Plan Review Details - Permit 19020935
Plan Review Stops For Permit 19020935
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-05-23 Cont ID  
Sent By pvalenti Date 2019-05-23 Time 17:57 Rev Time 0.00
Received By pvalenti Date 2019-05-23 Time 17:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-14 Cont ID  
Sent By pvalenti Date 2019-05-14 Time 09:19 Rev Time 0.00
Received By pvalenti Date 2019-05-14 Time 07:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-12 Cont ID  
Sent By jwitmer Date 2019-03-12 Time 14:02 Rev Time 0.00
Received By jwitmer Date 2019-03-12 Time 11:21 Sent To  
Notes
2019-03-12 14:02:472017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020935
 ADD: 9835 OKEECHOBEE BLVD.
 CONT: TBD/ TO BE DETERMINED
 TEL: 954-426-5144
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. MARCH 12/ 2019
 ACTION: DENIED
  
 1) SHEET A0.0 FOR REFUSE ENCLOSURE AND GATES:
 1A) MISSING UNDER WHAT CODE IS ENCLOSURE WAS DESIGNED?
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 2017 FBC-B WAS ADOPTED STATEWIDE DEC. 31/2017
  
 1B) SHEET A0.0 DOES NOT PROVIDE THE WIND DESIGN
 CRITERIA.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1B)(1.) ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND
 GUST), MILES PER HOUR AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 1B)(2.) RISK CATEGORY.
  
 1B)(3.) WIND EXPOSURE. APPLICABLE WIND DIRECTION IF
 MORE THAN ONE WIND EXPOSURE IS UTILIZED. TABLE
 1609.7.2. HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 1B)(4.) IF APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1B)(5.) DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-05-14 Cont ID  
Sent By jpearson Date 2019-05-14 Time 16:10 Rev Time 0.00
Received By jpearson Date 2019-05-14 Time 15:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-16 Cont ID  
Sent By jpearson Date 2019-03-16 Time 10:58 Rev Time 0.00
Received By jpearson Date 2019-03-16 Time 10:53 Sent To  
Notes
2019-03-16 10:58:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2019-05-23 Cont ID  
Sent By rrossano Date 2019-05-23 Time   Rev Time 0.00
Received By rrossano Date 2019-05-23 Time   Sent To B
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2019-05-17 Cont ID  
Sent By mgonzale Date 2019-05-17 Time   Rev Time 0.50
Received By mgonzale Date 2019-05-17 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2019-03-20 Cont ID  
Sent By RRossano Date 2019-03-20 Time   Rev Time 0.50
Received By rrossano Date 2019-03-20 Time   Sent To I
Notes
2019-03-20 09:06:26PASSED WITH PROVISO: PROVIDE DETECTABLE WARNING
 SURFACES FOR PEDESTRIAN CONNECTIVITY AT NEW CROSSWALK
 CONNECTIONS PER BUILDING CODE.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-02-26 Cont ID  
Sent By scaldero Date 2019-02-26 Time 11:40 Rev Time 0.00
Received By scaldero Date 2019-02-26 Time 11:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-23 Cont ID  
Sent By pvalenti Date 2019-05-23 Time 17:57 Rev Time 0.00
Received By pvalenti Date 2019-05-17 Time 14:59 Sent To  
Notes
2019-05-20 14:59:19RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-20 Cont ID  
Sent By shill Date 2019-05-20 Time 06:45 Rev Time 0.00
Received By shill Date 2019-04-25 Time 15:55 Sent To  
Notes
2019-04-26 15:55:22B19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-20 Cont ID  
Sent By cpuell Date 2019-03-20 Time 10:16 Rev Time 0.00
Received By cpuell Date 2019-02-20 Time 13:54 Sent To  
Notes
2019-02-21 13:55:03B08

Review Stop Z ZONING
Rev No 3 Status P Date 2019-05-21 Cont ID  
Sent By llouie Date 2019-05-21 Time   Rev Time 0.00
Received By llouie Date 2019-05-21 Time   Sent To ENG
Notes
2019-05-21 13:27:02SEPARATE PERMIT APPLICATIONS AND REVIEW REQUIRED FOR
 THE FOLLOWING: LANDSCAPE/IRRIGATION, AND
 LIGHTING/PHOTOMETRICS.

Review Stop Z ZONING
Rev No 2 Status F Date 2019-05-17 Cont ID  
Sent By llouie Date 2019-05-17 Time   Rev Time 0.00
Received By llouie Date 2019-05-17 Time   Sent To  
Notes
2019-05-17 13:34:11** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) REQUIRES APPROVAL OF A MINOR PD AMENDMENT TO THE
 BAYWINDS RPD PRIOR TO BUILDING PERMIT. PLEASE NOTE THAT
 AN APPLICATION FOR A MINOR PD AMENDMENT HAS BEEN
 SUBMITTED AND IS PENDING STAFF REVIEW (REFERENCE: PB
 1087XXX).
  
  
 NOTES:
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * MINOR PD AMENDMENT APPLICATION: PB 1087XXX
  
 * ZONE: RPD (BAYWINDS)
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-03-01 Cont ID  
Sent By llouie Date 2019-03-01 Time   Rev Time  
Received By llouie Date 2019-03-01 Time   Sent To  
Notes
2019-03-01 15:21:34** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) REQUIRES APPROVAL OF A MINOR PD AMENDMENT TO THE
 BAYWINDS RPD PRIOR TO BUILDING PERMIT. PLEASE NOTE THAT
 AN APPLICATION FOR A MINOR PD AMENDMENT HAS BEEN
 SUBMITTED AND IS PENDING STAFF REVIEW (REFERENCE: PB
 1087XXX).
  
  
 NOTES:
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * MINOR PD AMENDMENT APPLICATION: PB 1087XXX
  
 * ZONE: RPD (BAYWINDS)
  