Plan Review Details - Permit 19020771
Plan Review Stops For Permit 19020771
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-06-04 Cont ID  
Sent By jleahy Date 2019-06-04 Time 14:47 Rev Time 0.00
Received By cthroop Date 2019-06-04 Time 14:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-02 Cont ID  
Sent By cthroop Date 2019-05-02 Time 10:58 Rev Time 0.00
Received By cthroop Date 2019-05-02 Time 10:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-28 Cont ID  
Sent By cthroop Date 2019-03-28 Time 11:30 Rev Time 0.00
Received By cthroop Date 2019-03-27 Time 15:38 Sent To  
Notes
2019-03-28 13:18:12BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA) WITH A BASE FLOOD ELEVATION (BFE) OF 12.1 FEET
 NAVD88.
  
 1. R322.2.5.1 POOLS LOCATED IN DESIGNATED FLOODWAYS.
 WHERE POOLS ARE LOCATED IN DESIGNATED FLOODWAYS,
 DOCUMENTATION SHALL BE SUBMITTED TO THE BUILDING
 OFFICIAL, WHICH DEMONSTRATES THAT THE CONSTRUCTION OF
 THE POOL WILL NOT INCREASE THE DESIGN FLOOD ELEVATION
 AT ANY POINT WITHIN THE JURISDICTION.
  
 2. EQUIPMENT TO BE INSTALLED PER FBC R322.1.6. NOTE:
 APPLICANT MAY PETITION THE BUILDING OFFICIAL TO INSTALL
 EQUIPMENT AT FINISHED FLOOR ELEVATION.
  
 3. DIGITAL SIGNATURES AND SEALS CANNOT BE VERIFIED.
  
 4. POOL BARRIER SHALL COMPLY WITH FBC R4502.17.1. DOOR
 AND WINDOW ALARMS REQUIRED.
  
 5. STAIR RISERS SHALL BE A MINUMUM OF 12 INCHES PER
 ANSI/APSP/ICC-5 2011.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-06-04 Cont ID  
Sent By jleahy Date 2019-06-04 Time 07:57 Rev Time 0.00
Received By jleahy Date 2019-06-04 Time 07:44 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-30 Cont ID  
Sent By jleahy Date 2019-04-30 Time 15:11 Rev Time 0.00
Received By jleahy Date 2019-04-30 Time 15:11 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-11 Cont ID  
Sent By jleahy Date 2019-03-11 Time 16:53 Rev Time 0.00
Received By jleahy Date 2019-03-11 Time 16:53 Sent To  
Notes
2019-03-11 16:54:42FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO PANEL SIZE SHOWN FOR POOL EQUIPMENT, SHOW PANEL SIZE
 AND WIRE SIZES. 215.5

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-06-04 Cont ID  
Sent By cthroop Date 2019-06-04 Time 14:47 Rev Time 0.00
Received By cthroop Date 2019-05-15 Time 14:34 Sent To  
Notes
2019-05-16 14:34:50RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-02 Cont ID  
Sent By cthroop Date 2019-05-02 Time 10:58 Rev Time 0.00
Received By cthroop Date 2019-04-19 Time 13:08 Sent To  
Notes
2019-04-22 13:08:49RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-28 Cont ID  
Sent By cthroop Date 2019-03-28 Time 13:18 Rev Time 0.00
Received By cthroop Date 2019-02-22 Time 11:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-06-04 Cont ID  
Sent By cthroop Date 2019-06-04 Time 14:47 Rev Time 0.00
Received By cthroop Date 2019-06-04 Time 14:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-04-30 Cont ID  
Sent By thunt Date 2019-04-30 Time 16:45 Rev Time 0.00
Received By thunt Date 2019-04-30 Time 16:45 Sent To B
Notes
2019-04-30 16:45:19PLUMBING 2ND REVIEW COMPLETED**DENIED**
  
 1) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE AND THE SIMPLIFIED TOTAL DYNAMIC HEAD
 CALCULATION IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC
 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION
 ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT
 REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED
 THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET
 FITTING ASSEMBLY (DRAIN COVER).THE TDH CALCULATIONS
 MUST INCLUDE ALL OF THE SYSTEM COMPONENTS INCLUDING
 SUCTION AND RETURN PIPING, FITTINGS, VALVES, HEATER,
 FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS EXCEPT
 THE PUMP.
  
 2) SUBMIT TWO LEGIBLE COPIES OF THE POOL PUMP CURVE.
 IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC
 TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS
 NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH
 CALCULATIONS. ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9,
 4.4.9.1
  
 3) NOTE ON PLAN REFERS TO HEATER MIN EFF MIN AS 78%.
 GAS FIRED POOL HEATERS SHALL HAVE A MINIMUM THERMAL
 EFFICIENCY OF 82% PER THE 2017 FBC-ENERGY SEC.
 R403.10.4. THE SUBMITTED SPECS DO NOT SHOW THIS.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-21 Cont ID  
Sent By thunt Date 2019-03-21 Time 06:02 Rev Time 0.00
Received By thunt Date 2019-03-20 Time 16:45 Sent To  
Notes
2019-03-20 16:49:26PLUMBING 1ST REVIEW**DENIED**
  
 PLANS SUBMITTED ELECTRONICALLY SHALL BE SIGNED
 ELECTRONICALLY OR DIGITALLY. F.S 471/481 RULE
 61G15-23.003
  
  
  
 TIM HUNT
 PLUMBING INSPECTOR/PLUMBING PLAN EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2019-05-02 Cont ID  
Sent By cthroop Date 2019-05-02 Time 10:48 Rev Time 0.00
Received By cthroop Date 2019-05-02 Time 10:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-03-28 Cont ID  
Sent By cthroop Date 2019-03-28 Time 13:18 Rev Time 0.00
Received By cthroop Date 2019-03-27 Time 15:38 Sent To  
Notes
2019-03-28 13:20:56BUILDING PLAN REVIEW - DIGITAL SIGNATURE AND SEAL
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SIGNATURE AND SEAL OF DESIGN PROFESSIONAL CANNOT BE
 VERIFIED.
  
 DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH FS
 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE NEXT
 REVIEW CYCLE REQUIRE REVIEW.
  
 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-05-21 Cont ID  
Sent By mcruz Date 2019-05-21 Time 10:51 Rev Time 0.00
Received By mcruz Date 2019-05-21 Time 10:49 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-04-26 Cont ID  
Sent By mcruz Date 2019-04-26 Time 11:58 Rev Time 0.00
Received By mcruz Date 2019-04-26 Time 11:40 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-03-06 Cont ID  
Sent By mcruz Date 2019-03-06 Time 11:36 Rev Time 0.00
Received By mcruz Date 2019-03-06 Time 11:10 Sent To PC
Notes
2019-03-06 11:36:53ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) PURSUANT TO SEC. 94-304(D) - SWIMMING POOLS SHALL BE
 LOCATED 10' FROM THE PROPERTY LINE ON A CORNER LOT. THE
 PLAN SHOWS 7' SETBACK.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME. IF YOU WANT TO MEET IN PERSON TO GO OVER
 THE ABOVE COMMENTS, PLEASE CALL OR E-MAIL ME TO
 SCHEDULE AN APPOINTMENT.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]