Plan Review Details - Permit 19021006
Plan Review Stops For Permit 19021006
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-05-24 Cont ID  
Sent By jgomez Date 2019-05-24 Time 10:41 Rev Time 0.00
Received By jgomez Date 2019-05-23 Time 18:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-08 Cont ID  
Sent By jgomez Date 2019-05-08 Time 13:47 Rev Time 0.00
Received By jgomez Date 2019-05-08 Time 13:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-22 Cont ID  
Sent By jgomez Date 2019-03-21 Time 18:13 Rev Time 0.00
Received By jgomez Date 2019-03-21 Time 18:13 Sent To  
Notes
2019-03-22 15:53:36BUILDING REVIEW COMMENTS:
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- LIFE SAFETY PLAN SHEET A008 IS SHOWING EGRESS TRAVEL
 DISTANCE FROM POINT C TO EXIT #2 PASSING THRU THE WORK
 AREA ROOM. LIFE SAFETY PLAN AND ELECTRICAL PLAN ARE
 MISSING THE EXIT SIGNS SHOWING THE EGRESS PATH AT THIS
 AREA. SEC. 1013.1 FBC. SHOW THE REQUIRED EXIT SIGNS.
  
 2- DOOR #13 IN THE BREAK ROOM AREA DOESN'T COMPLY WITH
 THE DOOR MANEUVERING CLEARANCE REQUIRED BY SEC. 404.2.4
 FBC-ACCESSIBILITY ON THE PULL SIDE. REVISE AS REQUIRED.
  
 3- CHECK-IN COUNTER NEEDS TO COMPLY EITHER WITH SEC.
 904.4.1 FBC-ACCESSIBILITY FOR PARALLEL APPROACH OR SEC.
 904.4.2 FBC-ACCESSIBILITY FOR FORWARD APPROACH. REVISE
 PLANS AND DETAIL 1/A503 AS REQUIRED.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-05-01 Cont ID  
Sent By jleahy Date 2019-05-01 Time 14:09 Rev Time 0.00
Received By jleahy Date 2019-05-01 Time 12:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-03-12 Cont ID  
Sent By jleahy Date 2019-03-12 Time 14:58 Rev Time 0.00
Received By jleahy Date 2019-03-12 Time 14:58 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2019-05-01 Cont ID  
Sent By jleahy Date 2019-05-01 Time 14:10 Rev Time 0.00
Received By jleahy Date 2019-05-01 Time 14:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-04-29 Cont ID  
Sent By pleduc Date 2019-04-29 Time   Rev Time 0.00
Received By pleduc Date 2019-04-29 Time 09:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-03-04 Cont ID  
Sent By pleduc Date 2019-03-04 Time   Rev Time 0.00
Received By pleduc Date 2019-03-04 Time 15:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-06-03 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-15 Time 09:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-14 Cont ID  
Sent By shill Date 2019-05-14 Time 17:32 Rev Time 0.00
Received By shill Date 2019-04-19 Time 15:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-16 Cont ID  
Sent By shill Date 2019-04-16 Time 17:24 Rev Time 0.00
Received By shill Date 2019-02-25 Time 09:51 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-05-24 Cont ID  
Sent By shill Date 2019-05-24 Time 06:26 Rev Time 0.00
Received By shill Date 2019-05-15 Time 08:21 Sent To  
Notes
2019-05-24 06:27:175/24 PLAN STAMPED, NO FEE DUE PER EMAIL FROM W.SWOOPE
 MU-2019-015105-0000
  
  
2019-05-15 08:21:545/15/19 SENT EMAIL TO IMPACT FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-04-16 Cont ID  
Sent By shill Date 2019-04-16 Time 17:22 Rev Time 0.00
Received By shill Date 2019-04-16 Time 17:22 Sent To  
Notes
2019-04-16 17:22:27****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
  
 IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-06-03 Cont ID  
Sent By ccole Date 2019-06-03 Time 10:52 Rev Time 0.00
Received By ccole Date 2019-06-03 Time 10:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-05-01 Cont ID  
Sent By ccole Date 2019-05-01 Time 10:43 Rev Time 0.00
Received By ccole Date 2019-05-01 Time 10:43 Sent To  
Notes
2019-05-01 10:46:382ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19021006
 5/1/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #1 FROM THE 1ST REVIEW WAS NOT COMPLETELY
 ADDRESSED- SEE BELOW AND COMPLY.
  
 1) SHEETS M0003 & M101: PROVIDE EXHAUST VENTILATION
 CALCULATIONS FOR EF-1, EF-2, EF-3, & EF-6, AND A
 SEQUENCE OF OPERATION FOR EACH FAN- TABLE 403.3.1.1 FBC
 M. A) INDICATE HOW MAKEUP AIR IS BEING PROVIDED FOR
 EACH SYSTEM.
  
 2) M101, MED GAS STORAGE EXHAUST: A) THE FIRE DAMPER IS
 PROHIBITED IN THE HAZARDOUS EXHAUST SYSTEM- SECTION
 510.7.1 FBC M. B) THE EXHAUST DUCT SHALL BE ENCLOSED IN
 1-HR FIRE-RESISTANT RATED CONSTRUCTED FROM THE POINT OF
 PENETRATION OF THE FIRE-RATED WALL TO THE OUTLET
 TERMINAL- SECTION 510.7.3 FBC M. C) THE EXHAUST DUCT
 SHALL BE CONSTRUCTED OF G90 GALVANIZED STEEL OR
 NON-METALLIC MATERIALS THAT EXHIBIT A FLAME SPREAD
 INDEX OF 25 AND A SMOKE-DEVELOPED INDEX OF 50 OR LESS
 SECTION 510.9 FBC M. D) MAKEUP AIR SHALL BE PROVIDED AT
 A RATE APPROXIMATELY EQUAL TO THE RATE THAT AIR IS
 BEING EXHAUSTED BY THE SYSTEM- SECTION 510.6.5 FBC M.
 E) PROVIDE THE SEQUENCE OF OPERATION FOR EF-3- SEE
 COMMENT #1 ABOVE.
  
 3) M002: INCOMPLETE DETAILS HAVE BEEN PROVIDED FOR
 MOUNTING THE EF-3 ROOF FAN AND CURB, AND NO DETAILS
 HAVE BEEN PROVIDED FOR RH-1- SEE SECTION 301.15 FBC M
 AND COMPLY. PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 THE INSTALLATIONS, COMPLETE MOUNTING AND ANCHORING
 DETAILS, AND SUBMIT FL. PRODUCT APPROVALS AND/OR
 MIAMI-DADE NOA'S FOR THE UNITS-= RULE 9N-3 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-03-26 Cont ID  
Sent By ccole Date 2019-03-26 Time 15:21 Rev Time 0.00
Received By ccole Date 2019-03-26 Time 13:15 Sent To  
Notes
2019-03-26 16:24:391ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19021006
 3/26/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M0003 & M101: PROVIDE EXHAUST VENTILATION
 CALCULATIONS FOR EF-1, EF-2, EF-3, & EF-6, AND A
 SEQUENCE OF OPERATION FOR EACH FAN- TABLE 403.3.1.1 FBC
 M. A) INDICATE HOW MAKEUP AIR IS BEING PROVIDED FOR
 EACH SYSTEM AND PROVIDE AIR BALANCE CALCULATIONS-
 SECTION 501.4 FBC M.
  
 2) M101: AUTOMATIC SHUTOFF DAMPERS, EITHER MOTORIZED OR
 GRAVITY, SHALL BE PROVIDED FOR THE O/A SUPPLY DUCTS TO
 THE HP'S- SECTION C403.2.4.3 FBC-17 EC
  
 3) M101: INDICATE THE TOTAL NUMBER OF CYINDERS AND
 TOTAL CU.FT. OF OXYGEN AND NITROUS OXIDE GAS TO BE
 STORED IN THE MED GAS CLOSET SECTION 307.1 FBC B. A)
 INDICATE HOW THE CYLINDERS WILL BE SECURED IN THE
 CLOSET.
  
 4) M101: NOTE 1 INDICATES CONDENSATE TO BE DRAINED INTO
 THE CITY SANITARY WHICH IS PROHIBITED PER SECTION
 90-126 WPB CODE OF ORDINANCES. PLEASE PROVIDE A
 COMPLETE CONDENSATE DISPOSAL PLAN FOR ALL OF THE
 HANDLERS- SECTION 307.2.1 FBC M.
  
 5) M002: PROVIDE COMPLETE ANCHORING AND MOUNTING
 DETAILS FOR THE FANS AND FAN CURBS- SECTION 301.15 FBC
 M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status P Date 2019-04-25 Cont ID  
Sent By gjohnson Date 2019-04-25 Time 17:40 Rev Time 0.00
Received By gjohnson Date 2019-04-25 Time 17:40 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2019-03-28 Cont ID  
Sent By gjohnson Date 2019-03-28 Time 07:27 Rev Time 0.00
Received By gjohnson Date 2019-03-28 Time 07:27 Sent To  
Notes
2019-03-28 07:59:261ST REVIEW: 19021006
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 MED GAS COMMENTS:
  
 1. PROVIDE ROOF DRAWING SHOWING DISTANCE FROM VACUUM
 EXHAUST TO AIR INTAKES. PER NFPA 99
 2. PLEASE STATE ON PLAN WHAT CATEGORY THE MED GAS
 SYSTEM IN BEING DESIGNED FOR. PER NFPA 99
 3. PROVIDE NOTE ON THE PLAN THE CONTRACTOR AND
 INSTALLER SHALL BE MED GAS CERTIFIED AND SHALL PROVIDE
 CERTIFICATION FOR PERMIT ISSUANCE AND INSPECTIONS. PER
 FAC 61G4-15.031(1)(4A)(4B)
 4. PROVIDE ISOMETRIC DRAWING FOR MED GAS INCLUDING
 VACUUM EXHAUST. WPB AMEND TO FBC 107.3.5.1.3(13)
 5. PROVIDE PIPING DETAIL OF CONTROL VALVES AND TANK
 MANIFOLD ALSO DETAIL OF HOW TANK ARE SECURED. PER WPB
 AMEND TO FBC 107.2.1 AND NFPA 99
 6. NOTE ON THE PLAN THE NUMBER AND SIZE OF TANKS. PER
 WPB AMEND TO FBC 107.2.1 AND NFPA 99
 7. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION
 GUIDES FOR ALL MED GAS EQUIPMENT. PER WPB AMEND TO FBC
 107.2.1 AND NFPA 99
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-25 Cont ID  
Sent By gjohnson Date 2019-04-25 Time 18:03 Rev Time 0.00
Received By gjohnson Date 2019-04-25 Time 14:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-28 Cont ID  
Sent By gjohnson Date 2019-03-28 Time 07:25 Rev Time 0.00
Received By gjohnson Date 2019-03-25 Time 15:58 Sent To  
Notes
2019-03-28 07:26:261ST REVIEW: 19021006
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1.PROVIDE DETAIL SHOWING MOUNTING HEIGHTS OF THE GRAB
 BARS 33" MIN TO 36" TO THE TOP OF THE GRIPPING SURFACE.
 PER FBC ACC 609.4
 2.PROVIDE ISOMETRIC DRAWING FOR WATER INCLUDING VALVES
 ON DROPS DIRECTION OF FLOW AND LABEL HOT COLD AND
 RETURN. PER WPB AMEND TO FBC 107.3.5.1.3(13)
 3. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-05-23 Cont ID  
Sent By shill Date 2019-05-23 Time 16:21 Rev Time 0.00
Received By shill Date 2019-05-23 Time 16:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-05-14 Cont ID  
Sent By shill Date 2019-05-14 Time 17:37 Rev Time 0.00
Received By shill Date 2019-05-14 Time 17:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-04-16 Cont ID  
Sent By shill Date 2019-04-16 Time 17:24 Rev Time 0.00
Received By shill Date 2019-04-16 Time 17:23 Sent To  
Notes
2019-04-16 17:24:46DIGITAL SIGNATURES ARE OK - NEW PAGES SUBMITTED NEXT
 REVIEW CYCLE REQUIRE VERIFICATION
  
 S.HILL, 561-805-6724

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2019-05-01 Time   Rev Time 0.00
Received By pgreilic Date 2019-05-01 Time 10:04 Sent To  
Notes
2019-05-01 10:05:23LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 [email protected]
 561-822-1443
  

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By pgreilic Date 2019-04-16 Time   Rev Time 0.00
Received By pgreilic Date 2019-04-16 Time 16:37 Sent To  
Notes
2019-04-16 16:38:24PROVIDE SITE PLAN OR SURVEY INDICATING LIMITS OF WORK
 AND NOTE THAT WORK WILL BE LIMITED TO EXISTING BUILDING
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443