| 2019-02-25 08:31:25 | 02/25/2019 1ST PLUMBING/BACKFLOW REVIEW **DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR |
| | THE BACKFLOW PREVENTER. THE MAKE, MODEL, AND SIZE OF |
| | THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF WORK |
| | SECTION ON THE PERMIT APPLICATION. |
| | |
| | 2. THERE IS A DDCA AMES LFC300 8? ON PAGE 48 OF |
| | APPROVED MATERIAL LIST BUT ON PLANS IT SAYS 8" AMES |
| | 3000 SS PLEASE CLARIFY AND SUBMIT SPECIFICATION ON |
| | UNIT. |
| | |
| | 3. DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE. |
| | |
| | 4. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS |
| | ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY |
| | OF SOUTHERN CALIFORNIA (USC). PLEASE CONTACT DEPARTMENT |
| | OF PUBLIC UTILITY FIELD CUSTOMER SERVICE AT |
| | 561-822-2240 FOR DOCUMENTED CONFIRMATION THAT THE |
| | PROPOSED BACKFLOW PREVENTION DEVICE COMPLIES WITH CITY |
| | REQUIREMENTS. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |