Plan Review Details - Permit 19020934
Plan Review Stops For Permit 19020934
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-06-07 Cont ID  
Sent By rmcdouga Date 2019-06-07 Time 16:38 Rev Time 0.00
Received By rmcdouga Date 2019-06-07 Time 16:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-05-14 Cont ID  
Sent By rmcdouga Date 2019-05-14 Time 16:23 Rev Time 0.00
Received By rmcdouga Date 2019-05-14 Time 09:09 Sent To  
Notes
2019-05-14 16:23:102017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020934
 ADD: 3030 S DIXIE SUITES 7 & 8
 CONT: TEKONICA INDUSTRIES INC.
 TEL: 561-745-2858
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: 5/14/2019
 ACTION: DENIED
  
 1) COMPLIED.
  
 2A) COMPLIED.
  
 2B) COMPLIED.
  
 2C) COMPLIED
  
 3A) PARTIALLY COMPLIED. SUBMIT PRODUCT APPROVALS OR
 ENGINEERING FOR THE A/C WALL BRACKET. THE INFORMATION
 THAT WAS SUBMITTED IS NOT A PRODUCT APPROVAL. SHEET 1.1
 INDICATES THE REMOVAL AND REPLACEMENT OF BRACKET FOR
 WALL HUNG A/C CONDENSER. SHEET 4.1 DETAIL FOR WALL
 BRACKET INDICATES THE INSTALLATION OF A MIAMI TECH WALL
 BRACKET SYSTEM, PLEASE PROVIDE THE PRODUCT APPROVAL OR
 ENGINEERING FOR THIS BRACKET AND ANCHOR OF THE
 CONDENSER TO THE WALL BRACKET.
 2017 FBC-B 1609.1.2 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(C) WALL LOUVERS, OR OTHER PRODUCTS TESTED IN
 REGARDS TO NEW TECHNOLOGY
  
 3B) COMPLIED.
  
 3C) 2017 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING. FBC-B-1609.6.4.4.1 COMPONENTS
 AND CLADDING. WIND PRESSURE FOR EACH COMPONENT OR
 CLADDING ELEMENT IS TO BE DESIGNED FOR WIND PRESSURES
 COMPONENTS AND ATTACHMENTS.
  
 4) COMPLIED.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 6) NEW COMMENT. THE LIFE SAFETY PLAN, SHEET 3.1, IS
 MISSING FROM THE PLAN SETS. FBC 107.2.1
  
 ROBERT MCDOUGAL
 COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6714
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-12 Cont ID  
Sent By jwitmer Date 2019-03-12 Time 11:12 Rev Time 0.00
Received By jwitmer Date 2019-03-11 Time 10:39 Sent To  
Notes
2019-03-12 11:12:342017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020934
 ADD: 3030 S DIXIE SUITES 7 & 8
 CONT: TEKONICA INDUSTRIES INC.
 TEL: 561-745-2858
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 12/ 2019
 ACTION: DENIED
  
 1) SHEET 2.1 THE DESIGNER OF RECORD HAS INDICATED THIS
 IS A LEVEL III ALTERATION. PLEASE PROVIDE CODE
 COMPLIANCE WITH THE 2017 EXISTING BUILDING CODE
 SECTION:
 [BS] 907.4.1 EVALUATION AND ANALYSIS. AN ENGINEERING
 EVALUATION AND ANALYSIS THAT ESTABLISHES THE STRUCTURAL
 ADEQUACY OF THE ALTERED STRUCTURE SHALL BE PREPARED BY
 A REGISTERED DESIGN PROFESSIONAL AND SUBMITTED TO THE
 CODE OFFICIAL.
  
 2A) SHEET 2.1 THE DESIGNER OF RECORD HAS NOTED ON THE
 PLANS THE NEW DOOR OPENINGS TO THE EXTERIOR BACK OF THE
 TENANT SPACE ARE TO BE A MIAMI-DADE NOA 17- 17-0426.02.
 SUBMITTED WITH THE DESIGNER OF RECORDS APPROVAL IS NOA
 14-1021.03. PLEASE UPDATE THE NOTE ON SHEET 2.1 TO
 COINCIDE WITH THE APPROVED NOA. 107.2.1.2 ADDITIONAL
 INFORMATION NEEDED.
  
 2B) WITHIN THE APPROVED NOA BY THE DESIGNER OF RECORD
 THERE IS 2 DOOR LOCKING TYPES, A DEADBOLT AND LOCK OR
 PANIC HARDWARE DEVICE, PLEASE EITHER CIRCLE ON THE
 PRODUCT APPROVAL (NOA 17-0426.02) OR INDICATE ON SHEET
 2.1. 1010.1.10 PANIC AND FIRE EXIT HARDWARE.2017 FBC-B.
  
 2C) PLEASE NOTE THERE IS NO WIND DESIGN CRITERIA. 2017
 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 3A) SHEET 1.1 INDICATES THE REMOVAL AND REPLACEMENT OF
 BRACKET FOR WALL HUNG A/C CONDENSER. SHEET 4.1 DETAIL
 FOR WALL BRACKET INDICATES THE INSTALLATION OF A MIAMI
 TECH WALL BRACKET SYSTEM, PLEASE PROVIDE THE PRODUCT
 APPROVAL OR ENGINEERING FOR THIS BRACKET AND ANCHOR OF
 THE CONDENSER TO THE WALL BRACKET.
 2017 FBC-B 1609.1.2 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(C) WALL LOUVERS, OR OTHER PRODUCTS TESTED IN
 REGARDS TO NEW TECHNOLOGY
  
 3B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3C) 2017 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING. FBC-B-1609.6.4.4.1 COMPONENTS
 AND CLADDING. WIND PRESSURE FOR EACH COMPONENT OR
 CLADDING ELEMENT IS TO BE DESIGNED FOR WIND PRESSURES
 COMPONENTS AND ATTACHMENTS.
  
 4) THERE ARE MULTIPLE OF LOOSE SHEETS (1.1, 4.1 & 6.1)
 IN THE PERMIT PACKAGE, PLEASE PROVIDE ADDITIONAL
 INFORMATION ON THESE SHEETS? 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2019-06-20 Cont ID  
Sent By jpearson Date 2019-06-20 Time 11:19 Rev Time 0.00
Received By jpearson Date 2019-06-20 Time 11:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2019-06-14 Cont ID  
Sent By jpearson Date 2019-06-14 Time 08:36 Rev Time 0.00
Received By jpearson Date 2019-06-14 Time 08:36 Sent To I
Notes
2019-06-14 08:26:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE AND
 INDIVIDUAL PANELS, INCLUDE EXISTING AND NEW LOADS TO
 CONFIRM CAPACITY OF SERVICE IS ADEQUATE. RISER SHOWS
 TWO 200 AMP METERS TO UNITS, WHERE ARE THE LOADS FOR
 THESE? NEW 100 AMP PANEL B SHOWS A NEW RTU, BUT ONLY
 THE BLOWER MOTOR LOAD IS INCLUDED. THE LARGER OF AC OR
 HEAT LOAD SHOULD BE INCLUDED IN THIS PANEL LOAD.
 PROVIDE SPEC SHEET FOR NEW RTU WITH ELECTRICAL
 REQUIREMENTS. NEC 110.3, 215.2, 220, 220.60, 408.30;
 WPB FBC 107.2.1 (4TH REVIEW, STILL NOT CLARIFIED OR
 CORRECTED. LOAD CALCULATION FOR 600 AMP MAIN NOT
 PROVIDED. ADDITIONALLY, THE PANEL SCHEDULE SHOWS
 CIRCUITS A-21, A-23, A-25, AND A-27 AS SPARES. WHY IS
 THERE NO LOAD INCLUDED FOR THESE STYLING STATIONS? THIS
 WOULD NOT BE CALCULATED AT 180 VA PER RECEPTACLE AS
 THIS IS FOR A SPECIFIC LOAD. ALSO, THERE IS NOT LOAD
 INCLUDED FOR THE EXHAUST FANS SHOWN ON THE MECHANICAL
 PLAN. NEC 220, 220.14(A) PROVIDE CLARIFICATION AND
 CORRECTIONS.)
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-06-07 Cont ID  
Sent By jpearson Date 2019-06-07 Time 13:20 Rev Time 0.00
Received By jpearson Date 2019-06-07 Time 13:20 Sent To  
Notes
2019-06-07 13:20:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE AND
 INDIVIDUAL PANELS, INCLUDE EXISTING AND NEW LOADS TO
 CONFIRM CAPACITY OF SERVICE IS ADEQUATE. RISER SHOWS
 TWO 200 AMP METERS TO UNITS, WHERE ARE THE LOADS FOR
 THESE? NEW 100 AMP PANEL B SHOWS A NEW RTU, BUT ONLY
 THE BLOWER MOTOR LOAD IS INCLUDED. THE LARGER OF AC OR
 HEAT LOAD SHOULD BE INCLUDED IN THIS PANEL LOAD.
 PROVIDE SPEC SHEET FOR NEW RTU WITH ELECTRICAL
 REQUIREMENTS. NEC 110.3, 215.2, 220, 220.60, 408.30;
 WPB FBC 107.2.1 (3RD REVIEW, STILL NOT CLARIFIED. LOAD
 CALCULATION FOR 600 AMP MAIN NOT PROVIDED.
 ADDITIONALLY, THE PANEL SCHEDULE SHOWS CIRCUITS A-21,
 A-23, A-25, AND A-27 AS SPARES. WHY IS THERE NO LOAD
 INCLUDED FOR THESE STYLING STATIONS? THIS WOULD NOT BE
 CALCULATED AT 180 VA PER RECEPTACEL AS THIS IS FOR A
 SPECIFIC LOAD. NEC 220.14(A) PROVIDE CLARIFICATION AND
 CORRECTIONS.)
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
  
 NEW COMMENT:
  
 7. CIRCUITS FROM UNIT 8 (PANEL B) ARE SHOWN FEEDING
 LOADS IN THE UNIT 7, AND VICE VERSA, WHICH IS A CODE
 VIOLATION. EACH OCCUPANT SHALL HAVE READY ACCESS TO ALL
 OVERCURRENT DEVICES PROTECTING THE CONDUCTORS SUPPLYING
 THAT OCCUPANCY. PROVIDE CORRECTION. NEC 240.24(B)
 8. EACH TENANT SPACE REQUIRES A SIGN CIRCUIT. PROVIDE
 DEDICATED CIRCUIT AND CONTROL FOR SIGN. NEC 600.5; FBC
 EC 405.2.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-05-15 Cont ID  
Sent By jpearson Date 2019-05-15 Time 10:47 Rev Time 0.00
Received By jpearson Date 2019-05-15 Time 07:50 Sent To  
Notes
2019-05-15 10:47:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE AND
 INDIVIDUAL PANELS, INCLUDE EXISTING AND NEW LOADS TO
 CONFIRM CAPACITY OF SERVICE IS ADEQUATE. RISER SHOWS
 TWO 200 AMP METERS TO UNITS, WHERE ARE THE LOADS FOR
 THESE? NEW 100 AMP PANEL B SHOWS A NEW RTU, BUT ONLY
 THE BLOWER MOTOR LOAD IS INCLUDED. THE LARGER OF AC OR
 HEAT LOAD SHOULD BE INCLUDED IN THIS PANEL LOAD.
 PROVIDE SPEC SHEET FOR NEW RTU WITH ELECTRICAL
 REQUIREMENTS. NEC 110.3, 215.2, 220, 220.60, 408.30;
 WPB FBC 107.2.1 (INFORMATION NOT CLARIFIED. ARE THERE
 TWO 200 AMP METERS FEEDING OTHER LOADS TO UNIT 7 AND 8,
 WHERE ARE THE METERS FOR THE 100 AMP SINGLE PHASE
 PANELS, AND WHAT IS THE LOAD OF THE 600 AMP MAIN? ALSO,
 WHEN LOADS STATED ARE ADDED TOGETHER, THE AMOUNT IS
 DIFFERENT THAN WHAT IS STATED FOR A PHASE OF EACH
 PANEL. THE CORRECTED MATH SHOWS THE PANEL AND FEEDERS
 AS OVERLOADED. PROVIDE CLARIFICATIONS AND CORRECTIONS.)
 2. PROVIDE LOCATION OF ALL PANELS IN UNITS. PROVIDE
 PANEL SCHEDULES FOR ALL PANELS INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4 (NO REPLY TO THIS COMMENT.)
 3. SHOW WINDOW RECEPTACLES ARE SHOWN ON PANEL SCHEDULE,
 BUT NOT SHOWN ON PLAN. PROVIDE CORRECTION. WPB FBC
 107.2.1; NEC 210.62 (COMMENT NOT ADDRESSED. PROVIDE
 SHOW WINDOW OUTLETS PER CODE.)
 4. ALL RECEPTACLES WITHIN 6 FEET OF A SINK MUST BE GFCI
 PROTECTED. PROVIDE CORRECTION. NEC 210.8 (RECEPTACLE
 OOUTLET ADJACENT TO HAIR WASH AREA NOT CORRECTED.)
 5. CORRECTED.
 6. PROVIDE COPY OF CONTRACT TO VERIFY VALUE OF WORK FOR
 TOTAL PROJECT. WPB FBC 109.3 (NOT PROVIDED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-16 Cont ID  
Sent By jpearson Date 2019-03-16 Time 10:50 Rev Time 0.00
Received By jpearson Date 2019-03-15 Time 10:56 Sent To  
Notes
2019-03-16 10:50:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE AND
 INDIVIDUAL PANELS, INCLUDE EXISTING AND NEW LOADS TO
 CONFIRM CAPACITY OF SERVICE IS ADEQUATE. RISER SHOWS
 TWO 200 AMP METERS TO UNITS, WHERE ARE THE LOADS FOR
 THESE? NEW 100 AMP PANEL B SHOWS A NEW RTU, BUT ONLY
 THE BLOWER MOTOR LOAD IS INCLUDED. THE LARGER OF AC OR
 HEAT LOAD SHOULD BE INCLUDED IN THIS PANEL LOAD.
 PROVIDE SPEC SHEET FOR NEW RTU WITH ELECTRICAL
 REQUIREMENTS. NEC 110.3, 215.2, 220, 220.60, 408.30;
 WPB FBC 107.2.1
 2. PROVIDE LOCATION OF ALL PANELS IN UNITS. PROVIDE
 PANEL SCHEDULES FOR ALL PANELS INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4
 3. SHOW WINDOW RECEPTACLES ARE SHOWN ON PANEL SCHEDULE,
 BUT NOT SHOWN ON PLAN. PROVIDE CORRECTION. WPB FBC
 107.2.1; NEC 210.62
 4. ALL RECEPTACLES WITHIN 6 FEET OF A SINK MUST BE GFCI
 PROTECTED. PROVIDE CORRECTION. NEC 210.8
 5. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63
 6. PROVIDE COPY OF CONTRACT TO VERIFY VALUE OF WORK FOR
 TOTAL PROJECT. WPB FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-06-06 Cont ID  
Sent By pleduc Date 2019-06-06 Time   Rev Time 0.00
Received By pleduc Date 2019-06-06 Time 16:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2019-04-26 Cont ID  
Sent By scaldero Date 2019-04-26 Time 10:32 Rev Time 0.00
Received By scaldero Date 2019-04-26 Time 10:24 Sent To  
Notes
2019-04-26 10:29:26PERMIT # 19020934
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENTS: ORIGINAL COMMENTS NOT ADDRESSED IN
 RESUBMISSION.
  
 1) SHEET C.1: SHEET INDEX SHOWS A LIFE SAFETY PLAN
 IDENTIFIED AS SHEET 3.1. THIS SHEET WAS NOT PROVIDED IN
 THIS SUBMISSION. SHEET 2.1 IS DUPLICATED.
  
 2) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-02-26 Cont ID  
Sent By scaldero Date 2019-02-26 Time 10:31 Rev Time 0.00
Received By scaldero Date 2019-02-26 Time 10:26 Sent To  
Notes
2019-02-26 10:31:54PERMIT # 19020934
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) SHEET C.1: SHEET INDEX SHOWS A LIFE SAFETY PLAN
 IDENTIFIED AS SHEET 3.1. THIS SHEET WAS NOT PROVIDED IN
 THIS SUBMISSION. SHEET 2.1 IS DUPLICATED.
  
 2) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2019-06-10 Cont ID  
Sent By gjohnson Date 2019-06-10 Time 15:37 Rev Time 0.00
Received By gjohnson Date 2019-06-10 Time 15:37 Sent To  
Notes
2019-06-10 15:38:52GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-04-29 Cont ID  
Sent By thunt Date 2019-04-29 Time 10:46 Rev Time 0.00
Received By thunt Date 2019-04-29 Time 10:46 Sent To  
Notes
2019-04-29 10:52:34GAS 2ND REVIEW**DENIED**
  
  
 *FL ST 553.80 (B)2B WITH RESPECT TO EVALUATION OF
 DESIGN PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT
 FINDS IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH
 THE FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW.
  
  
  
 1) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6
  
 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS)
  
 3) 2ND REQUEST**SUBMIT TWO COPIES OF THE APPLICABLE
 SIZING TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A
 NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH SIZING
 TABLE(S) FROM THE GAS CODE OR OTHER STANDARD THAT WERE
 USED IN THE DESIGN OF THIS GAS SYSTEM. REFER TO THE
 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES
 402.4 (1) THRU 402.4 (37)
  
 4) 2ND REQUEST**GAS TANKLESS CALLED OUT ON SHT.5.1 AS
 140,000 BTU'S. INSTALLATION MANUAL PROVIDE DOES NOT
 LIST A MODEL WITH THAT BTU RATING. PLEASE CLARIFY AND
 CALL OUT MODEL OF TANKLESS BEING USED. FBC 107.2.1
  
 5) 2ND REQUEST**DRYER SPEC SUBMITTED DOES NOT SHOW
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1,
  
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-03-13 Cont ID  
Sent By thunt Date 2019-03-13 Time 11:52 Rev Time 0.00
Received By thunt Date 2019-03-13 Time 11:52 Sent To  
Notes
2019-03-13 11:55:47GAS 1ST REVIEW**DENIED**
  
 THERE IS A GAS DRYER AND GAS TANKLESS WATER HEATER ON
 THIS PLAN BUT NOT SUPPORTING DOCUMENTS SUPPLIED ON THIS
 PLAN. PROVIDE A COMPLETE GAS ISOMETRIC DRAWNING INCLUDE
 SIZE, PIPING MATERIAL AND SIZING CHARTS BEING USED.
 PLEASE INCLUDE THE MANUFACTURE INSTALLATION MANUALS AS
 WELL. FBC 107.3.5
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561-248-2703
  
 SAMANTHA HILL
 CHIEF PLANS EXAMINER
 561-805-6724

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2019-06-20 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-18 Time 09:49 Sent To  
Notes
2019-06-20 09:49:46RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2019-06-14 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-11 Time 15:29 Sent To  
Notes
2019-06-12 15:30:00RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-06-10 Cont ID  
Sent By gjohnson Date 2019-06-10 Time 15:38 Rev Time 0.00
Received By gjohnson Date 2019-06-03 Time 15:50 Sent To  
Notes
2019-06-04 15:50:45B27

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-05-15 Time   Rev Time 0.00
Received By lmarchan Date 2019-04-22 Time 11:04 Sent To  
Notes
2019-04-23 11:04:28B07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-03-19 Time   Rev Time 0.00
Received By lmarchan Date 2019-02-20 Time 10:45 Sent To  
Notes
2019-02-21 10:45:18B07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-03-12 Cont ID  
Sent By jwitmer Date 2019-03-12 Time 11:12 Rev Time 0.00
Received By jwitmer Date 2019-03-11 Time 10:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-06-07 Cont ID  
Sent By ccole Date 2019-06-07 Time 15:39 Rev Time 0.00
Received By ccole Date 2019-06-07 Time 14:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-05-02 Cont ID  
Sent By ccole Date 2019-05-02 Time 15:35 Rev Time 0.00
Received By ccole Date 2019-05-01 Time 14:07 Sent To  
Notes
2019-05-02 16:29:422ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19020934
 5/2/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED SUBMITTED MECHANICAL PLAN SHOWS THESE
 PRIOR AND NEW DEFICIENCIES:
  
 A) THE REQUESTED EXHAUST VENTILATION CALCULATIONS WERE
 NOT PROVIDED- SEE COMMENT #1 FROM THE 1ST REVIEW
 PRINTED HERE- 1) SHEET 4.1: EF-2 AT 150 CFMS APPEARS TO
 BE UNDERSIZED FOR THE REQUIRED EXHAUST RATE OF 0.60
 CFMS PER SF. FOR THE SALON AREA- SEE TABLE 403.3.1.1
 AND PROVIDE CALCULATIONS.
  
 B) NO EXHAUST HAS BEEN PROVIDED FOR THE TREATMENT ROOM-
 TABLE 403.3.1.1 FBC M.
  
 C) NO OUTSIDE AIR DUCT OR AUTOMATIC CONTROL DAMPER HAVE
 BEEN PROVIDED FOR THE NEW 5-TON AC SYSTEM- TABLE
 403.3.1.1 FBC M & SECTION C403.2.4.3 FBC EC.
  
 D) CLARIFY THE LOCATION OF THE NEW 5-TON CONDENSER. IS
 THE UNIT TO BE GROUND MOUNTED OR WALL BRACKET MOUNTED?
 THE WALL BRACKET DETAIL SHOWN IS FOR A PACKAGE UNIT. IN
 EITHER CASE- WALL OR GROUND- COMPLETE ENGINEERING IS
 REQUIRED- SECTION 301.15 FBC M. PLEASE NOTE THAT THE
 CONDENSER BELOW THE SLOPING ROOF MAY BE DETRIMENTAL TO
 THE FUNCTION OF THE SYSTEM AND MAY BE
  
 INCONSISTENT WITH THE MANUFACTURER'S INSTALLATION AND
 WARRANTY GUIDELINES. SUBMIT DOCUMENTATION VERIFYING
 COMPLIANCE- SEE SECTION 304.1 FBC M.
  
 E) THE NEW ENERGYGAUGE COMPLIANCE REPORT INDICATES THE
 NEW 5-TON SYSTEM IS 17 SEER, HOWEVER THE SCHEDULE ON
 THE PLAN INDICATES 14 SEER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-03-19 Cont ID  
Sent By ccole Date 2019-03-19 Time 11:38 Rev Time 0.00
Received By ccole Date 2019-03-19 Time 08:45 Sent To I
Notes
2019-03-19 12:23:391ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19020934
 3/19/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 4.1: EF-2 AT 150 CFMS APPEARS TO BE UNDERSIZED
 FOR THE REQUIRED EXHAUST RATE OF 0.60 CFMS PER SF. FOR
 THE SALON AREA- SEE TABLE 403.3.1.1 AND PROVIDE
 CALCULATIONS.
  
 2) 4.1: PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF
 DAMPERS FOR THE OUTDOOR AIR INTAKES ON THE RTU'S -
 SECTION C403.2.4.3 FBC-17 ENERGY CONSERVATION.
  
 3) 4.1: THE LOCATIONS OF THE RTU'S AND DUCT TRUNKS
 BELOW THE SLOPING ROOF MAY BE DETRIMENTAL TO THE
 FUNCTION OF THE SYSTEM AND MAY BE INCONSISTENT WITH THE
 MANUFACTURER'S INSTALLATION AND WARRANTY GUIDELINES.
 SUBMIT DOCUMENTATION VERIFYING COMPLIANCE- SEE SECTION
 304.1 FBC M.
  
 4) 4.1: SITE SPECIFIC ENGINEERING IS REQUIRED FOR
 INSTALLATION OF THE RTU AND WALL BRACKET- SECTION
 301.15 FBC M. A) PROVIDE THE WIND LOAD DESIGN CRITERIA
 PER SECTION 1609 FBC B. B) PROVIDE A FL. PRODUCT
 APPROVAL OR MIAMI-DADE NOA FOR THE BRACKET. C) REQUIRED
 DETAILS- BRACKET TO WALL ATTACHMENT, AND RTU TO BRACKET
 ATTACHEMNT.
  
 5) THE SUMMARY AC LOAD CALCULATIONS MUST BE SIGNED AND
 SEALED BY A F. LICENSED ENGINEER- SECTION C403.2.1
 EXCEPTION FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-06-10 Cont ID  
Sent By gjohnson Date 2019-06-10 Time 15:37 Rev Time 0.00
Received By gjohnson Date 2019-06-10 Time 15:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-04-29 Cont ID  
Sent By thunt Date 2019-04-29 Time 11:55 Rev Time 0.00
Received By thunt Date 2019-04-29 Time 09:51 Sent To  
Notes
2019-04-29 11:55:23PLUMBING 1ST REVIEW**DENIED**
  
 ***FL ST 553.80 (B)2B WITH RESPECT TO EVALUATION OF
 DESIGN PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT
 FINDS IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH
 THE FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW.
  
  
 1) 2ND REQUEST** PLAN DOES NOT SHOW THE REQUIRED HI-LO
 DRINKING FOUNTAIN AS REQUIRED IN FBC-P 410.3. THE
 BOTTLE WATER DISPENCER'S SHOWN IS ONLY ALLOWED TO
 REPLACED UP TO 50% OF THE REQUIRED NUMBER OF DRINKING
 FOUNTAINS REQUIRED. FBC-P 410.4
  
 2) 2ND REQUEST SHT.2.1 UNDER TOILET ACCESSORY SCHEDULE
 HAS SOME INCORRECT INFORMATION FOR THE GRAB BARS. SHOW
 GRAB BAR HEIGHT AS 33"-36" TO THE TOP OF GRIPPING
 SURFACE. GB CALLS OUT 33" TO THE CENTER BUT GB1 CALLS
 OUT 33"-36" TO THE CENTER WHICH IF MOUNTED @ 36" WOULD
 HAVE THE GRIPPING SURFACE TO HIGH. FBC-ACC 609.4
  
 3) ANSWERED
  
 4) 2ND REQUEST PROVIDE THE MANUFACTURE INSTALLATION
 MANUAL FOR THE GAS TANKLESS WATER HEATER. WHICH
 MODEL.FBC 107.3.5
  
 5) 2ND REQUEST PROVIDE THE MANUFACTURES INSTALLATION
 MAUNAL SHOWING THE HAIR WAS STATIONS COMPLY WITH
 FBC-P423.3. SHOW AS TEMP LIMITED BY A ASSE 1070 DEVICE.
  
 6) 2ND REQUEST PROVIDE A SEPERATE SIZED WATER ISOMETRIC
 DRAWNING WITH PIPE SIZING. FBC 107.3.5
  
 7) 2ND REQUESTSHT 5.1 WASHING MACHINE DETAIL CALLS OUT
 3" PIPING TO WASHING MACHINE BOX BUT NOTE TOP CENTER
 SAAYS PROPOSED WASHING WITH 2" PVC. PLEASE CLEARIFY.
 FBC 107.3.5
  
 8) NEW COMMENT: PROVIDE A LINT INTERCEPTOR FOR THE
 WASHING MACHINE. PROVIDE COMPLETE INSTALLATION MANUALS
 AND REVISE SANITARY ISOMETRIC DRAWING. FBC 1003.1,
 1003.2, 1003.6
  
  
 PLEASE PROVIDE A NARRATIVE REAPONSE TO ALL COMMENTS. I
 WOULD RECOMMENDED A MEETING WITH PLAN REVIEW STAFF
 BEFORE RESUBMITTING .
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-13 Cont ID  
Sent By thunt Date 2019-03-13 Time 12:39 Rev Time 0.00
Received By thunt Date 2019-03-13 Time 10:54 Sent To  
Notes
2019-03-13 12:29:09PLUMBING 1ST REVIEW**DENIED**
  
 PLAN REVIEW WAS BASED ON THIS BEING A LEVEL LLL
 RENOVATION COMPLYING WITH THE FBC 2017 6TH ED.
  
 1) PLAN DOES NOT SHOW THE REQUIRED HI-LO DRINKING
 FOUNTAIN AS REQUIRED IN FBC-P 410.3. THE BOTTLE WATER
 DISPENCER SHOWN IS ONLY ALLOWED TO REPLACED UP TO 50%
 OF THE REQUIRED NUMBER OF DRINKING FOUNTAINS REQUIRED.
 FBC-P 410.4
  
 2) SHT.2.1 UNDER TOILET ACCESSORY SCHEDULE HAS SOME
 INCORRECT INFORMATION FOR THE GRAB BARS. BEING THAT YOU
 HAVE A CORRECT TOILET ROOM ELEVATIONS ON SHT5.1 YOU CAN
 REMOVE THE NOTES OR CORRECT AS FOLLOWED. GB-1 (SIDE
 BAR) 42" BAR MUST BE MOUNT @ 12" TO GET THE REQUIRED
 OVERALL 54".FBC-A 604.5.1 (2B) GB-1 (REAR) 36" GRAB BAR
 SHALL BE MOUNT 12" FOR CENTER OF TOILET BEING THAT THE
 TOILET IS PERMITTED TO BE 16"-18" IT CAN BE 4'-6' FROM
 THE SIDE WALL. FBC-A 604.5.2
  
 3) THE EMPLOYEE BREAKROOM SINK SHALL COMPLY WITH
 FLORIDA ACCESSIBILITY CHAPTER 6 SAME AS THE WAITING
 ROOM DOES. PLEASE PROVIDE CLEAR FLOOR SPACE AND SHOW
 CABINET HEIGHT DETAIL LISTING MAX 34".FBC-A 606.2,
 606.3
  
 4) PROVIDE THE MANUFACTURE INSTALLATION MANUAL FOR THE
 GAS TANKLESS WATER HEATER. FBC 107.3.5
  
 5) PROVIDE THE MANUFACTURES INSTALLATION MAUNAL SHOWING
 THE HAIR WAS STATIONS COMPLY WITH FBC-P423.3 AND ARE
 TEMP LIMITED BY A ASSE 1070 DEVICE.
  
 6) PROVIDE A SEPERATE SIZED WATER ISOMETRIC DRAWNING.
 FBC 107.3.5. IF THE DEVELOPED LENGHT OF THE HOT WATER
 LINE IS OVER 50' A RECIRCULATION SYSTEM WAS ALSO BE
 INSTALL. FBC-P 607.2 AND INSULATED WITH 1" WALL
 COMPLYING WITH FBC-ENERGY C404.6
  
 7) SHT 5.1 WASHING MACHINE DETAIL CALLS OUT 3" PIPING
 TO WASHING MACHINE BOX BUT NOTE TOP CENTER SAAYS
 PROPOSED WASHING WITH 2" PVC. PLEASE CLEARIFY. FBC
 107.3.5
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561-248-2703
  
 SAMANTHA HILL
 CHIEF PLANS EXAMINER
 561-805-6724
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status N Date 2019-05-14 Cont ID  
Sent By skennedy Date 2019-05-14 Time 17:02 Rev Time 0.00
Received By skennedy Date 2019-05-14 Time 17:02 Sent To  
Notes
2019-05-14 17:03:16PER MC

Review Stop Z ZONING
Rev No 1 Status P Date 2019-03-06 Cont ID  
Sent By mcruz Date 2019-03-06 Time 14:52 Rev Time 0.00
Received By mcruz Date 2019-03-06 Time 13:48 Sent To PC
Notes
***NONE***