Plan Review Details - Permit 19020927
Plan Review Stops For Permit 19020927
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-13 Cont ID  
Sent By shill Date 2019-05-13 Time 08:05 Rev Time 0.00
Received By shill Date 2019-05-13 Time 08:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-11 Cont ID  
Sent By jwitmer Date 2019-03-11 Time 15:04 Rev Time 0.00
Received By jwitmer Date 2019-03-11 Time 14:10 Sent To  
Notes
2019-03-11 15:04:122017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020927
 ADD: 4100 S DIXIE HWY. SUITE: B
 CONT: LEIGHTON MCGINN CO.
 TEL: 561-863-4455
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY / MARCH 11/ 2019
 ACTION: DENIED
 1) IT APPEARS THE SUBMITTED PLANS WERE ORIGINALLY PAPER
 PLANS THAT WERE CONVERTED TO DIGITAL PLANS, NONE OF THE
 DESIGNER OF RECORD SIGNATURE AND SEAL ARE DIGITAL
 SIGNATURE AND SEAL.
 ARCHITECTS: FLORIDA ADMINISTRATIVE CODE 61G1-16.005.
 PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR
 ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 2) SHEET 004_A2 THE WATER CLOSET DETAIL SHOWS THE GRAB
 BARS BEING MEASURED FROM THE CENTERLINE OF THE GRAB BAR
 TO FINISH FLOOR. PLEASE NOTE UNDER THE 2017
 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 3) SHEET 005_A3 SHOWS AN OPEN SHELF THE BOTTOM AT 56
 INCHES OR 4 FOOT 8 INCHES ABOVE THE FINISH FLOOR, IT
 APPEARS TO BE FOR A MICROWAVE. SHEET 006_E1 THE POWER
 PLAN SHOWS AN OUTLET AT 72 INCHES FOR A MICROWAVE
 MACHINE. WITH A MICROWAVE PLACED IN THIS POSITION
 COMPLIANCE CAN NOT BE ACHIEVED FOR CODE SECTIONS, 2017
 FBC-ACCESSIBILITY CODE:
  
 308 REACH RANGES. 308.2 FORWARD REACH./ 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-25 Cont ID  
Sent By jleahy Date 2019-04-25 Time 15:10 Rev Time 0.00
Received By jleahy Date 2019-04-25 Time 15:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-03-11 Cont ID  
Sent By jleahy Date 2019-03-11 Time 08:42 Rev Time 0.00
Received By jleahy Date 2019-03-08 Time 17:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-04-10 Cont ID  
Sent By scaldero Date 2019-04-10 Time 13:06 Rev Time 0.00
Received By scaldero Date 2019-04-10 Time 13:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-02-25 Cont ID  
Sent By scaldero Date 2019-02-25 Time 11:24 Rev Time 0.00
Received By scaldero Date 2019-02-25 Time 11:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-13 Cont ID  
Sent By shill Date 2019-05-13 Time 08:09 Rev Time 0.00
Received By shill Date 2019-04-09 Time 12:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-03-26 Time   Rev Time 0.00
Received By lmarchan Date 2019-02-20 Time 15:18 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-03-11 Cont ID  
Sent By jwitmer Date 2019-03-11 Time 15:04 Rev Time 0.00
Received By jwitmer Date 2019-03-11 Time 14:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-04-25 Cont ID  
Sent By ccole Date 2019-04-25 Time 11:58 Rev Time 0.00
Received By ccole Date 2019-04-25 Time 11:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-03-26 Cont ID  
Sent By ccole Date 2019-03-26 Time 07:42 Rev Time 0.00
Received By ccole Date 2019-03-19 Time 12:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-22 Cont ID  
Sent By thunt Date 2019-04-22 Time 07:09 Rev Time 0.00
Received By thunt Date 2019-04-18 Time 13:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-18 Cont ID  
Sent By thunt Date 2019-03-18 Time 15:12 Rev Time 0.00
Received By thunt Date 2019-03-15 Time 15:01 Sent To  
Notes
2019-03-18 15:12:43PLUMBING 1ST REVIEW PERMIT # 19020927**DENIED**
  
 1) SHT A2 CALLS OUT GRAB BARS TO BE MOUNTED 33"-36" TO
 THE CENTER LINE OF THE BAR.GRAB BARS SHALL BE INSTALLED
 IN A HORIZONTAL POSITION, 33 INCHES (840 MM) MINIMUM
 AND 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE FBC-ACC
 609.4\
  
 2) SHOW PAPER DISPENSER 7"-9" FROM THE FRONT OF THE
 TOILET. FBC-ACC 604.9.6
  
 3)IS IT YOUR INTENT TO MAKE ALL FIXTURE AND RESTROOMS
 COMPLY WITH THE FLORIDA ACCESSIBILITY? SHT.T1 UNDER
 GENERAL NOTES E) CODE NOTES #8 CALLS FOR ALL FIXTURES
 AND HARDWARE TO COMPLY WITH ADA/ FBC-ACC. FBC 107.2.1
  
 4) PROVIDE COMPLETE BATHROOM LAY OUT SHOWING CLEAR
 FLOOR SPACE FOR BOTHT THE TOILET AND SINK COMPLYING
 WITH FBC-ACC604.3.2, 604.8.1.6
  
 TIM HUNT
 PLUMBING INSPECTOR/PLUMBING PLAN EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-05-13 Cont ID  
Sent By shill Date 2019-05-13 Time 08:06 Rev Time 0.00
Received By shill Date 2019-05-13 Time 08:06 Sent To  
Notes
2019-04-18 13:35:24ALL SHEETS OK AND ARE DIGITALLY SIGNED

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-03-22 Cont ID  
Sent By shill Date 2019-03-22 Time 15:21 Rev Time 0.00
Received By shill Date 2019-03-22 Time 15:21 Sent To  
Notes
2019-03-22 15:22:08SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THE PLANS SUBMITTED ARE NOT DIGITALLY SIGNED AND
 SEALED.
  
 DO THE DESIGN PROFESSIONALS HAVE DIGITAL SEALS? IF YES,
 PLEASE PROVIDE DIGITALLY SIGNED PLANS.
  
 IF THEY DO NOT, AFTER ALL REVIEWS HAVE PASSED, SUBMIT
 ONE ORIGINAL SIGNED AND SEALED PAPER SET TO THE
 BUILDING DIVISION.
  
  
2019-03-11 14:44:45IT APPEARS THE SUBMITTED PLANS WERE ORIGINALLY PAPER
 PLANS THAT WERE CONVERTED TO DIGITAL PLANS, NONE OF THE
 DESIGNER OF RECORD SIGNATURE AND SEAL ARE DIGITAL
 SIGNATURE AND SEAL.
 ARCHITECTS: FLORIDA ADMINISTRATIVE CODE 61G1-16.005.
 PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR
 ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved