Details - Permit 19021022
Plan Review Stops For Permit 19021022
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-03-21 Cont ID  
Sent By dbattles Date 2019-03-21 Time 15:49 Rev Time 0.00
Received By dbattles Date 2019-03-21 Time 15:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-28 Cont ID  
Sent By dbattles Date 2019-02-28 Time 08:20 Rev Time 0.00
Received By dbattles Date 2019-02-28 Time 08:06 Sent To  
Notes
2019-02-28 08:20:45****CORRECTIONS****
 W.P.B. PERMIT: 19021022
 REVIEWED: FEBRUARY 28, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1. SHEET A000 BUILDING CODE DATA STATES NUMBER OF EXITS
 REQUIRED = 2 AND NUMBER PROVIDED = 1.
 -PLEASE UPDATE IF THIS IS REVERSED.
  
 2. SHEET A000 BUILDING CODE DATA SHOWS OCCUPANY DATA.
 VERIFY IF THE LINE STOCKROOM SHOULD SAY 15 PEOPLE. I
 THINK IT GOES IN LINE BELOW TOTAL OCCUPANT LOAD.
 -ADJUST TOTAL IF NEEDED TO INCLUDE STOCK ROOM TO SALES
 AREA + TOILET ROOMS LINE.
  
 3. 501 FBC[EXISTING] PROVIDE EXISTING OCCUPANCY.
 -IF NO CHANGE IN OCCUPANCY, PLEASE STATE OCCUPANCY AS
 NO CHANGE FROM PREVIOUS. THIS WILL SATISFY THE IMPACT
 STOP THAT WAS INCLUDED WITH THIS PERMIT REVIEW.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-03-16 Cont ID  
Sent By jpearson Date 2019-03-16 Time 08:05 Rev Time 0.00
Received By jpearson Date 2019-03-16 Time 08:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-28 Cont ID  
Sent By jpearson Date 2019-02-28 Time 07:34 Rev Time 0.00
Received By jpearson Date 2019-02-28 Time 06:55 Sent To  
Notes
2019-02-28 07:34:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLANS NEED APPROVAL FROM PALM BEACH OUTLETS
 MANAGEMENT PRIOR TO APPROVAL. WPB FBC 107.2.1
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4
 3. IF THERE IS ANY LOAD BEING ADDED, PROVIDE LOAD
 CALCULATION FOR SERVICE, INCLUDE EXISTING AND NEW LOADS
 TO CONFIRM CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2,
 220, 408.30
 4. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-02-26 Cont ID  
Sent By scaldero Date 2019-02-26 Time 11:33 Rev Time 0.00
Received By scaldero Date 2019-02-26 Time 11:27 Sent To  
Notes
2019-02-26 11:33:46PERMIT # 19021022
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 2) ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 3) EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED
 WITH SIGNS OR STENCILING READING FIRE BARRIER-PROTECT
 ALL OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 4) PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 5) SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO
 THE FIRE ALARM AND SPRINKLER SYSTEM.
  
 6) WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-21 Cont ID  
Sent By dbattles Date 2019-03-21 Time 15:49 Rev Time 0.00
Received By dbattles Date 2019-03-11 Time 14:19 Sent To  
Notes
2019-03-13 14:19:44B18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-05 Cont ID  
Sent By cpuell Date 2019-03-05 Time 13:17 Rev Time 0.00
Received By cpuell Date 2019-02-22 Time 14:51 Sent To  
Notes
2019-02-25 14:51:46B15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-03-21 Cont ID  
Sent By dbattles Date 2019-03-21 Time 15:47 Rev Time 0.00
Received By dbattles Date 2019-03-21 Time 15:47 Sent To  
Notes
2019-03-21 15:48:47PBC REVIEWED, STAMPED AND NO CHANGE IN USE OR AREA.
 NO MU NUMBER BECAUSE NO FEES CHARGED.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-02-28 Cont ID  
Sent By dbattles Date 2019-02-28 Time 08:20 Rev Time 0.00
Received By dbattles Date 2019-02-28 Time 08:20 Sent To  
Notes
2019-02-28 08:21:40109 FBC[AMENDED] PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. ?CALL (561) 233-5025. ?UPON APPROVAL, YOU
 MAY CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. ?PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop Z ZONING
Rev No 2 Status P Date 2019-03-19 Cont ID  
Sent By eschneid Date 2019-03-19 Time 11:21 Rev Time 0.25
Received By eschneid Date 2019-03-19 Time 09:29 Sent To  
Notes
2019-03-19 11:21:46THE SIGNS REQUIRE SEPARATE PERMITS WITH PLANS.

Review Stop Z ZONING
Rev No 1 Status F Date 2019-03-04 Cont ID  
Sent By eschneid Date 2019-03-04 Time 16:31 Rev Time 0.25
Received By eschneid Date 2019-03-04 Time 16:31 Sent To PC
Notes
2019-03-04 16:47:12FAILED
  
 1) THE LANDLORD APPROVAL STAMP IS NOT PROVIDED ON THE
 SUBMITTED PLANS.
  
 2) THE SIGNS REQUIRE SEPARATE PERMITS WITH PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]