Plan Review Details - Permit 19020967
Plan Review Stops For Permit 19020967
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-05-13 Cont ID  
Sent By jgomez Date 2019-05-13 Time 09:39 Rev Time 0.00
Received By jgomez Date 2019-05-13 Time 08:26 Sent To  
Notes
2019-05-13 09:40:18JULIO,
 THANK YOU AGAIN FOR THE CALL LAST NIGHT.
 THE PROVISO OPTION IS PREFERRED AT THIS TIME ? WE
 UNDERSTAND WE WILL BE REQUIRED TO SUBMIT INFORMATION
 AFTER THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO
 AVOID CONFLICTS OR DELAYS.
 PLEASE ADVISE IF YOU REQUIRE ADDITIONAL INFORMATION AT
 THIS TIME. THANKYOU! JULIE
 JULIE T. WEHMEYER A.I.A.
 STUDIO DIRECTOR / ASSOCIATE PRINCIPAL
 21 SOUTH EVERGREEN AVENUE, SUITE 200, ARLINGTON
 HEIGHTS, IL 60005
 T: 847.788.9200 C: 312.965.1972
  
  
  
 BUILDING APPROVED WITH PROVISO:
 1- SHEET CS1.0: REVISE LIFE SAFETY PLAN SHOW NUMBER OF
 PEOPLE ON EACH ROOM. ALSO, REVISE OCCUPANT LOAD CHART
 SHOWING THE BREAKDOWN OF THE PEOPLE ON EACH SPACE.
 NEED POSTING OF THE OCCUPANT LOAD PER ROOM. SEC. 1004.3
 FBC-BUILDING.
  
 2- REVISE DOOR HARDWARE & HARDWARE SCHEDULE TO MATCH.
  
 3- REAR EXTERIOR EGRESS: RAMP NEEDS HANDRAILS. SEC.
 405.8 FBC-ACCESSIBILITY & RAMP EDGE PROTECTION. SEC.
 405.9 FBC-ACCESSIBILITY.
  
 4- REVISE BUILDING CODE INFORMATION: THIS IS ALTERATION
 LEVEL 3 & CHANGE OF OCCUPANCY. NON-SEPARATED
 OCCUPANCIES IS SEC. 508.3 FBC-BUILDING NOT SEC. 508.4.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-05-09 Cont ID  
Sent By jgomez Date 2019-05-09 Time 15:52 Rev Time 0.00
Received By jgomez Date 2019-05-08 Time 13:54 Sent To  
Notes
2019-05-09 15:55:29COMMERCIAL CHANGE OF OCCUPANCY, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
  
 1- SHEET CS1.0:
 A)ACCORDING TO OCCUPANCY LOAD (88 PERSONS) SHOWN ON
 SHEET CS1, TWO EXITS ARE REQUIRED. SEC. 1006.2.1 FBC.
 LIFE SAFETY PLAN ON SAME SHEET SHOWS ONLY ONE EXIT FOR
 THE RETAIL AREA TO THE MAIN ENTRY DOORS AND ONLY ONE
 EXIT FOR THE SALES COUNTER AREA TO THE REAR DOORS. THE
 TWO EXITS OPTIONS ARE REQUIRED FOR FOR ALL THE PERSONS
 IN THIS ESTABLISHMENT. REVISE AS LIFE SAFETY PLAN AS
 REQUIRED SHOWING BOTH EXITS AVAILABLE FOR EVERYBODY.
  
 RESPONSE:
 OCCUPANT LOAD CHART AND LIFE SAFETY PLAN SUBMITTED
 DON'T REFLECT WHAT WAS SAID ON THE RESPONSE LETTER.
 PLEASE REVISE THE OCCUPANT LOAD CHART SHOWING THE
 BREAKDOWN OF THE SPACES AS EXPLAINED ON THE RESPONSE
 LETTER AND REVISE THE LIFE SAFETY PLAN SHOWING THE
 NUMBER OF PEOPLE PER ROOM. ALSO, PROVIDE A NOTE ON PLAN
 INDICATING THE POSTING OF THE OCCUPANT LOAD PER ROOM AS
 REQUIRED BY SEC. 1004.3 FBC-BUILDING.
  
 B)CLARIFY HOW EGRESS THROUGH THE SALES COUNTER AREA
 FROM THE RETAIL AREA IS GOING TO BE ACHIEVED SINCE THE
 DOORS LEADING TO THIS AREA SEEM TO BE LOCKED. SEC.
 1016.2 FBC DOESN'T ALLOW EGRESS THROUGH INTERVENING
 SPACES THAT CAN BE LOCKED.
  
 RESPONSE:
 DOOR SCHEDULE AND DOOR HARDWARE SCHEDULE SOWN ON SHEET
 A2.0 WERE REVISED AND ARE CONFUSING. DOOR & SECURITY
 SCHEDULE, DOOR HARDWARE SCHEDULE AND FLOOR PLAN SHOWING
 ALL THE DOORS NEED TO BE COORDINATED. FOR EXAMPLE WHERE
 IS HARDWARE SET #3.1. DOOR HARDWARE SCHEDULE SHOW TWO
 SINGLE DOORS #EX-02 WITH DIFFERENT HARDWARE #. PROVIDE
 FLOOR PLAN SHOWING ALL THE DOOR PROPERLY NUMBERED AND
 MATCHING THE DOOR SCHEDULE.
 ALSO, THERE ARE NO NOTES SPECIFYING ADA THRESHOLDS AT
 THE ENTRY AND EXIT DOORS.
  
 C)OK. THIS WILL BE COORDINATED WITH ITEM #1A ABOVE.
  
 2- BASED ON THE REQUIRED NUMBER OF EXITS REQUIRED BY
 THE OCCUPANT LOAD SHOWN ON SHEET CS1.O BOTH EXITS NEED
 TO BE ACCESSIBLE MEANS OF EGRESS. PROVIDE DETAILS AND
 SPECIFICATIONS SHOWING HOW THE REAR EXIT COMPLIES WITH
 THE ACCESSIBLE MEANS OF EGRESS. SEC. 1012.8 FBC
 EXISTING BUILDING. SEC. 207 FBC-ACCESSIBILITY AND SEC.
 1007.1 2003 INTERNATIONAL BUILDING CODE.
  
 RESPONSE:
 RAMP SHOWN BY THE REAR EGRESS DOORS SHOWN ON THE LIFE
 SAFETY NEEDS TO SHOW THE HANDRAIL REQUIRED BY SEC.
 405.8 FBC-ACCESSIBILITY AND THE RAMP EDGE PROTECTION AS
 REQUIRED BY SEC. 405.9 FBC-ACCESSIBILITY.
  
 3- CLARIFY BUILDING USE SHOWN ON THE BUILDING CODE
 INFORMATION: THIS IS NOT ALTERATION LEVEL 2. ACCORDING
 TO SEC. 506 FBC-EXISTING BUILDING THIS IS A CHANGE OF
 OCCUPANCY. THE BUILDING IS CURRENTLY USED AS BUSINESS
 OCCUPANCY. REVISE AS REQUIRED.
  
 RESPONSE:
 THIS IS NOT ALTERATION LEVEL 2. THIS IS AN ALTERATION
 LEVEL 3 (THE WORK AREA EXCEEDS 50 PERCENT OF THE
 BUILDING AREA) AND THIS IS A CHANGE OF OCCUPANCY FROM
 BUSINESS TO MERCANTILE.
 ALSO, NON-SEPARATED OCCUPANCIES IS SEC. 508.3
 FBC-BUILDING NOT SEC. 508.4.
  
  
 4- OK. THE 18" MIN. ON PULL SIDE TO BE VERIFIED IN THE
 FIELD.
  
 5- OK.
  
 6- PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR
 REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW
 COMMENTS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-27 Cont ID  
Sent By jgomez Date 2019-03-27 Time 18:46 Rev Time 0.00
Received By jgomez Date 2019-03-27 Time 17:06 Sent To  
Notes
2019-03-27 18:48:07COMMERCIAL CHANGE OF OCCUPANCY, BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- SHEET CS1.0:
 A)ACCORDING TO OCCUPANCY LOAD (88 PERSONS) SHOWN ON
 SHEET CS1, TWO EXITS ARE REQUIRED. SEC. 1006.2.1 FBC.
 LIFE SAFETY PLAN ON SAME SHEET SHOWS ONLY ONE EXIT FOR
 THE RETAIL AREA TO THE MAIN ENTRY DOORS AND ONLY ONE
 EXIT FOR THE SALES COUNTER AREA TO THE REAR DOORS. THE
 TWO EXITS OPTIONS ARE REQUIRED FOR FOR ALL THE PERSONS
 IN THIS ESTABLISHMENT. REVISE AS LIFE SAFETY PLAN AS
 REQUIRED SHOWING BOTH EXITS AVAILABLE FOR EVERYBODY.
  
 B)CLARIFY HOW EGRESS THROUGH THE SALES COUNTER AREA
 FROM THE RETAIL AREA IS GOING TO BE ACHIEVED SINCE THE
 DOORS LEADING TO THIS AREA SEEM TO BE LOCKED. SEC.
 1016.2 FBC DOESN'T ALLOW EGRESS THROUGH INTERVENING
 SPACES THAT CAN BE LOCKED.
  
 C)CLARIFY OCCUPANT LOAD CALCULATIONS. WHY USING 1:15
 SQUARE FOOTAGE FOR WAITING AREA. CLARIFY IF USING GROSS
 OR NET AREAS. CLARIFY USE. SEE TABLE 1004.1.2 FBC.
 ALSO, CLARIFY HOW THE AREAS FOR WAITING, RETAIL,
 STORAGE/STOCK WERE CALCULATED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 2- BASED ON THE REQUIRED NUMBER OF EXITS REQUIRED BY
 THE OCCUPANT LOAD SHOWN ON SHEET CS1.O BOTH EXITS NEED
 TO BE ACCESSIBLE MEANS OF EGRESS. PROVIDE DETAILS AND
 SPECIFICATIONS SHOWING HOW THE REAR EXIT COMPLIES WITH
 THE ACCESSIBLE MEANS OF EGRESS. SEC. 1012.8 FBC
 EXISTING BUILDING. SEC. 207 FBC-ACCESSIBILITY AND SEC.
 1007.1 2003 INTERNATIONAL BUILDING CODE.
  
 3- CLARIFY BUILDING USE SHOWN ON THE BUILDING CODE
 INFORMATION: THIS IS NOT ALTERATION LEVEL 2. ACCORDING
 TO SEC. 506 FBC-EXISTING BUILDING THIS IS A CHANGE OF
 OCCUPANCY. THE BUILDING IS CURRENTLY USED AS BUSINESS
 OCCUPANCY. REVISE AS REQUIRED.
  
 4- FLOOR PLAN ON SHEET A1.0: DOORS 03A AND O3B DON'T
 SEEM TO COMPLY WITH DOOR MANEUVERING FOR FRONT
 APPROACH. FLOOR PLAN SHOWS 1'-5-1/4". NEED 18 INCHES
 MIN AS REQUIRED BY SEC. 404.2.4 FBC-ACCESSIBILITY.
 REVISE AS REQUIRED.
  
 5- WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM
 SHALL COMPLY WITH SEC. 603 AS REQUIRED BY SEC. 213.2
 FBC-ACCESSIBILITY. EXISTING TOILET ROOM SHOWN ON FLOOR
 PLAN NEEDS TO COMPLY ALSO. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE (INCLUDING DOOR).
  
 6- PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR
 REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW
 COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-05-03 Cont ID  
Sent By jpearson Date 2019-05-03 Time 15:34 Rev Time 0.00
Received By jpearson Date 2019-05-03 Time 15:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-18 Cont ID  
Sent By jpearson Date 2019-03-18 Time 15:51 Rev Time 0.00
Received By jpearson Date 2019-03-18 Time 15:51 Sent To  
Notes
2019-03-18 15:51:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. POWER PLAN SHOWS WHAT APPEARS TO BE A COUNTER IN
 FRONT OF PANEL DCP AND PANEL L2. THESE PANELS MUXT HAVE
 CLEARANCE PER NEC 110.26. PROVIDE CLARIFICATION AND/OR
 CORRECTION. NEC 110.26
 2. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63
 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2019-05-03 Cont ID  
Sent By jpearson Date 2019-05-03 Time 15:33 Rev Time 0.00
Received By jpearson Date 2019-05-03 Time 15:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-04-24 Cont ID  
Sent By pleduc Date 2019-04-24 Time   Rev Time 0.00
Received By pleduc Date 2019-04-24 Time 13:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-03-04 Cont ID  
Sent By pleduc Date 2019-03-04 Time   Rev Time 0.00
Received By pleduc Date 2019-03-04 Time 15:38 Sent To  
Notes
2019-03-04 16:31:45THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A101- THERE IS AN AREA INDICATED AS MAN TRAP
 AREA.
  
 PLEASE PROVIDE A NARRATIVE OF WHAT THIS AREA IS FOR AND
 HOW WILL IT COMPLY WITH THE FLORIDA FIRE PREVENTION
 CODE, NFPA 101 CH 7, MEANS OF EGRESS.
  
  
  
 2) SHEET A 501 - THERE ARE INDICATIONS OF ACCESS
 CONTROL AND DOOR RELEASE BUTTON.
  
 ALL ACCESS CONTROL INSTALLTIONS SHALL BE UNDER SEPARATE
 SHOP DRAWINGS AND PERMIT.
  
 ALL ACCESS CONTROL SHALL COMPLY WITH NFPA 101, CH 7
 MEANS OF EGRESS.
  
 PLEASE REVIEW AND COMPLY AND PROVIDE AN APPLICABLE NOTE
 OF ACKNOWLEDGEMENT.
  
  
  
 3) SHEET A 101 & A 201 - THERE IS AN INDICATION THAT
 DOOR 07 IS WITHIN A FIRE WALL, HOWEVER, THE DOOR
 SCHEDULE FOR DOOR 07 HAS NO RATING.
  
 THE WALL THE DOOR IS IN IS A 1 HOUR FIRE WALL AND THE
 DOOR SHOULD HAVE THE SAME RATING.
  
  
 PLEASE AND CORRECT.
  
  
  
  
 4) SHEET A 201 - THERE IS AN INDICATION OF TWO DEAD
 BOLTS ON THE VAULT DOOR AND SELF LOCKING.
  
 NFPA 101 CH 7, MEANS OF EGRESS
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
  
 PLEASE REVIEW AND PROVIDE HOW THESE LOCKAS WILL COMPLY.
  
  
  
  
 5) SHEET A 101 & A 201 - THERE IS AN INDICATION THAT
 DOOR 09 IS WITHIN A FIRE WALL, HOWEVER, THE DOOR
 SCHEDULE FOR DOOR 09 HAS NO RATING.
  
 THE WALL THE DOOR IS IN IS A 1 HOUR FIRE WALL AND THE
 DOOR SHOULD HAVE THE SAME RATING.
  
  
 PLEASE AND CORRECT.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-16 Cont ID  
Sent By shill Date 2019-05-16 Time 14:04 Rev Time 0.00
Received By shill Date 2019-05-13 Time 07:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-09 Cont ID  
Sent By jgomez Date 2019-05-09 Time 16:49 Rev Time 0.00
Received By jgomez Date 2019-04-15 Time 08:01 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-27 Cont ID  
Sent By jgomez Date 2019-03-27 Time 18:51 Rev Time 0.00
Received By jgomez Date 2019-02-25 Time 12:38 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2019-05-20 Cont ID  
Sent By lmarchan Date 2019-05-20 Time 14:33 Rev Time 0.00
Received By lmarchan Date 2019-05-20 Time 12:57 Sent To  
Notes
2019-05-20 14:34:12NO RECEIPT AS NO MU NUMBER WAS CREATED. SEE ATTACHED
 EMAIL FROM IMPACT OFFICE.
2019-05-20 12:57:465/20/19 SENT EMAIL TO IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-03-27 Cont ID  
Sent By jgomez Date 2019-03-27 Time 18:51 Rev Time 0.00
Received By jgomez Date 2019-03-27 Time 18:51 Sent To  
Notes
2019-03-27 18:51:54IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-04-29 Cont ID  
Sent By ccole Date 2019-04-29 Time 16:19 Rev Time 0.00
Received By ccole Date 2019-04-29 Time 15:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-03-26 Cont ID  
Sent By ccole Date 2019-03-26 Time 12:40 Rev Time 0.00
Received By ccole Date 2019-03-26 Time 11:11 Sent To  
Notes
2019-03-26 13:09:541ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19020967
 3/26/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M101 & M102: REFER TO SECTION 809.2 FBC-17
 EXISTING BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE
 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR.
  
 2) M101 & M102: PROVIDE AN EQUIPMENT SCHEDUKLE FOR THE
 EXISTING FCU-1, AND RENAME THE FCU FOR THE VAULT AS
 FCU-2 TO AVOID CONFUSION.
  
 3) M101: PROVIDE A DUCT MOKE DETECTORS IN THE SUPPLY
 AIR SYSTEMS OF THE EXISTING FCU-1- SECTION 606.2.1.
  
 4) M101: THE LOCATION OF THE NEW O/A INTAKE FIOR THE
 EXISTING FCU-1 APPEARS TO BE WITHIN THE REQUIRED 10'
 CLEARANCE DISTANCE TO THE REAR PARKING LOT- SEE SECTION
 401.4 (2) FBC M.
  
 5) M101: SUBMIT MANUFACTURER'S SPECIFICATIONS AND A
 MIAMI-DADE NOA AND/OR A FL. PRODUCT APPROVAL FOR THE
 O/A INTAKE LOUVER- SEE SECTION 401.5 FBC M.
  
 6) M101 & M102: KEYED NOTES 8 AND 9 INDICATE EXHAUST
 DUCTS RUNNING FROM THE VAULT FCU. THIS APPEARS TO BE A
 MISTAKE. IS THIS SYSTEM AN ERV WITH ONE OF THOSE DUCTS
 INTENDED TO BE O/A INTAKE? THE EQUIPMENT SCHEDULE DOES
 NOT LIST ANY EXHAUST CFMS.
  
 7) M103: THE CONDENSING SUPPORT STAND DOES NOT PROVIDE
 COMPLETRE ENGINEERING AND DESIGN CRITERIA FOR
 INSTALLATION OF THE ROOFTOP CONDENSER. PLEASE PROVIDE
 SITE SPECIFIC ENGINERRING- SECTION 301.15 FBC M AND SEE
 TABLE 1510.10 FBC -B FOR REQUIRED CLEARANCE UNDER THE
 UNIT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-05-15 Cont ID  
Sent By gjohnson Date 2019-05-15 Time 12:22 Rev Time 0.00
Received By gjohnson Date 2019-05-15 Time 10:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-04-22 Cont ID  
Sent By gjohnson Date 2019-04-22 Time 17:06 Rev Time 0.00
Received By gjohnson Date 2019-04-22 Time 17:06 Sent To  
Notes
2019-04-22 17:10:551ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1) DIGITAL SUBMITTED PLANS ARE REQUIRED TO BE SIGNED
 DIGITALLY P-1 AND P-2 ARE NOT DIGITALLY SIGNED. RULE
 61G15-23. PLEASE RESUBMITPLANS WITH A DIGITAL
 SIGNATURE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-25 Cont ID  
Sent By thunt Date 2019-03-25 Time 10:48 Rev Time 0.00
Received By thunt Date 2019-03-25 Time 09:58 Sent To  
Notes
2019-03-25 10:49:03PLUMBING 1ST REVIEW**DENIED**
  
 1) DIGITAL SUBMITTED PLANS ARE REQUIRED TO BE SIGNED
 DIGITALLY. RULE 61G15-23. PLEASE RESUBMIT ALL PLANS
 WITH A DIGITAL SIGNATURE.
  
 2) PROVIDE A SANITARY RISER AND WATER DISTRIBUTION
 RISER DRAWING. FBC 107.3.5
  
 3) PROVIDE WHERE HOT WATER SUPPLY IS COMING FROM FOR
 THE EMPLOYEE SINK AND THE TOTAL DEVELOPED LENGTH OF
 THAT LINE. IF OVER 50' A RETURN SYSTEM WILL BE NEEDED.
 FBC-P 607.2
  
 4) PROVIDE MOUNTING HEIGHT OG THE REAR AND SIDE GRAB
 BAR ON SHT.A2.1
  
 5) SHT.CS1.0 CALLS OUT BUILDING AS 3604 SQUARE FEET.
 PALM BEACH COUNTY PROPERTY'S APPRAISERS OFFICE LIST
 SQUARE FOOTAGE AS 4257. PLEASE CLARIFY OR CHANGE TO
 CORRECT SQUARE FOOTAGE AND OCCUPANT LOAD. FBC 107.2.1
  
 6)PROVIDE CLEAR FLOOR SPACE FOR STAFF BREAK ROOM SINK
 AREA WITH HEIGHT. FBC-A 606.2, 606.3
  
 7) PROVIDE DRINKING FOUNTAIN DETAIL SHOWING IT IS TO
 COMPLY WITH FBC0A 602.
  
 8)SHT.A2.1 SHOWS TOILET DISPENSER HEIGHT BUT IS NOT
 SHOWING DISTANCE FROM BOWL. FBC-A 604.7
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-05-16 Cont ID  
Sent By shill Date 2019-05-16 Time 10:02 Rev Time 0.00
Received By shill Date 2019-05-16 Time 10:02 Sent To  
Notes
2019-04-29 16:21:04MECH SHEETS ARE OK- 4/29/19

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-03-18 Cont ID  
Sent By jpearson Date 2019-03-18 Time 15:17 Rev Time 0.00
Received By jpearson Date 2019-03-18 Time 15:17 Sent To  
Notes
2019-03-26 14:23:31ARCHITECTURAL PLANS NEED DIGITAL SIGNATURE. JG.
2019-03-26 11:48:17MECH SHEETS AND ENERGY CALCULATIONS NOT DIGITALLY
 SIGNED AND SEALED.
2019-03-18 15:17:07PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481

Review Stop Z ZONING
Rev No 3 Status P Date 2019-05-16 Cont ID  
Sent By aaponte Date 2019-05-16 Time 13:09 Rev Time 0.00
Received By aaponte Date 2019-05-16 Time 13:09 Sent To  
Notes
2019-05-16 13:10:00PROVISO: FINAL CO CONDITIONAL TO THE SUBMITTAL AND
 APPROVAL OF LANDSCAPE AND PAVING PLAN FOR THE AREA ON
 BACK OF BUILDING.

Review Stop Z ZONING
Rev No 2 Status F Date 2019-04-19 Cont ID  
Sent By aaponte Date 2019-04-19 Time 16:50 Rev Time 0.00
Received By aaponte Date 2019-04-19 Time 16:49 Sent To  
Notes
2019-04-19 16:53:02COMMENTS FROM PREVIOUS REVIEW HAVE NOT BEEN SATISFIED.
 A SEPARATE LANDSCAPE AND PAVING PERMIT SHALL BE
 REQUIRED, BUT A SITE PLAN SHALL BE INCLUDED INTHE MAIN
 PERMIT.
 SATISFIED1. PLEASE REMOVE SIGNS FROM THE DRAWINGS, THEY
 REQUIRE A SEPARATE PERMIT.
 NOT SATISFIED. 2. DUE TO THE VALUE OF THE IMPROVEMENTS
 , THE PARKING AREA ON THE BACK OF THE BUILDING SHALL
 MEET THE LANDSCAPE REQUIREMENTS FOR PAKING LOTS. A 5
 FOOT WIDE PLANTING AREA WITH A HEDGE AND A TREE SHALL
 BE PROVIDED ALONG THE QUADRILLE BOULEVARD FRONTAGE.
 NOT SATISFIED. 3. PARKING SPACES SHALL BE RESTRIPED
 MEETING STALL DIMENSIONS AND STRIPING DETAIL. WHEEL
 STOPS SHALL BE INSTALLED, AND IF DIMENSIONS ALLOW BASE
 PLANTING SHALL BE INSTALLED ALONG THE FACADE.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status F Date 2019-03-15 Cont ID  
Sent By aaponte Date 2019-03-15 Time 16:19 Rev Time 0.00
Received By aaponte Date 2019-03-15 Time 16:19 Sent To  
Notes
2019-03-15 16:27:111. PLEASE REMOVE SIGNS FROM THE DRAWINGS, THEY REQUIRE
 A SEPARATE PERMIT.
 2. DUE TO THE VALUE OF THE IMPROVEMENTS , THE PARKING
 AREA ON THE BACK OF THE BUILDING SHALL MEET THE
 LANDSCAPE REQUIREMENTS FOR PAKING LOTS. A 5 FOOT WIDE
 PLANTING AREA WITH A HEDGE AND A TREE SHALL BE PROVIDED
 ALONG THE QUADRILLE BOULEVARD FRONTAGE.
 3. PARKING SPACES SHALL BE RESTRIPED MEETING STALL
 DIMENSIONS AND STRIPING DETAIL. WHEEL STOPS SHALL BE
 INSTALLED, AND IF DIMENSIONS ALLOW BASE PLANTING SHALL
 BE INSTALLED ALONG THE FACADE.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.