| 2019-03-13 08:44:18 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19021011 |
| | ADD: 1400 CENTREPARK BLVD. / SUITE: 305 |
| | CONT: CHANDLER CONSTRUCTION |
| | TEL: 561-791-6934 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. MARCH 13/ 2019 |
| | ACTION: DENIED |
| | |
| | 1400 CENTREPARK IS A 10 STORY HIGHRISE/ CONSTRUCTION |
| | TYPE I-A. |
| | |
| | 2017 FBC-EXISTING BUILDING CODE LEVEL 2 ALTERATION. |
| | SECTION: 803.2.2 SUPPLEMENTAL SHAFT AND FLOOR OPENING |
| | ENCLOSURE REQUIREMENTS. WHERE THE WORK AREA ON ANY |
| | FLOOR EXCEEDS 50 PERCENT OF THAT FLOOR AREA, THE |
| | ENCLOSURE REQUIREMENTS OF SECTION 803.2 SHALL APPLY TO |
| | VERTICAL OPENINGS OTHER THAN STAIRWAYS THROUGHOUT THE |
| | FLOOR. |
| | EXCEPTION: VERTICAL OPENINGS LOCATED IN TENANT SPACES |
| | THAT ARE ENTIRELY OUTSIDE THE WORK AREA. |
| | |
| | 1) PLEASE BE AWARE IN MARCH 2011 THERE WAS ISSUED AN |
| | INTERIOR DEMO PERMIT (11030687) FOR THE WHOLE OF THE |
| | 3RD FLOOR WITH THE EXCEPTION OF THE BUILDING CORE |
| | COMPONENTS AND A COMMON CORRIDOR. WITH THIS ACTION IT |
| | WOULD ENACT THE REQUIREMENTS FOR CODE COMPLIANCE WITH |
| | THE 2017 EXISTING BUILDING CODE 803.2.2 SUPPLEMENTAL |
| | SHAFT AND FLOOR OPENING ENCLOSURE REQUIREMENTS. YOU |
| | CANNOT ENACT THIS REQUIREMENT ON THE DEMO-PERMIT SINCE |
| | IT IS FOR THE REMOVAL OF MATERIALS, BUT IS ENACTED ON |
| | THE TENANT BUILD-OUTS. |
| | IN THE 2017 FBC-B SECTION 1016.2 EGRESS THROUGH |
| | INTERVENING SPACES. EGRESS THROUGH INTERVENING SPACES |
| | SHALL COMPLY WITH THIS SECTION. |
| | 1. EXIT ACCESS THROUGH AN ENCLOSED ELEVATOR LOBBY IS |
| | PERMITTED. ACCESS TO NOT LESS THAN ONE OF THE REQUIRED |
| | EXITS SHALL BE PROVIDED WITHOUT TRAVEL THROUGH THE |
| | ENCLOSED ELEVATOR LOBBIES REQUIRED BY SECTION 3006. |
| | WHERE THE PATH OF EXIT ACCESS TRAVEL PASSES THROUGH AN |
| | ENCLOSED ELEVATOR LOBBY, THE LEVEL OF PROTECTION |
| | REQUIRED FOR THE ENCLOSED ELEVATOR LOBBY IS NOT |
| | REQUIRED TO BE EXTENDED TO THE EXIT UNLESS DIRECT |
| | ACCESS TO AN EXIT IS REQUIRED BY OTHER SECTIONS OF THIS |
| | CODE. |
| | |
| | 2) PLEASE ALSO NOTE THE LAST KNOWN (PERMITTED) WORK ON |
| | THIS FLOOR WAS THE DEMO-PERMIT 11030687. THE DOORS ON |
| | BOTH SIDES OF THE ELEVATOR LOBBY ARE SHOWN TO BE A |
| | SINGLE SWING DOOR NOT DOUBLE DOORS AND THE REMOVAL OF A |
| | DOOR AND FRAME BETWEEN THE RESTROOMS AND ELEVATOR |
| | LOBBY. THE DEMO PERMIT INDICATED THAT ONLY THE DOOR WAS |
| | TO BE REMOVED FROM THE DOOR FRAME. WE BELIEVED THAT ON |
| | THE TENANT BUILDOUT A NEW DOOR WAS TO BE INSTALLED. |
| | WORK COMPLETED WITHOUT THE BENEFIT OF A PERMIT. |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 105.1 PERMITS REQUIRED. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |