| Plan Review Stops For Permit 19020967 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2019-05-13 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-05-13 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-05-13 |
Time |
08:26 |
Sent To |
|
|
| Notes |
| 2019-05-13 09:40:18 | JULIO, | | | THANK YOU AGAIN FOR THE CALL LAST NIGHT. | | | THE PROVISO OPTION IS PREFERRED AT THIS TIME ? WE | | | UNDERSTAND WE WILL BE REQUIRED TO SUBMIT INFORMATION | | | AFTER THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO | | | AVOID CONFLICTS OR DELAYS. | | | PLEASE ADVISE IF YOU REQUIRE ADDITIONAL INFORMATION AT | | | THIS TIME. THANKYOU! JULIE | | | JULIE T. WEHMEYER A.I.A. | | | STUDIO DIRECTOR / ASSOCIATE PRINCIPAL | | | 21 SOUTH EVERGREEN AVENUE, SUITE 200, ARLINGTON | | | HEIGHTS, IL 60005 | | | T: 847.788.9200 C: 312.965.1972 | | | | | | | | | | | | BUILDING APPROVED WITH PROVISO: | | | 1- SHEET CS1.0: REVISE LIFE SAFETY PLAN SHOW NUMBER OF | | | PEOPLE ON EACH ROOM. ALSO, REVISE OCCUPANT LOAD CHART | | | SHOWING THE BREAKDOWN OF THE PEOPLE ON EACH SPACE. | | | NEED POSTING OF THE OCCUPANT LOAD PER ROOM. SEC. 1004.3 | | | FBC-BUILDING. | | | | | | 2- REVISE DOOR HARDWARE & HARDWARE SCHEDULE TO MATCH. | | | | | | 3- REAR EXTERIOR EGRESS: RAMP NEEDS HANDRAILS. SEC. | | | 405.8 FBC-ACCESSIBILITY & RAMP EDGE PROTECTION. SEC. | | | 405.9 FBC-ACCESSIBILITY. | | | | | | 4- REVISE BUILDING CODE INFORMATION: THIS IS ALTERATION | | | LEVEL 3 & CHANGE OF OCCUPANCY. NON-SEPARATED | | | OCCUPANCIES IS SEC. 508.3 FBC-BUILDING NOT SEC. 508.4. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-05-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-05-09 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-05-08 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2019-05-09 15:55:29 | COMMERCIAL CHANGE OF OCCUPANCY, SECOND BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | NOTE: | | | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO | | | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER | | | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID | | | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR | | | TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME | | | OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT | | | ISSUANCE. | | | | | | | | | | | | | | | 1- SHEET CS1.0: | | | A)ACCORDING TO OCCUPANCY LOAD (88 PERSONS) SHOWN ON | | | SHEET CS1, TWO EXITS ARE REQUIRED. SEC. 1006.2.1 FBC. | | | LIFE SAFETY PLAN ON SAME SHEET SHOWS ONLY ONE EXIT FOR | | | THE RETAIL AREA TO THE MAIN ENTRY DOORS AND ONLY ONE | | | EXIT FOR THE SALES COUNTER AREA TO THE REAR DOORS. THE | | | TWO EXITS OPTIONS ARE REQUIRED FOR FOR ALL THE PERSONS | | | IN THIS ESTABLISHMENT. REVISE AS LIFE SAFETY PLAN AS | | | REQUIRED SHOWING BOTH EXITS AVAILABLE FOR EVERYBODY. | | | | | | RESPONSE: | | | OCCUPANT LOAD CHART AND LIFE SAFETY PLAN SUBMITTED | | | DON'T REFLECT WHAT WAS SAID ON THE RESPONSE LETTER. | | | PLEASE REVISE THE OCCUPANT LOAD CHART SHOWING THE | | | BREAKDOWN OF THE SPACES AS EXPLAINED ON THE RESPONSE | | | LETTER AND REVISE THE LIFE SAFETY PLAN SHOWING THE | | | NUMBER OF PEOPLE PER ROOM. ALSO, PROVIDE A NOTE ON PLAN | | | INDICATING THE POSTING OF THE OCCUPANT LOAD PER ROOM AS | | | REQUIRED BY SEC. 1004.3 FBC-BUILDING. | | | | | | B)CLARIFY HOW EGRESS THROUGH THE SALES COUNTER AREA | | | FROM THE RETAIL AREA IS GOING TO BE ACHIEVED SINCE THE | | | DOORS LEADING TO THIS AREA SEEM TO BE LOCKED. SEC. | | | 1016.2 FBC DOESN'T ALLOW EGRESS THROUGH INTERVENING | | | SPACES THAT CAN BE LOCKED. | | | | | | RESPONSE: | | | DOOR SCHEDULE AND DOOR HARDWARE SCHEDULE SOWN ON SHEET | | | A2.0 WERE REVISED AND ARE CONFUSING. DOOR & SECURITY | | | SCHEDULE, DOOR HARDWARE SCHEDULE AND FLOOR PLAN SHOWING | | | ALL THE DOORS NEED TO BE COORDINATED. FOR EXAMPLE WHERE | | | IS HARDWARE SET #3.1. DOOR HARDWARE SCHEDULE SHOW TWO | | | SINGLE DOORS #EX-02 WITH DIFFERENT HARDWARE #. PROVIDE | | | FLOOR PLAN SHOWING ALL THE DOOR PROPERLY NUMBERED AND | | | MATCHING THE DOOR SCHEDULE. | | | ALSO, THERE ARE NO NOTES SPECIFYING ADA THRESHOLDS AT | | | THE ENTRY AND EXIT DOORS. | | | | | | C)OK. THIS WILL BE COORDINATED WITH ITEM #1A ABOVE. | | | | | | 2- BASED ON THE REQUIRED NUMBER OF EXITS REQUIRED BY | | | THE OCCUPANT LOAD SHOWN ON SHEET CS1.O BOTH EXITS NEED | | | TO BE ACCESSIBLE MEANS OF EGRESS. PROVIDE DETAILS AND | | | SPECIFICATIONS SHOWING HOW THE REAR EXIT COMPLIES WITH | | | THE ACCESSIBLE MEANS OF EGRESS. SEC. 1012.8 FBC | | | EXISTING BUILDING. SEC. 207 FBC-ACCESSIBILITY AND SEC. | | | 1007.1 2003 INTERNATIONAL BUILDING CODE. | | | | | | RESPONSE: | | | RAMP SHOWN BY THE REAR EGRESS DOORS SHOWN ON THE LIFE | | | SAFETY NEEDS TO SHOW THE HANDRAIL REQUIRED BY SEC. | | | 405.8 FBC-ACCESSIBILITY AND THE RAMP EDGE PROTECTION AS | | | REQUIRED BY SEC. 405.9 FBC-ACCESSIBILITY. | | | | | | 3- CLARIFY BUILDING USE SHOWN ON THE BUILDING CODE | | | INFORMATION: THIS IS NOT ALTERATION LEVEL 2. ACCORDING | | | TO SEC. 506 FBC-EXISTING BUILDING THIS IS A CHANGE OF | | | OCCUPANCY. THE BUILDING IS CURRENTLY USED AS BUSINESS | | | OCCUPANCY. REVISE AS REQUIRED. | | | | | | RESPONSE: | | | THIS IS NOT ALTERATION LEVEL 2. THIS IS AN ALTERATION | | | LEVEL 3 (THE WORK AREA EXCEEDS 50 PERCENT OF THE | | | BUILDING AREA) AND THIS IS A CHANGE OF OCCUPANCY FROM | | | BUSINESS TO MERCANTILE. | | | ALSO, NON-SEPARATED OCCUPANCIES IS SEC. 508.3 | | | FBC-BUILDING NOT SEC. 508.4. | | | | | | | | | 4- OK. THE 18" MIN. ON PULL SIDE TO BE VERIFIED IN THE | | | FIELD. | | | | | | 5- OK. | | | | | | 6- PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR | | | REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW | | | COMMENTS. | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-03-27 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-03-27 |
Time |
18:46 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-03-27 |
Time |
17:06 |
Sent To |
|
|
| Notes |
| 2019-03-27 18:48:07 | COMMERCIAL CHANGE OF OCCUPANCY, BUILDING REVIEW | | | COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1- SHEET CS1.0: | | | A)ACCORDING TO OCCUPANCY LOAD (88 PERSONS) SHOWN ON | | | SHEET CS1, TWO EXITS ARE REQUIRED. SEC. 1006.2.1 FBC. | | | LIFE SAFETY PLAN ON SAME SHEET SHOWS ONLY ONE EXIT FOR | | | THE RETAIL AREA TO THE MAIN ENTRY DOORS AND ONLY ONE | | | EXIT FOR THE SALES COUNTER AREA TO THE REAR DOORS. THE | | | TWO EXITS OPTIONS ARE REQUIRED FOR FOR ALL THE PERSONS | | | IN THIS ESTABLISHMENT. REVISE AS LIFE SAFETY PLAN AS | | | REQUIRED SHOWING BOTH EXITS AVAILABLE FOR EVERYBODY. | | | | | | B)CLARIFY HOW EGRESS THROUGH THE SALES COUNTER AREA | | | FROM THE RETAIL AREA IS GOING TO BE ACHIEVED SINCE THE | | | DOORS LEADING TO THIS AREA SEEM TO BE LOCKED. SEC. | | | 1016.2 FBC DOESN'T ALLOW EGRESS THROUGH INTERVENING | | | SPACES THAT CAN BE LOCKED. | | | | | | C)CLARIFY OCCUPANT LOAD CALCULATIONS. WHY USING 1:15 | | | SQUARE FOOTAGE FOR WAITING AREA. CLARIFY IF USING GROSS | | | OR NET AREAS. CLARIFY USE. SEE TABLE 1004.1.2 FBC. | | | ALSO, CLARIFY HOW THE AREAS FOR WAITING, RETAIL, | | | STORAGE/STOCK WERE CALCULATED. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | | | | 2- BASED ON THE REQUIRED NUMBER OF EXITS REQUIRED BY | | | THE OCCUPANT LOAD SHOWN ON SHEET CS1.O BOTH EXITS NEED | | | TO BE ACCESSIBLE MEANS OF EGRESS. PROVIDE DETAILS AND | | | SPECIFICATIONS SHOWING HOW THE REAR EXIT COMPLIES WITH | | | THE ACCESSIBLE MEANS OF EGRESS. SEC. 1012.8 FBC | | | EXISTING BUILDING. SEC. 207 FBC-ACCESSIBILITY AND SEC. | | | 1007.1 2003 INTERNATIONAL BUILDING CODE. | | | | | | 3- CLARIFY BUILDING USE SHOWN ON THE BUILDING CODE | | | INFORMATION: THIS IS NOT ALTERATION LEVEL 2. ACCORDING | | | TO SEC. 506 FBC-EXISTING BUILDING THIS IS A CHANGE OF | | | OCCUPANCY. THE BUILDING IS CURRENTLY USED AS BUSINESS | | | OCCUPANCY. REVISE AS REQUIRED. | | | | | | 4- FLOOR PLAN ON SHEET A1.0: DOORS 03A AND O3B DON'T | | | SEEM TO COMPLY WITH DOOR MANEUVERING FOR FRONT | | | APPROACH. FLOOR PLAN SHOWS 1'-5-1/4". NEED 18 INCHES | | | MIN AS REQUIRED BY SEC. 404.2.4 FBC-ACCESSIBILITY. | | | REVISE AS REQUIRED. | | | | | | 5- WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM | | | SHALL COMPLY WITH SEC. 603 AS REQUIRED BY SEC. 213.2 | | | FBC-ACCESSIBILITY. EXISTING TOILET ROOM SHOWN ON FLOOR | | | PLAN NEEDS TO COMPLY ALSO. PROVIDE COMPLETE DETAILS AND | | | SPECIFICATIONS SHOWING COMPLIANCE (INCLUDING DOOR). | | | | | | 6- PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR | | | REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW | | | COMMENTS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-05-03 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-05-03 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-05-03 |
Time |
15:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-03-18 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-03-18 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-03-18 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2019-03-18 15:51:28 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. POWER PLAN SHOWS WHAT APPEARS TO BE A COUNTER IN | | | FRONT OF PANEL DCP AND PANEL L2. THESE PANELS MUXT HAVE | | | CLEARANCE PER NEC 110.26. PROVIDE CLARIFICATION AND/OR | | | CORRECTION. NEC 110.26 | | | 2. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR | | | SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE | | | EQUIPMENT PER CODE. NEC 210.63 | | | 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, | | | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD | | | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND | | | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN | | | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE | | | INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN | | | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC | | | 105.1, 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
| Rev No |
1 |
Status |
P |
Date |
2019-05-03 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-05-03 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-05-03 |
Time |
15:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-04-24 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-04-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-04-24 |
Time |
13:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2019-03-04 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-03-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-03-04 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2019-03-04 16:31:45 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) SHEET A101- THERE IS AN AREA INDICATED AS MAN TRAP | | | AREA. | | | | | | PLEASE PROVIDE A NARRATIVE OF WHAT THIS AREA IS FOR AND | | | HOW WILL IT COMPLY WITH THE FLORIDA FIRE PREVENTION | | | CODE, NFPA 101 CH 7, MEANS OF EGRESS. | | | | | | | | | | | | 2) SHEET A 501 - THERE ARE INDICATIONS OF ACCESS | | | CONTROL AND DOOR RELEASE BUTTON. | | | | | | ALL ACCESS CONTROL INSTALLTIONS SHALL BE UNDER SEPARATE | | | SHOP DRAWINGS AND PERMIT. | | | | | | ALL ACCESS CONTROL SHALL COMPLY WITH NFPA 101, CH 7 | | | MEANS OF EGRESS. | | | | | | PLEASE REVIEW AND COMPLY AND PROVIDE AN APPLICABLE NOTE | | | OF ACKNOWLEDGEMENT. | | | | | | | | | | | | 3) SHEET A 101 & A 201 - THERE IS AN INDICATION THAT | | | DOOR 07 IS WITHIN A FIRE WALL, HOWEVER, THE DOOR | | | SCHEDULE FOR DOOR 07 HAS NO RATING. | | | | | | THE WALL THE DOOR IS IN IS A 1 HOUR FIRE WALL AND THE | | | DOOR SHOULD HAVE THE SAME RATING. | | | | | | | | | PLEASE AND CORRECT. | | | | | | | | | | | | | | | 4) SHEET A 201 - THERE IS AN INDICATION OF TWO DEAD | | | BOLTS ON THE VAULT DOOR AND SELF LOCKING. | | | | | | NFPA 101 CH 7, MEANS OF EGRESS | | | | | | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE | | | OF A KEY, A | | | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM | | | THE EGRESS | | | SIDE. | | | | | | PLEASE REVIEW AND PROVIDE HOW THESE LOCKAS WILL COMPLY. | | | | | | | | | | | | | | | 5) SHEET A 101 & A 201 - THERE IS AN INDICATION THAT | | | DOOR 09 IS WITHIN A FIRE WALL, HOWEVER, THE DOOR | | | SCHEDULE FOR DOOR 09 HAS NO RATING. | | | | | | THE WALL THE DOOR IS IN IS A 1 HOUR FIRE WALL AND THE | | | DOOR SHOULD HAVE THE SAME RATING. | | | | | | | | | PLEASE AND CORRECT. | | | | | | | | | | | | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-05-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-05-16 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-05-13 |
Time |
07:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-05-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-05-09 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-04-15 |
Time |
08:01 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-03-27 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-03-27 |
Time |
18:51 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-02-25 |
Time |
12:38 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
N |
Date |
2019-05-20 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2019-05-20 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-05-20 |
Time |
12:57 |
Sent To |
|
|
| Notes |
| 2019-05-20 14:34:12 | NO RECEIPT AS NO MU NUMBER WAS CREATED. SEE ATTACHED | | | EMAIL FROM IMPACT OFFICE. | | 2019-05-20 12:57:46 | 5/20/19 SENT EMAIL TO IMPACT FEE OFFICE FOR REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2019-03-27 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-03-27 |
Time |
18:51 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-03-27 |
Time |
18:51 |
Sent To |
|
|
| Notes |
| 2019-03-27 18:51:54 | IMPACT FEES - DIGITAL SUBMITTALS | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | | YOUR PROJECT OR EMAIL IT TO [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2019-04-29 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-04-29 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-04-29 |
Time |
15:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-03-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-03-26 |
Time |
12:40 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-03-26 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2019-03-26 13:09:54 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #19020967 | | | 3/26/2019 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M101 & M102: REFER TO SECTION 809.2 FBC-17 | | | EXISTING BUILDING CODE AND PROVIDE MINIMUM VENTILATION | | | CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE | | | 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT | | | INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR | | | AIR. | | | | | | 2) M101 & M102: PROVIDE AN EQUIPMENT SCHEDUKLE FOR THE | | | EXISTING FCU-1, AND RENAME THE FCU FOR THE VAULT AS | | | FCU-2 TO AVOID CONFUSION. | | | | | | 3) M101: PROVIDE A DUCT MOKE DETECTORS IN THE SUPPLY | | | AIR SYSTEMS OF THE EXISTING FCU-1- SECTION 606.2.1. | | | | | | 4) M101: THE LOCATION OF THE NEW O/A INTAKE FIOR THE | | | EXISTING FCU-1 APPEARS TO BE WITHIN THE REQUIRED 10' | | | CLEARANCE DISTANCE TO THE REAR PARKING LOT- SEE SECTION | | | 401.4 (2) FBC M. | | | | | | 5) M101: SUBMIT MANUFACTURER'S SPECIFICATIONS AND A | | | MIAMI-DADE NOA AND/OR A FL. PRODUCT APPROVAL FOR THE | | | O/A INTAKE LOUVER- SEE SECTION 401.5 FBC M. | | | | | | 6) M101 & M102: KEYED NOTES 8 AND 9 INDICATE EXHAUST | | | DUCTS RUNNING FROM THE VAULT FCU. THIS APPEARS TO BE A | | | MISTAKE. IS THIS SYSTEM AN ERV WITH ONE OF THOSE DUCTS | | | INTENDED TO BE O/A INTAKE? THE EQUIPMENT SCHEDULE DOES | | | NOT LIST ANY EXHAUST CFMS. | | | | | | 7) M103: THE CONDENSING SUPPORT STAND DOES NOT PROVIDE | | | COMPLETRE ENGINEERING AND DESIGN CRITERIA FOR | | | INSTALLATION OF THE ROOFTOP CONDENSER. PLEASE PROVIDE | | | SITE SPECIFIC ENGINERRING- SECTION 301.15 FBC M AND SEE | | | TABLE 1510.10 FBC -B FOR REQUIRED CLEARANCE UNDER THE | | | UNIT. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2019-05-15 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-05-15 |
Time |
12:22 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-05-15 |
Time |
10:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2019-04-22 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-04-22 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-04-22 |
Time |
17:06 |
Sent To |
|
|
| Notes |
| 2019-04-22 17:10:55 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1) DIGITAL SUBMITTED PLANS ARE REQUIRED TO BE SIGNED | | | DIGITALLY P-1 AND P-2 ARE NOT DIGITALLY SIGNED. RULE | | | 61G15-23. PLEASE RESUBMITPLANS WITH A DIGITAL | | | SIGNATURE. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-03-25 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-03-25 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-03-25 |
Time |
09:58 |
Sent To |
|
|
| Notes |
| 2019-03-25 10:49:03 | PLUMBING 1ST REVIEW**DENIED** | | | | | | 1) DIGITAL SUBMITTED PLANS ARE REQUIRED TO BE SIGNED | | | DIGITALLY. RULE 61G15-23. PLEASE RESUBMIT ALL PLANS | | | WITH A DIGITAL SIGNATURE. | | | | | | 2) PROVIDE A SANITARY RISER AND WATER DISTRIBUTION | | | RISER DRAWING. FBC 107.3.5 | | | | | | 3) PROVIDE WHERE HOT WATER SUPPLY IS COMING FROM FOR | | | THE EMPLOYEE SINK AND THE TOTAL DEVELOPED LENGTH OF | | | THAT LINE. IF OVER 50' A RETURN SYSTEM WILL BE NEEDED. | | | FBC-P 607.2 | | | | | | 4) PROVIDE MOUNTING HEIGHT OG THE REAR AND SIDE GRAB | | | BAR ON SHT.A2.1 | | | | | | 5) SHT.CS1.0 CALLS OUT BUILDING AS 3604 SQUARE FEET. | | | PALM BEACH COUNTY PROPERTY'S APPRAISERS OFFICE LIST | | | SQUARE FOOTAGE AS 4257. PLEASE CLARIFY OR CHANGE TO | | | CORRECT SQUARE FOOTAGE AND OCCUPANT LOAD. FBC 107.2.1 | | | | | | 6)PROVIDE CLEAR FLOOR SPACE FOR STAFF BREAK ROOM SINK | | | AREA WITH HEIGHT. FBC-A 606.2, 606.3 | | | | | | 7) PROVIDE DRINKING FOUNTAIN DETAIL SHOWING IT IS TO | | | COMPLY WITH FBC0A 602. | | | | | | 8)SHT.A2.1 SHOWS TOILET DISPENSER HEIGHT BUT IS NOT | | | SHOWING DISTANCE FROM BOWL. FBC-A 604.7 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2019-05-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-05-16 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-05-16 |
Time |
10:02 |
Sent To |
|
|
| Notes |
| 2019-04-29 16:21:04 | MECH SHEETS ARE OK- 4/29/19 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2019-03-18 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-03-18 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-03-18 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2019-03-26 14:23:31 | ARCHITECTURAL PLANS NEED DIGITAL SIGNATURE. JG. | | 2019-03-26 11:48:17 | MECH SHEETS AND ENERGY CALCULATIONS NOT DIGITALLY | | | SIGNED AND SEALED. | | 2019-03-18 15:17:07 | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | | IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON | | | RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A | | | DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY | | | VERIFICATION. PROVIDE CORRECTION. WPB FBC 107.1; FS | | | 471/481 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2019-05-16 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2019-05-16 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2019-05-16 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2019-05-16 13:10:00 | PROVISO: FINAL CO CONDITIONAL TO THE SUBMITTAL AND | | | APPROVAL OF LANDSCAPE AND PAVING PLAN FOR THE AREA ON | | | BACK OF BUILDING. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2019-04-19 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2019-04-19 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2019-04-19 |
Time |
16:49 |
Sent To |
|
|
| Notes |
| 2019-04-19 16:53:02 | COMMENTS FROM PREVIOUS REVIEW HAVE NOT BEEN SATISFIED. | | | A SEPARATE LANDSCAPE AND PAVING PERMIT SHALL BE | | | REQUIRED, BUT A SITE PLAN SHALL BE INCLUDED INTHE MAIN | | | PERMIT. | | | SATISFIED1. PLEASE REMOVE SIGNS FROM THE DRAWINGS, THEY | | | REQUIRE A SEPARATE PERMIT. | | | NOT SATISFIED. 2. DUE TO THE VALUE OF THE IMPROVEMENTS | | | , THE PARKING AREA ON THE BACK OF THE BUILDING SHALL | | | MEET THE LANDSCAPE REQUIREMENTS FOR PAKING LOTS. A 5 | | | FOOT WIDE PLANTING AREA WITH A HEDGE AND A TREE SHALL | | | BE PROVIDED ALONG THE QUADRILLE BOULEVARD FRONTAGE. | | | NOT SATISFIED. 3. PARKING SPACES SHALL BE RESTRIPED | | | MEETING STALL DIMENSIONS AND STRIPING DETAIL. WHEEL | | | STOPS SHALL BE INSTALLED, AND IF DIMENSIONS ALLOW BASE | | | PLANTING SHALL BE INSTALLED ALONG THE FACADE. | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-03-15 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2019-03-15 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2019-03-15 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2019-03-15 16:27:11 | 1. PLEASE REMOVE SIGNS FROM THE DRAWINGS, THEY REQUIRE | | | A SEPARATE PERMIT. | | | 2. DUE TO THE VALUE OF THE IMPROVEMENTS , THE PARKING | | | AREA ON THE BACK OF THE BUILDING SHALL MEET THE | | | LANDSCAPE REQUIREMENTS FOR PAKING LOTS. A 5 FOOT WIDE | | | PLANTING AREA WITH A HEDGE AND A TREE SHALL BE PROVIDED | | | ALONG THE QUADRILLE BOULEVARD FRONTAGE. | | | 3. PARKING SPACES SHALL BE RESTRIPED MEETING STALL | | | DIMENSIONS AND STRIPING DETAIL. WHEEL STOPS SHALL BE | | | INSTALLED, AND IF DIMENSIONS ALLOW BASE PLANTING SHALL | | | BE INSTALLED ALONG THE FACADE. | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439. |
|
|