| Plan Review Stops For Permit 19020826 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2019-05-28 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-05-28 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-05-28 |
Time |
16:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-05-22 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-05-22 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-05-22 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2019-05-22 14:02:34 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 2ND BUILDING PLAN REVIEW DENIED: | | | | | | 1. ADDITIONAL PERMITS REQUIRED. MECH., ELECTRICAL, | | | PLUMBING, GAS & ROOFING. | | | (2ND REVIEW, STILL PENDING THE PLUMBING, MECHANICAL, | | | AND GAS PERMITS.) | | | | | | | | | 2. DESIGN PROFESSIONALS SIGNATURE AND SEAL ARE COPIES. | | | PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE, | | | DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE | | | 61G15?23.001. | | | (2ND REVIEW, STILL PENDING THE CORRECTION OF SIGNATURES | | | OVER SEALS AS PER FL ADMIN. CODE RULE 61G15-23.001 TO | | | 61G15-23.003.) | | | | | | 3. OK | | | 4. OK | | | 5. OK | | | 6. OK | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY | | | RESULT IN NEW PLAN REVIEW COMMENTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-03-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-03-13 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-03-13 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2019-03-13 16:15:35 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. ADDITIONAL PERMITS REQUIRED. MECH., ELECTRICAL, | | | PLUMBING, GAS & ROOFING. | | | | | | 2. DESIGN PROFESSIONALS SIGNATURE AND SEAL ARE COPIES. | | | PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE, | | | DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE | | | 61G15-23.001. | | | | | | 3. ENERGY SUBMITTAL TO BE SIGNED BY OWNER/AGENT. | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | 4. PROVIDE SITE DRAINAGE PLAN. | | | FBC R401.3 SITE DRAINAGE | | | PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING | | | COMPLIANCE WITH FBC R401.3 DRAINAGE. | | | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER | | | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT | | | DOES NOT CREATE A HAZARD. | | | LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM | | | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 | | | INCHES WITHIN THE FIRST 10 FEET. | | | EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER | | | PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10 | | | FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE | | | DRAINAGE AWAY FROM THE STRUCTURE. | | | IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING | | | FOUNDATION SHALL BE SLOPED A MINIMUM OF | | | 2 PERCENT AWAY FROM THE BUILDING. | | | | | | FBC R 401.3 (DRAINAGE) | | | FBC 107.2.5 (SITE PLAN) | | | FBC 110.9 (IMPACT OF CONSTRUCTION) | | | | | | 5. PROVIDE FINISH FLOOR ELEVATION ON PLAN. | | | R403.1.7.3 FOUNDATION ELEVATION. | | | ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION | | | SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER | | | AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED | | | DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2 | | | PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO | | | THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN | | | BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF | | | DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT | | | ALL LOCATIONS ON THE SITE. | | | | | | 6. SHOW SIZE AND LOCATION OF ATTIC ACCESS SCUTTLE. | | | R807.1 ATTIC ACCESS. | | | BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF CONSTRUCTION | | | SHALL HAVE AN ATTIC ACCESS OPENING TO ATTIC AREAS THAT | | | HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR GREATER | | | OVER AN AREA OF NOT LESS THAN 30 SQUARE FEET (2.8 M2). | | | THE VERTICAL HEIGHT SHALL BE MEASURED FROM THE TOP OF | | | THE CEILING FRAMING MEMBERS TO THE UNDERSIDE OF THE | | | ROOF FRAMING MEMBERS. | | | THE ROUGH-FRAMED OPENING SHALL BE NOT LESS THAN 22 | | | INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE | | | LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE | | | LOCATION. WHERE LOCATED IN A WALL, THE OPENING SHALL BE | | | NOT LESS THAN 22 INCHES WIDE BY 30 INCHES HIGH (559 MM | | | WIDE BY 762 MM HIGH). WHERE THE ACCESS IS LOCATED IN A | | | CEILING, MINIMUM UNOBSTRUCTED HEADROOM IN THE ATTIC | | | SPACE SHALL BE 30 INCHES (762 MM) AT SOME POINT ABOVE | | | THE ACCESS MEASURED VERTICALLY FROM THE BOTTOM OF | | | CEILING FRAMING MEMBERS. SEE SECTION M1305.1.3 FOR | | | ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS | | | LOCATED IN ATTICS. | | | | | | R402.2.4 ACCESS HATCHES AND DOORS. | | | ACCESS DOORS FROM CONDITIONED SPACES TO UNCONDITIONED | | | SPACES (E.G., ATTICS AND CRAWL SPACES) SHALL BE | | | WEATHERSTRIPPED AND INSULATED TO A LEVEL EQUIVALENT TO | | | THE INSULATION ON THE SURROUNDING SURFACES. ACCESS | | | SHALL BE PROVIDED TO ALL EQUIPMENT THAT PREVENTS | | | DAMAGING OR COMPRESSING THE INSULATION. A WOOD FRAMED | | | OR EQUIVALENT BAFFLE OR RETAINER IS REQUIRED TO BE | | | PROVIDED WHEN LOOSE FILL INSULATION IS INSTALLED, THE | | | PURPOSE OF WHICH IS TO PREVENT THE LOOSE FILL | | | INSULATION FROM SPILLING INTO THE LIVING SPACE WHEN THE | | | ATTIC ACCESS IS OPENED, AND TO PROVIDE A PERMANENT | | | MEANS OF MAINTAINING THE INSTALLED R-VALUE OF THE LOOSE | | | FILL INSULATION. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-05-02 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2019-05-02 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2019-05-02 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2019-05-02 12:33:38 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: OK, SEE COMMENTS BELOW. | | | | | | 1.SEE PROVISO ON PLAN | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD | | | SHEETS?. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | ELECTRICAL PLANS EXAMINER/CHIEF ELECTRICAL INSPECTOR | | | 561-805-6742 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-03-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-03-13 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-03-13 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2019-03-13 17:21:56 | ELECTRICAL PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. NEC 250.64 / E3607.3.1 EQUIPMENT GROUNDING CONDUCTOR | | | REQUIRED. | | | FBC R E3607.3 | | | BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) OR BRANCH | | | CIRCUIT(S). | | | BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) OR BRANCH | | | CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR | | | GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH | | | SECTION E3608. THE GROUNDING ELECTRODE CONDUCTOR(S) | | | SHALL BE CONNECTED IN A MANNER SPECIFIED IN SECTION | | | E3607.3.1 OR, FOR EXISTING PREMISES WIRING SYSTEMS | | | ONLY, SECTION E3607.3.2. WHERE THERE IS NO EXISTING | | | GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S) | | | REQUIRED IN SECTION E3608 SHALL BE INSTALLED. | | | [250.32(A)] | | | | | | 2. NEC 225.31 & 240.21 (B) (2) / E3706.3 DISCONNECTING | | | MEANS. | | | . FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A | | | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE | | | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR | | | MAIN BREAKER AT THE PANEL FOR THE SUB-PANELS IN THE | | | GUEST HOUSE. NEC 225.31, 225.32. | | | NOTE: SHOW DISCONNECTING DEVICE ON RISER DIAGRAHM. | | | | | | 3. NEC TABLE 310.15 (B) (16) / TABLE E3705.1 - | | | ALLOWABLE AMPACITY OF INSULATED CONDUCTORS. | | | CONDUCTOR SIZE TO SUB PANEL NOT OF SUFFICIENT SIZE | | | BASED ON THE AMPACITY OF THE MAIN DISCONNECT. | | | NOTE: YOU MAY EITHER RE-SIZE THE CONDUCTORS BASED ON | | | THE REFERENCED TABLES OF INSTALL A DISCONNECT AT MAIN | | | DISCONNECT UPSTREAM OF CONDUCTORS. | | | | | | 4. INCLUDE VP NEXT TO THE SYMBOL AT THE VAPOR PROOF | | | FIXTURE IN THE SHOWER AREA. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2019-05-28 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-05-28 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-05-28 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2019-05-28 16:36:41 | GAS PLAN REVIEW | | | | | | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE | | | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. | | | PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT | | | SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE | | | SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2019-04-29 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-04-29 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-04-29 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2019-04-29 14:17:46 | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | | THIS TIME. A SEPARATE GAS PERMIT IS REQUIRED FOR A | | | CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE | | | COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF GAS | | | WORK TO BE DONE. WPB AMEND. TO FBC SEC.107.2.1. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-03-11 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-03-11 |
Time |
08:13 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-03-11 |
Time |
08:13 |
Sent To |
|
|
| Notes |
| 2019-03-11 08:19:58 | GAS 1ST REVIEW**DENIED** | | | | | | PLAN IS SHOWING A GAS TANKLESS WATER HEATER BUT NO GAS | | | PLANS OR SUPPORTING DOCUMENTS SUPPLIED. I HAVE INCLUDED | | | A GAS PLAN REVIEW CHECK LIST IN YOUR PACKET AND | | | HIGHLIGHTED THE REQUIRED ITEM YOU WILL NEED FOR PLAN | | | REVIEW, CITY RECORD SHOW EXISTING GAS ON THIS HOME. FBC | | | 107.3.5 | | | | | | | | | TIM HUNT | | | PLUMBING INSPECTOR/ PLANS EXAMINER | | | 561-805-6711 | | | 561-805-6724 | | | | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-05-21 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2019-05-21 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2019-05-21 |
Time |
12:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2019-03-05 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2019-03-05 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2019-03-05 |
Time |
16:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-05-28 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-05-28 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-05-28 |
Time |
16:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-05-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-05-22 |
Time |
17:15 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-04-24 |
Time |
14:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-03-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-03-13 |
Time |
17:23 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-02-19 |
Time |
15:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2019-05-28 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-05-28 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-05-28 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2019-05-28 16:34:37 | MU-2019-016171-0000 CT |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2019-03-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-03-13 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-03-13 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2019-03-13 11:56:28 | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | | RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS | | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2019-05-28 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-05-28 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-05-28 |
Time |
16:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2019-05-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-05-22 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-05-22 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2019-05-22 17:15:01 | MECHANICAL PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. DESIGN PROFESSIONALS SIGNATURE AND SEAL IS INVALID. | | | PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE, | | | DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE | | | 61G15-23.001. | | | | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-03-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-03-13 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-03-13 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2019-03-13 15:57:53 | MECHANICAL PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. DESIGNERS SIGNATURE AND SEAL IS A COPY. | | | PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE, | | | DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE | | | 61G15-23.001. | | | | | | 2. OWNER/AGENT TO SIGN ENERGY SUBMITTAL. | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | 3. TAMPER RESISTANT PORT CAPS REQUIRED. | | | M1411.8 LOCKING ACCESS PORT CAPS. | | | REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL | | | BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS OR | | | SHALL BE OTHERWISE SECURED TO PREVENT UNAUTHORIZED | | | ACCESS. | | | EXCEPTION: NO LOCKING-TYPE TAMPER-RESISTANT CAPS ARE | | | REQUIRED IF PORTS ARE LOCATED INSIDE THE CONDENSING | | | UNIT CABINET. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2019-05-28 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-05-28 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-05-28 |
Time |
16:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2019-04-29 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-04-29 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-04-29 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2019-04-29 14:26:33 | PLUMBING 2ND REVIEW**DENIED** | | | | | | | | | ***FL ST 553.80 (B)2B WITH RESPECT TO EVALUATION OF | | | DESIGN PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT | | | FINDS IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH | | | THE FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT | | | DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE | | | TIMES FOR FAILURE TO CORRECT A CODE VIOLATION | | | SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, | | | INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, | | | STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, | | | VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS | | | SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF | | | THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO | | | CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH | | | TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED | | | FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT | | | OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS | | | REVIEW. | | | | | | | | | | | | | | | 1) 2ND REQUEST.THE P.E SIGNATURE APPREAR'S TO BE COPIED | | | ON ALL PAGES AGAIN. SIGNATURE IS REQUIRED TO BE WET | | | SIGNED PER F.A.C 61G15-23.003. THE P.E IS ADAM GINSBURG | | | (A.G) BUT THE SIGNATURE SIGNED IS C.G. AND IS | | | DEFINITELY PIXELATED AND EACH CORRESPONDING SHEET | | | MATCHES EACH OTHER. | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-03-11 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-03-11 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-03-11 |
Time |
07:32 |
Sent To |
|
|
| Notes |
| 2019-03-11 08:23:42 | PLUMBING 1ST REVIEW**DENIED** | | | | | | 1) P.E SIGNATURE APPREAR TO BE COPIED ON ALL PAGES. | | | SIGNATURE IS REQUIRED TO BE WET SIGNED PER F.A.C | | | 61G15-23.003 | | | | | | 2) PROVIDE SPEC'S ON TANKLESS WATER HEATER. FBC 107.3.5 | | | | | | TIM HUNT | | | PLUMBING INSPECTOR/ PLANS EXAMINER | | | 561-805-6711 | | | 561-805-6724 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2019-05-22 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-05-22 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-05-22 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2019-05-22 14:13:47 | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | APPROVED WITH PROVISO: | | | | | | PROVIDE ROOFING SUB- PERMIT PRIOR TO ROOFING WORK. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-03-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-03-13 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-03-13 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2019-03-13 15:35:47 | BUILDING PLAN REVIEW - ROOFING | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE PRODUCT APPROVALS FOR NEW ROOFING SYSTEM | | | COMPONENTS. DESIGNER TO REVIEW AND APPROVE IN WRITING. | | | | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-05-21 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2019-05-21 |
Time |
12:57 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2019-05-21 |
Time |
12:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2019-03-05 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2019-03-05 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2019-03-05 |
Time |
16:36 |
Sent To |
|
|
| Notes |
|
|