Plan Review Details - Permit 19020686
Plan Review Stops For Permit 19020686
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-09-09 Cont ID  
Sent By cthroop Date 2019-09-09 Time 16:55 Rev Time 0.00
Received By cthroop Date 2019-09-09 Time 16:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-16 Cont ID  
Sent By cthroop Date 2019-08-16 Time 08:01 Rev Time 0.00
Received By cthroop Date 2019-08-15 Time 15:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-13 Cont ID  
Sent By jgomez Date 2019-03-13 Time 13:27 Rev Time 0.00
Received By jgomez Date 2019-03-13 Time 09:55 Sent To  
Notes
2019-03-12 12:39:50NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1-PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 2- PROVIDE SOIL TEST REPORT (2 COPIES) AS REQUIRED BY
 SEC. R401.4 FBC-RESIDENTIAL.
  
 3- SHEET A-2:
 A) REVISE WIND DESIGN BASIS INFORMATION. ACCORDING TO
 SEC. R301.2.1.4 FBC-RESIDENTIAL, THIS BUILDINGS ARE
 LOCATED IN EXPOSURE "D" NO EXPOSURE "B". REVISE AS
 REQUIRED AND REVISE THE WALL PRESSURES SHOWN ON SHEETS
 A-2 AND A-3 ALSO.
 NOTE: THIS APPLIES TO DRAWINGS FOR THE DETACHED GARAGE
 ALSO.
  
 B) REVISE THE WALL ELEVATION DIMENSION "A" SHOWN ON THE
 WIND DESIGN BASIS. ACCORDING TO FIGURE R301.2(7)
 FBC-RESIDENTIAL THE END ZONE "A" IS 4 FEET NO 3 FEET.
 REVISE AS REQUIRED.
  
 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 "SPECIAL FRAMING" AT THE COVERED PATIO SLIDING GLASS
 DOORS . SPECIFY ALL FRAMING MEMBERS AND ALL CONNECTORS.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 5- REVISE ATTIC ACCESS SECTION #2 ON SHEET A-1. NEED
 22" MIN. FOR FRAMED OPENING NOT 21". SEE SEC. R807.1
 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 6- REAR PATIO SECTION #4 ON SHEET A-4:
 A) PROVIDE SPECIFICATIONS FOR CONCRETE DECK FINISH
 (SEC. R903.1 FBC-RESIDENTIAL.
  
 B) PROVIDE DETAILS AND SPECIFICATION FOR CEILING
 CONSTRUCTION. SEC. R301.1 FBC-RESIDENTIAL.
  
 7-SPECIFY PITCH OF CONCRETE DECK ABOVE COVERED PATIO.
 TYPICALLY, LOW SLOPE ROOF REQUIRE AT LEAST 1/4" PER
 FOOT SLOPE. SEC. R905.11 FBC-RESIDENTIAL. NOTE:
 COORDINATE WITH ROOF COVERING SPECIFIED ON PLANS. NOTE:
 BUILDING SECTION A ON SHEET A-4 SPECIFIES 1" SLOPE
 MINIMUM. THIS SLOPE DOESN'T COMPLY. REVISE AS REQUIRED.
  
 8- WALL SECTIONS ON SHEET A-4: SPECIFY THE MINIMUM 12"
 FOOTING DEPTH AS REQUIRED BY SEC. R403.1.4
 FBC-RESIDENTIAL.
  
 9- PROVIDE SPECIFICATIONS FOR INSULATION BETWEEN GARAGE
 AND THE A/C AREA. SEC. R103.2 FBC-ENERGY CONSERVATION.
 NOTE: THIS APPLIES TO DETACHED GARAGE ALSO.
  
 10- DETACHED GARAGE: PROVIDE SPECIFICATIONS FOR FIRE
 RATED DOOR BETWEEN THE GARAGE AND THE OFFICE/WORK SHOP
 AREA. SEC. R302.5.1 FBC-RESIDENTIAL.
  
 11- ENERGY CALCULATIONS (MAIN HOUSE):
 A)THE ENERGY FORM R405-2017 IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM BY THE OWNER OR OWNER?S LEGALLY
 DESIGNATED AGENT PRIOR TO RECEIVE THE PERMIT AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 6TH EDITION (2017).
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER NAME, BUILDER NAME, PERMIT OFFICE AND
 JURISDICTION NUMBER (THIS JURISDICTION IS 604700) .
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) PROVIDE WINDOWS AND DOORS MANUFACTURER'S
 SPECIFICATIONS SHOWING THE U-FACTOR AND SHGC FACTOR
 SPECIFIED ON THE ENERGY CALCULATIONS ON ITEM #7 ON PAGE
 1 OF 5 AS REQUIRED BY SEC. R405.4.3 FBC-ENERGY
 CONSERVATION. NOTE: COORDINATE WITH PLANS AND PRODUCT
 APPROVALS SUBMITTED TO AVOID CONFLICTS/DELAYS.
  
 D)REVISE ITEM #9(B) AND #9(C). THE MATERIAL OF ADJACENT
 WALL FRAME IS NOT WOOD. SEE PLANS AND REVISE AS
 REQUIRED. COORDINATE R-VALUE WITH PLANS. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)TYPICALLY THE THE ATTIC VENT RATIO IS 1/150. PAGE 2
 OF 5 SPECIFIES 1/300. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH THE EXCEPTION OF
 SEC. R806.2 FBC-RESIDENTIAL WHEN SPECIFYING A VENT
 RATIO OF 1/300 AS SHOWN ON PAGE 2 OF 5. NOTE:
 COORDINATE WITH PLANS TO AVOID CONFLICTS/DELAYS.F)
  
 F) REVISE THE DOORS INFORMATION SHOWN ON PAGE 3 OF 5 TO
 MATCH PLANS. WHY COUNTING THE GARAGE OVERHEAD DOORS?.
 ONLY THE DOORS SEPARATING A/C FROM THE NON-A/C AREAS
 ARE CONSIDERED. THE GARAGE IS NO PART OF THE A/C AREA
 OF THIS HOUSE. SEE A/C AREA ON FRONT PAGE. REVISE AS
 REQUIRED. DELETE THE GARAGE DOORS.
  
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G) REVISE THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 5
 TO MATCH PLANS. REVISE ORIENTATION, WINDOW AREA AND
 OVERHANG DEPTH AND SEPARATION TO MATCH PLANS. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR.
  
 12)ENERGY CALCULATIONS (DETACHED GARAGE):
 A) ITEM #4 IS INCORRECT. ACCORDING TO PLANS THERE IS
 NOT BEDROOM. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 B) ITEM #6 IS INCORRECT. ACCORDING TO PLANS THE A/C
 AREA IS 411 S.F. NOT 561 S.F. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) MISSING INFORMATION ABOUT THE ADJACENT WALL.
 COORDINATE WITH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 D) SPACES INFORMATION ON PAGE 2 OF 4 SPECIFIES THAT
 THERE IS A KITCHEN. ACCORDING TO PLANS THERE IS NOT
 KITCHEN. REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 E) REVISE WINDOWS INFORMATION ON PAGE 3 OF 4 TO MATCH
 PLANS. REVISE WINDOW ORIENTATION. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 F) REVISE ALL OTHER COMMENTS LISTED FOR THE MAIN HOUSE
 ABOVE AND THAT APPLY TO THIS BUILDING. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 13-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A)ENTRY DOORS
 B)EXTERIOR SWING DOORS.
 C)SINGLE HUNG WINDOWS.
 D)WINDOW MULLIONS AS SHOWN ON PLANS. REQUIRED: CLEARLY
 SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE
 WITH THE CALCULATED DESIGN PRESSURES.
 E)OVERHEAD GARAGE DOORS.
 F)POCKET SLIDING GLASS DOORS AS SHOWN ON PLANS.
 G)PRECAST LINTELS AS SPECIFIED ON PLANS.
 H) METAL ROOF AS SPECIFIED ON PLANS.
  
 14-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 15- HANDRAILS AND GUARDRAILS
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INTERIOR HANDRAILS AND GUARDRAIL AND FOR BALCONY
 GUARDRAIL SHOWING COMPLIANCE WITH TABLE R301.5, SEC.
 R311.7.8 AND SEC. R312.1 FBC-RESIDENTIAL.
 NOTE: IF THIS IS A DEFERRED SUBMITTAL, THEN SPECIFY THE
 DESIGN GUIDELINES REQUIRED BY TABLE R301.5, SEC.
 R311.7.8 AND SEC. R312.1 AND CLEARLY SPECIFY ON PLANS
 THAT SHOP DRAWINGS NEED TO BE SUBMITTED FOR REVIEW
 PRIOR TO CONSTRUCTION. ALL SHOP DRAWINGS TO BE REVIEWED
 BY THE DESIGN PROFESSIONAL OF RECORD PRIOR TO SUBMITTAL
 TO THIS OFFICE.
  
 16- PROVIDE COMPLETE DETAILS ANS SPECIFICATIONS FOR THE
 CONSTRUCTION AND INSTALLATION OF THE DECORATIVE
 ALUMINUM SHUTTERS SHOWN ON THE FRONT ELEVATION OF THE
 MAIN HOUSE. SEC. R301.1 FBC-RESIDENTIAL.
  
 17- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $495,627 TOTAL FOR
 MAIN HOUSE AND DETACHED GARAGE. THE PERMIT FEE BALANCE
 IS $9,167.71.
  
  
 18-PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR
 REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW
 COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-08-29 Cont ID  
Sent By ppetty Date 2019-08-29 Time 12:57 Rev Time 0.00
Received By ppetty Date 2019-08-29 Time 12:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-07-30 Cont ID  
Sent By jpearson Date 2019-07-30 Time 13:28 Rev Time 0.00
Received By jpearson Date 2019-07-30 Time 06:41 Sent To  
Notes
2019-07-30 13:28:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS PER THE FORMAT IN FBC RES. THIS SHOULD INCLUDE
 THE AMOUNT DETERMINED FOR GARAGE UNDER SEPARATE PERMIT.
 ALSO, IT APPEARS THE AC LOAD WAS NOT INCLUDED IN TOTAL.
 NEC 220; FBC RE E3602.2 (NOT CORRECTED. LOOK AT THE
 MATH OF THE CALCULATION. A TOTAL OF 20432 WATTS IS
 SHOWN. HOWEVER, WHEN YOU ADD THE TOTAL OF 16,500 FOR
 AC/AHU, 10,000 FOR THE FIRST 10K, AND 10432 FOR THE
 REMAINDER AT 40%, THIS EQUALS MORE THAN 20,432. PROVIDE
 CORRECTION AS REQUESTED.)
 2. PLAN SHOWS THE GARAGE FEED COMING DIRECTLY FROM
 METER CAN AS UNFUSED CONDUCTORS. THIS INSTALLATION
 WOULD MEAN THE MAINS FOR THIS ADDRESS ARE IN 2
 DIFFERENT LOCATIONS, WHICH IS A CODE VIOLATION. MAINS
 MUST BE GROUPED. PROVIDE CORRECTION. NEC 230.72: FBC RE
 E3601.7 (MAINS ARE STILL SHOWN IN TWO DIFFERENT
 LOCATIONS. THE RISER DIAGRAM DOES NOT MATCH WHAT IS
 SHOWN ON PLAN. PROVIDE CORRECTIONS.)
 3. RISER DIAGRAM SHOWS A FEED FROM THE METER TO THE
 INTERIOR PANEL WHICH IS LOCATED IN THE GARAGE.
 CONDUCTORS THAT ARE NOT PROTECTED BY A MAIN BREAKER OR
 DISCONNECT ARE NOT PERMITTED TO RUN THROUGH THE HOUSE
 IN THIS FASHION. PROVIDE EITHER A MAIN ON THE OUTSIDE
 OF THE HOME, OR INSTALL THE CONDUCTORS UNDER THE SLAB.
 PROVIDE CORRECTIONS. NEC 230.70, 250.6; FBC RE E3601.6
 (NOT CORRECTED. SEE COMMENT 2.)
 4. WIRE SIZE SHOWN FROM METER CAN TO PANELS IS NOT
 SIZED PROPERLY. WIRE SIZES FROM NEC 310.15(B)(7), OR
 FBC RE E3603.1, CAN ONLY BE USED WHEN THE SERVICE
 CONDUCTOR SUPPLIES 100% OF THE LOAD. SINCE THIS IS NOT
 THE CASE, PROVIDE CORRECTED WIRE SIZE FROM METER CAN TO
 PANELS. NEC 310.15(B)(7) AND (B)(16); FBC RE E3603.1,
 E3705.1 (WIRE TO MAIN PANEL SHOWS THREE 3/0 AND ONE 1/0
 CONDUCTOR, BUT THIS IS NOT A THREE PHASE SYSTEM. THERE
 SHOULD NOT BE A EQUIPMENT GROUND FROM THE METER TO THE
 FIRST MEANS OF DISCONNECT.)
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-07 Cont ID  
Sent By jpearson Date 2019-03-07 Time 11:24 Rev Time 0.00
Received By jpearson Date 2019-03-06 Time 06:45 Sent To  
Notes
2019-03-06 14:37:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS PER THE FORMAT IN FBC RES. THIS SHOULD INCLUDE
 THE AMOUNT DETERMINED FOR GARAGE UNDER SEPARATE PERMIT.
 ALSO, IT APPEARS THE AC LOAD WAS NOT INCLUDED IN TOTAL.
 NEC 220; FBC RE E3602.2
 2. PLAN SHOWS THE GARAGE FEED COMING DIRECTLY FROM
 METER CAN AS UNFUSED CONDUCTORS. THIS INSTALLATION
 WOULD MEAN THE MAINS FOR THIS ADDRESS ARE IN 2
 DIFFERENT LOCATIONS, WHICH IS A CODE VIOLATION. MAINS
 MUST BE GROUPED. PROVIDE CORRECTION. NEC 230.72: FBC RE
 E3601.7
 3. RISER DIAGRAM SHOWS A FEED FROM THE METER TO THE
 INTERIOR PANEL WHICH IS LOCATED IN THE GARAGE.
 CONDUCTORS THAT ARE NOT PROTECTED BY A MAIN BREAKER OR
 DISCONNECT ARE NOT PERMITTED TO RUN THROUGH THE HOUSE
 IN THIS FASHION. PROVIDE EITHER A MAIN ON THE OUTSIDE
 OF THE HOME, OR INSTALL THE CONDUCTORS UNDER THE SLAB.
 PROVIDE CORRECTIONS. NEC 230.70, 250.6; FBC RE E3601.6
 4. WIRE SIZE SHOWN FROM METER CAN TO PANELS IS NOT
 SIZED PROPERLY. WIRE SIZES FROM NEC 310.15(B)(7), OR
 FBC RE E3603.1, CAN ONLY BE USED WHEN THE SERVICE
 CONDUCTOR SUPPLIES 100% OF THE LOAD. SINCE THIS IS NOT
 THE CASE, PROVIDE CORRECTED WIRE SIZE FROM METER CAN TO
 PANELS. NEC 310.15(B)(7) AND (B)(16); FBC RE E3603.1,
 E3705.1
 5. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 7. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9; FBC RE E3606.3
 8. LIGHTING IN CLOSETS IS SHOWN AS STANDARD RECESS
 LIGHTS. PER CODE, LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE
 CORRECTION. NEC 410.16; FBC RE E4003.12
 9. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC
 410.10(D); FBC RE E4003.11
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2019-07-30 Cont ID  
Sent By jesmith Date 2019-07-30 Time 16:29 Rev Time 0.00
Received By jesmith Date 2019-08-01 Time 07:44 Sent To  
Notes
2019-07-30 16:28:58A SEPARATE GAS PERMIT AND PLANS ARE REQUIRED

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-09-09 Cont ID  
Sent By cthroop Date 2019-09-09 Time 16:55 Rev Time 0.00
Received By cthroop Date 2019-08-23 Time 10:52 Sent To  
Notes
2019-08-26 10:52:21R29

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-16 Cont ID  
Sent By cpuell Date 2019-08-16 Time 13:11 Rev Time 0.00
Received By cpuell Date 2019-07-09 Time 16:16 Sent To  
Notes
2019-07-10 16:16:30R29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-15 Cont ID  
Sent By hmoser Date 2019-03-15 Time 09:49 Rev Time 0.00
Received By hmoser Date 2019-02-14 Time 11:30 Sent To  
Notes
2019-02-15 11:30:54R28

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-09-11 Cont ID  
Sent By cthroop Date 2019-09-11 Time 15:43 Rev Time 0.00
Received By cthroop Date 2019-09-11 Time 15:43 Sent To  
Notes
2019-09-11 15:44:08MU-2019-019380-0000. CT

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-03-13 Cont ID  
Sent By jgomez Date 2019-03-13 Time 13:44 Rev Time 0.00
Received By jgomez Date 2019-03-13 Time 13:44 Sent To  
Notes
2019-03-13 13:45:02IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-09-06 Cont ID  
Sent By hmoser Date 2019-09-06 Time 07:49 Rev Time 0.00
Received By hmoser Date 2019-09-05 Time 15:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-08-09 Cont ID  
Sent By hmoser Date 2019-08-09 Time 09:37 Rev Time 0.00
Received By hmoser Date 2019-08-08 Time 14:16 Sent To  
Notes
2019-08-09 09:37:55PLAN DENIED
 1) REFER TO SECTION 107.2.1 CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY. FBC.
 2) DESIGNER OF THE AIR CONDITIONING SYSTEM IS
 EDWARD DEJESUS. THE PLAN CAN'T BE ON
 ARCHITECT PAPER.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 56+1-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-03-15 Cont ID  
Sent By hmoser Date 2019-03-15 Time 09:48 Rev Time 0.00
Received By hmoser Date 2019-03-15 Time 08:49 Sent To I
Notes
2019-03-15 09:48:39PLAN DENIED
 1) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.
 2) SEER ON ENERGY CALCULATIONS DO NOT MATCH PLAN.
 3) PROVIDE MANUFACTURE SPECKS ON RANGE HOOD IN REGARDS
 TO SECTION
 M1503.4 MAKE UP AIR REQUIRED 2017 RESIDENTIAL CODE
 4) REFER TO SECTION R103.1.1.2 FLORIDA ENERGY CODE 2017
 OWNER/AGENT MUST SIGN ENERGY CALCULATIONS.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-07-30 Cont ID  
Sent By jesmith Date 2019-07-30 Time 16:27 Rev Time 0.00
Received By jesmith Date 2019-08-01 Time 07:43 Sent To  
Notes
2019-07-30 16:27:27PLUMBING COMMENTS: APPROVED WITH PROVISO
 1.NEW GARAGE PLAN SHEET GS-1: PLUMBING RISER DIAGRAM IS
 CODE COMPLIANT.
 2. NEW HOUSE PLAN SHEET P-1 COMMENTS NOTED ARE REDLINED
 ON THE PLAN AND NO ACTION IS EREQUIRED.
 A.SANITARY RISER DIAGRAM
 B.CLOTHES WASHER AND SINK SHALL CONNECT TO BUILDING
 DRAIN DOWNSTREAM OF THE BATHROOM FIXTURES TO COMPLY
 WITH FBC RES P3108.1
 C.CONNECT FIXTURE DRAIN OF SINK TO VERTICAL WASTE PIPE
 AT A POINT ABOVE THAT OF THE CLOTHES WASHER AND COMPLY
 WITH FBC RES 3107.3.
 E.ELIMINATE LOOP VENT AT HIS BATH AND COMPLY W/ FBC RES
 P3108.1.
 F.IN HER BATH, CONNECT TUB WASTE AND SHOWER WASTE
 INDEPENDENTLY TO WET VENT AND SIZE WET VENT BETWEEN
 SHOWER AND WATER CLOSET DRAIN 3? TO COMPLY WITH FBC RES
 P3108.1.
 G.RECONCILE FLOOR PLAN PIPING LAYOUT WITH SANITARY
 RISER.
  
 A SEPARATE GAS PERMIT AND PLANS ARE REQUIRED
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-03-09 Cont ID  
Sent By gjohnson Date 2019-03-09 Time 09:20 Rev Time 0.00
Received By gjohnson Date 2019-03-09 Time 08:16 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2019-08-16 Cont ID  
Sent By cthroop Date 2019-08-16 Time 08:01 Rev Time 0.00
Received By cthroop Date 2019-08-15 Time 15:44 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-03-13 Cont ID  
Sent By jgomez Date 2019-03-13 Time 13:42 Rev Time 0.00
Received By jgomez Date 2019-03-13 Time 13:42 Sent To  
Notes
2019-03-13 13:44:121-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) METAL ROOF AS SPECIFIED ON PLANS.

Review Stop Z ZONING
Rev No 4 Status N Date 2019-09-05 Cont ID  
Sent By awooten Date 2019-09-05 Time   Rev Time 0.00
Received By awooten Date 2019-09-05 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2019-08-16 Cont ID  
Sent By awooten Date 2019-08-16 Time   Rev Time 0.00
Received By awooten Date 2019-08-16 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-04-03 Cont ID  
Sent By awooten Date 2019-04-02 Time   Rev Time 0.00
Received By awooten Date 2019-04-02 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By awotten Date 2019-02-27 Time   Rev Time  
Received By   Date 2019-02-27 Time   Sent To  
Notes
2019-02-27 10:31:22*******************************ZONING REVIEW
 FAILED*****************************
  
 PROVIDE LANDSCAPING.
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]