Plan Review Details - Permit 19020826
Plan Review Stops For Permit 19020826
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-05-28 Cont ID  
Sent By cthroop Date 2019-05-28 Time 16:34 Rev Time 0.00
Received By cthroop Date 2019-05-28 Time 16:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-05-22 Cont ID  
Sent By pvalenti Date 2019-05-22 Time 13:38 Rev Time 0.00
Received By pvalenti Date 2019-05-22 Time 13:38 Sent To  
Notes
2019-05-22 14:02:34***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND BUILDING PLAN REVIEW DENIED:
  
 1. ADDITIONAL PERMITS REQUIRED. MECH., ELECTRICAL,
 PLUMBING, GAS & ROOFING.
 (2ND REVIEW, STILL PENDING THE PLUMBING, MECHANICAL,
 AND GAS PERMITS.)
  
  
 2. DESIGN PROFESSIONALS SIGNATURE AND SEAL ARE COPIES.
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15?23.001.
 (2ND REVIEW, STILL PENDING THE CORRECTION OF SIGNATURES
 OVER SEALS AS PER FL ADMIN. CODE RULE 61G15-23.001 TO
 61G15-23.003.)
  
 3. OK
 4. OK
 5. OK
 6. OK
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-13 Cont ID  
Sent By cthroop Date 2019-03-13 Time 15:57 Rev Time 0.00
Received By cthroop Date 2019-03-13 Time 11:18 Sent To  
Notes
2019-03-13 16:15:35BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ADDITIONAL PERMITS REQUIRED. MECH., ELECTRICAL,
 PLUMBING, GAS & ROOFING.
  
 2. DESIGN PROFESSIONALS SIGNATURE AND SEAL ARE COPIES.
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 3. ENERGY SUBMITTAL TO BE SIGNED BY OWNER/AGENT.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 4. PROVIDE SITE DRAINAGE PLAN.
 FBC R401.3 SITE DRAINAGE
 PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10
 FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE
 DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING
 FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
  
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 5. PROVIDE FINISH FLOOR ELEVATION ON PLAN.
 R403.1.7.3 FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
  
 6. SHOW SIZE AND LOCATION OF ATTIC ACCESS SCUTTLE.
 R807.1 ATTIC ACCESS.
 BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF CONSTRUCTION
 SHALL HAVE AN ATTIC ACCESS OPENING TO ATTIC AREAS THAT
 HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR GREATER
 OVER AN AREA OF NOT LESS THAN 30 SQUARE FEET (2.8 M2).
 THE VERTICAL HEIGHT SHALL BE MEASURED FROM THE TOP OF
 THE CEILING FRAMING MEMBERS TO THE UNDERSIDE OF THE
 ROOF FRAMING MEMBERS.
 THE ROUGH-FRAMED OPENING SHALL BE NOT LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. WHERE LOCATED IN A WALL, THE OPENING SHALL BE
 NOT LESS THAN 22 INCHES WIDE BY 30 INCHES HIGH (559 MM
 WIDE BY 762 MM HIGH). WHERE THE ACCESS IS LOCATED IN A
 CEILING, MINIMUM UNOBSTRUCTED HEADROOM IN THE ATTIC
 SPACE SHALL BE 30 INCHES (762 MM) AT SOME POINT ABOVE
 THE ACCESS MEASURED VERTICALLY FROM THE BOTTOM OF
 CEILING FRAMING MEMBERS. SEE SECTION M1305.1.3 FOR
 ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
  
 R402.2.4 ACCESS HATCHES AND DOORS.
 ACCESS DOORS FROM CONDITIONED SPACES TO UNCONDITIONED
 SPACES (E.G., ATTICS AND CRAWL SPACES) SHALL BE
 WEATHERSTRIPPED AND INSULATED TO A LEVEL EQUIVALENT TO
 THE INSULATION ON THE SURROUNDING SURFACES. ACCESS
 SHALL BE PROVIDED TO ALL EQUIPMENT THAT PREVENTS
 DAMAGING OR COMPRESSING THE INSULATION. A WOOD FRAMED
 OR EQUIVALENT BAFFLE OR RETAINER IS REQUIRED TO BE
 PROVIDED WHEN LOOSE FILL INSULATION IS INSTALLED, THE
 PURPOSE OF WHICH IS TO PREVENT THE LOOSE FILL
 INSULATION FROM SPILLING INTO THE LIVING SPACE WHEN THE
 ATTIC ACCESS IS OPENED, AND TO PROVIDE A PERMANENT
 MEANS OF MAINTAINING THE INSTALLED R-VALUE OF THE LOOSE
 FILL INSULATION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-05-02 Cont ID  
Sent By ppetty Date 2019-05-02 Time 14:49 Rev Time 0.00
Received By ppetty Date 2019-05-02 Time 14:49 Sent To  
Notes
2019-05-02 12:33:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: OK, SEE COMMENTS BELOW.
  
 1.SEE PROVISO ON PLAN
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER/CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-13 Cont ID  
Sent By cthroop Date 2019-03-13 Time 16:15 Rev Time 0.00
Received By cthroop Date 2019-03-13 Time 11:19 Sent To  
Notes
2019-03-13 17:21:56ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. NEC 250.64 / E3607.3.1 EQUIPMENT GROUNDING CONDUCTOR
 REQUIRED.
 FBC R E3607.3
 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) OR BRANCH
 CIRCUIT(S).
 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) OR BRANCH
 CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR
 GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH
 SECTION E3608. THE GROUNDING ELECTRODE CONDUCTOR(S)
 SHALL BE CONNECTED IN A MANNER SPECIFIED IN SECTION
 E3607.3.1 OR, FOR EXISTING PREMISES WIRING SYSTEMS
 ONLY, SECTION E3607.3.2. WHERE THERE IS NO EXISTING
 GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S)
 REQUIRED IN SECTION E3608 SHALL BE INSTALLED.
 [250.32(A)]
  
 2. NEC 225.31 & 240.21 (B) (2) / E3706.3 DISCONNECTING
 MEANS.
 . FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR THE SUB-PANELS IN THE
 GUEST HOUSE. NEC 225.31, 225.32.
 NOTE: SHOW DISCONNECTING DEVICE ON RISER DIAGRAHM.
  
 3. NEC TABLE 310.15 (B) (16) / TABLE E3705.1 -
 ALLOWABLE AMPACITY OF INSULATED CONDUCTORS.
 CONDUCTOR SIZE TO SUB PANEL NOT OF SUFFICIENT SIZE
 BASED ON THE AMPACITY OF THE MAIN DISCONNECT.
 NOTE: YOU MAY EITHER RE-SIZE THE CONDUCTORS BASED ON
 THE REFERENCED TABLES OF INSTALL A DISCONNECT AT MAIN
 DISCONNECT UPSTREAM OF CONDUCTORS.
  
 4. INCLUDE VP NEXT TO THE SYMBOL AT THE VAPOR PROOF
 FIXTURE IN THE SHOWER AREA.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2019-05-28 Cont ID  
Sent By cthroop Date 2019-05-28 Time 16:35 Rev Time 0.00
Received By cthroop Date 2019-05-28 Time 16:17 Sent To  
Notes
2019-05-28 16:36:41GAS PLAN REVIEW
  
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2019-04-29 Cont ID  
Sent By thunt Date 2019-04-29 Time 14:16 Rev Time 0.00
Received By thunt Date 2019-04-29 Time 14:16 Sent To  
Notes
2019-04-29 14:17:46A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT IS REQUIRED FOR A
 CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF GAS
 WORK TO BE DONE. WPB AMEND. TO FBC SEC.107.2.1.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-03-11 Cont ID  
Sent By thunt Date 2019-03-11 Time 08:13 Rev Time 0.00
Received By thunt Date 2019-03-11 Time 08:13 Sent To  
Notes
2019-03-11 08:19:58GAS 1ST REVIEW**DENIED**
  
 PLAN IS SHOWING A GAS TANKLESS WATER HEATER BUT NO GAS
 PLANS OR SUPPORTING DOCUMENTS SUPPLIED. I HAVE INCLUDED
 A GAS PLAN REVIEW CHECK LIST IN YOUR PACKET AND
 HIGHLIGHTED THE REQUIRED ITEM YOU WILL NEED FOR PLAN
 REVIEW, CITY RECORD SHOW EXISTING GAS ON THIS HOME. FBC
 107.3.5
  
  
 TIM HUNT
 PLUMBING INSPECTOR/ PLANS EXAMINER
 561-805-6711
 561-805-6724
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-05-21 Cont ID  
Sent By fmittner Date 2019-05-21 Time 12:56 Rev Time 0.00
Received By fmittner Date 2019-05-21 Time 12:56 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-03-05 Cont ID  
Sent By fmittner Date 2019-03-05 Time 16:36 Rev Time 0.00
Received By fmittner Date 2019-03-05 Time 16:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-28 Cont ID  
Sent By cthroop Date 2019-05-28 Time 16:36 Rev Time 0.00
Received By cthroop Date 2019-05-28 Time 16:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-22 Cont ID  
Sent By cthroop Date 2019-05-22 Time 17:15 Rev Time 0.00
Received By cthroop Date 2019-04-24 Time 14:11 Sent To  
Notes
2019-04-25 14:11:43R14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-13 Cont ID  
Sent By cthroop Date 2019-03-13 Time 17:23 Rev Time 0.00
Received By cthroop Date 2019-02-19 Time 15:45 Sent To  
Notes
2019-02-20 15:45:44R07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-05-28 Cont ID  
Sent By cthroop Date 2019-05-28 Time 16:33 Rev Time 0.00
Received By cthroop Date 2019-05-28 Time 16:33 Sent To  
Notes
2019-05-28 16:34:37MU-2019-016171-0000 CT

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-03-13 Cont ID  
Sent By cthroop Date 2019-03-13 Time 11:55 Rev Time 0.00
Received By cthroop Date 2019-03-13 Time 11:19 Sent To  
Notes
2019-03-13 11:56:28PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-05-28 Cont ID  
Sent By cthroop Date 2019-05-28 Time 16:34 Rev Time 0.00
Received By cthroop Date 2019-05-28 Time 16:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-05-22 Cont ID  
Sent By cthroop Date 2019-05-22 Time 17:12 Rev Time 0.00
Received By cthroop Date 2019-05-22 Time 14:17 Sent To  
Notes
2019-05-22 17:15:01MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DESIGN PROFESSIONALS SIGNATURE AND SEAL IS INVALID.
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-03-13 Cont ID  
Sent By cthroop Date 2019-03-13 Time 15:52 Rev Time 0.00
Received By cthroop Date 2019-03-13 Time 11:19 Sent To  
Notes
2019-03-13 15:57:53MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DESIGNERS SIGNATURE AND SEAL IS A COPY.
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 2. OWNER/AGENT TO SIGN ENERGY SUBMITTAL.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 3. TAMPER RESISTANT PORT CAPS REQUIRED.
 M1411.8 LOCKING ACCESS PORT CAPS.
 REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL
 BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS OR
 SHALL BE OTHERWISE SECURED TO PREVENT UNAUTHORIZED
 ACCESS.
 EXCEPTION: NO LOCKING-TYPE TAMPER-RESISTANT CAPS ARE
 REQUIRED IF PORTS ARE LOCATED INSIDE THE CONDENSING
 UNIT CABINET.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-05-28 Cont ID  
Sent By cthroop Date 2019-05-28 Time 16:35 Rev Time 0.00
Received By cthroop Date 2019-05-28 Time 16:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-04-29 Cont ID  
Sent By thunt Date 2019-04-29 Time 14:18 Rev Time 0.00
Received By thunt Date 2019-04-29 Time 14:18 Sent To  
Notes
2019-04-29 14:26:33PLUMBING 2ND REVIEW**DENIED**
  
  
 ***FL ST 553.80 (B)2B WITH RESPECT TO EVALUATION OF
 DESIGN PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT
 FINDS IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH
 THE FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW.
  
  
  
  
 1) 2ND REQUEST.THE P.E SIGNATURE APPREAR'S TO BE COPIED
 ON ALL PAGES AGAIN. SIGNATURE IS REQUIRED TO BE WET
 SIGNED PER F.A.C 61G15-23.003. THE P.E IS ADAM GINSBURG
 (A.G) BUT THE SIGNATURE SIGNED IS C.G. AND IS
 DEFINITELY PIXELATED AND EACH CORRESPONDING SHEET
 MATCHES EACH OTHER.
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-11 Cont ID  
Sent By thunt Date 2019-03-11 Time 08:20 Rev Time 0.00
Received By thunt Date 2019-03-11 Time 07:32 Sent To  
Notes
2019-03-11 08:23:42PLUMBING 1ST REVIEW**DENIED**
  
 1) P.E SIGNATURE APPREAR TO BE COPIED ON ALL PAGES.
 SIGNATURE IS REQUIRED TO BE WET SIGNED PER F.A.C
 61G15-23.003
  
 2) PROVIDE SPEC'S ON TANKLESS WATER HEATER. FBC 107.3.5
  
 TIM HUNT
 PLUMBING INSPECTOR/ PLANS EXAMINER
 561-805-6711
 561-805-6724
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2019-05-22 Cont ID  
Sent By pvalenti Date 2019-05-22 Time 14:11 Rev Time 0.00
Received By pvalenti Date 2019-05-22 Time 14:11 Sent To  
Notes
2019-05-22 14:13:47 
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED WITH PROVISO:
  
 PROVIDE ROOFING SUB- PERMIT PRIOR TO ROOFING WORK.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-03-13 Cont ID  
Sent By cthroop Date 2019-03-13 Time 15:33 Rev Time 0.00
Received By cthroop Date 2019-03-13 Time 11:19 Sent To  
Notes
2019-03-13 15:35:47BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR NEW ROOFING SYSTEM
 COMPONENTS. DESIGNER TO REVIEW AND APPROVE IN WRITING.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-05-21 Cont ID  
Sent By fmittner Date 2019-05-21 Time 12:57 Rev Time 0.00
Received By fmittner Date 2019-05-21 Time 12:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-03-05 Cont ID  
Sent By fmittner Date 2019-03-05 Time 16:36 Rev Time 0.00
Received By fmittner Date 2019-03-05 Time 16:36 Sent To  
Notes
***NONE***