Plan Review Details - Permit 19020657
Plan Review Stops For Permit 19020657
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-08-07 Cont ID  
Sent By jwitmer Date 2019-08-07 Time 15:57 Rev Time 0.00
Received By jwitmer Date 2019-08-07 Time 15:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-06-14 Cont ID  
Sent By jgomez Date 2019-06-14 Time 14:10 Rev Time 0.00
Received By jgomez Date 2019-06-14 Time 11:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-11 Cont ID  
Sent By jwitmer Date 2019-03-11 Time 14:08 Rev Time 0.00
Received By jwitmer Date 2019-03-11 Time 10:45 Sent To  
Notes
2019-03-11 14:08:352017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020657
 ADD: 525 OKEECHOBEE BLVD. 14TH FLOOR / ADDITIONAL EXAM
 ROOMS & PHARMACY
 CONT: TBD/ TO BE DETERMINED
 TEL: ?????????????
 E-MAIL: [email protected] CONTACT: JIM
 PITZER
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MARCH 11/ 2017
 ACTION: DENIED
  
 1) THE 16 SHEETS SUBMITTED UNDER THE REGISTERED
 ARCHITECT ROBERT L. BOSTWICK ARE NOT ELECTRONICALLY
 SIGNED NOR SEALED.
 FLORIDA ADMINISTRATIVE CODE 61G1-16.005. PROCEDURES FOR
 DIGITALLY SIGNING AND SEALING AND FOR ELECTRONICALLY
 TRANSMITTING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
  
 2A) SHEET 002_FL110- LIFE SAFETY PLAN LIST THE CODE
 REFERENCES BUT THE CODE SUMMARY STATES THIS IS A
 RENOVATION, BUT DOES NOT REFERENCE THE 2017 FLORIDA
 BUILDING CODE EXISTING BUILDING CODE. THE FAMILY OF THE
 2017 FBC WAS ADOPTED ON DEC. 31/ 2017.
  
 2B) THE PLANS ARE SILENT AS TO WHICH METHODOLOGY UNDER
 THE 2017 EXISTING BUILDING CODE THE PLANS WERE
 DEVELOPED?
 301.1. THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY,
 ADDITION OR RELOCATION OF ALL EXISTING BUILDINGS SHALL
 COMPLY WITH ONE OF THE METHODS LISTED IN SECTIONS
 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE APPLICANT.
 SECTIONS 301.1.1 THROUGH 301.1.3 SHALL NOT BE APPLIED
 IN COMBINATION WITH EACH OTHER.
 301.1.1 PRESCRIPTIVE COMPLIANCE METHOD.
 301.1.2 WORK AREA COMPLIANCE METHOD.
 301.1.3 PERFORMANCE COMPLIANCE METHOD.
  
 3) SHEET 011_A101 DETAIL 18 SHOWS WHAT APPEARS TO BE
 (3) MICROWAVES ABOVE THE REACH RANGES AND OPERATING
 PARTS OF THE 2017 FBC-ACCESSIBILITY CODE. SHEET
 014_A800 DETAIL 12 DOES INDICATE AN ADJUSTABLE SHELF TO
 HOLD MICROWAVES. PLEASE NOTE AT LEAST ONE OF THE
 MICROWAVES MUST COMPLY WITH THE 2017 FBC-ACCESSIBILITY
 CODE SECTIONS:
 308 REACH RANGES
 308.2 FORWARD REACH./ 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 309 OPERABLE PARTS
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N)
 MAXIMUM.
 4) SHEET 012_A-102 FOR THE HAZARDOUS IV PREP, ANTI-ROOM
 AND NON-HAZARDOUS IV PREP ALL NEW WALLS ARE SHOWN WITH
 A WALL TAG 1E. SHEET 009-A003 THE PARTITION TYPES
 PROVIDES A CUT SECTION THROUGH PARTITION TYPE 1E THERE
 IS NO VERTICAL SECTION FOR THIS WALL SHOWING IF THIS IS
 A FIRE RATED WALL, SMOKE BARRIER, ETC. THERE ARE OTHER
 PERMITS FOR ON THIS FLOOR SHOWING THERE IS CANCER
 TREATMENT ON THIS FLOOR. THE INFUSION SUITE LEEDS US TO
 BELIEVE THIS AREA MAY BE USED FOR RENAL DIALYSIS CENTER
 AND WOULD BE COVERED UNDER THE FGI GUIDELINES BUT THE
 COVERSHEET DOES NOT INCLUDE THE SCOPE OF TREATMENT FOR
 THIS AREA. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
 THE FGI GUIDELINES SECTION 2.2-3.10 IS FOR CANCER
 TREATMENT/ INFUSION THERAPY SERVICE BUT THIS SECTION
 DOES NOT ADDRESS HAZARDOUS IV PREP ROOMS????AND THE
 RATING OF SUCH ROOM.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-06-04 Cont ID  
Sent By jpearson Date 2019-06-04 Time 11:23 Rev Time 0.00
Received By jpearson Date 2019-06-04 Time 08:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-03-05 Cont ID  
Sent By jleahy Date 2019-03-05 Time 11:41 Rev Time 0.00
Received By jleahy Date 2019-03-05 Time 11:17 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 2 Status P Date 2019-06-04 Cont ID  
Sent By jpearson Date 2019-06-04 Time 11:04 Rev Time 0.00
Received By jpearson Date 2019-06-04 Time 11:03 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2019-03-05 Cont ID  
Sent By jleahy Date 2019-03-05 Time 11:42 Rev Time 0.00
Received By jleahy Date 2019-03-05 Time 11:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-05-31 Cont ID  
Sent By pleduc Date 2019-05-31 Time   Rev Time 0.00
Received By pleduc Date 2019-05-31 Time 10:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-02-25 Cont ID  
Sent By scaldero Date 2019-02-25 Time 11:14 Rev Time 0.00
Received By scaldero Date 2019-02-19 Time 13:05 Sent To  
Notes
2019-02-25 09:05:27PERMIT # 19020657
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) COVER SHEET: UPDATE THE CODE LIST TO REFERENCE THE
 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2015 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 2) PERMIT WAS ENTERED AS SUITE #100, HOWEVER PLANS
 INDICATE THAT THE WORK IS ON THE 14TH FLOOR. PLEASE
 REVIEW AND CORRECT WHERE NEEDED.
  
 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-09 Cont ID  
Sent By pvalenti Date 2019-08-09 Time 06:36 Rev Time 0.00
Received By pvalenti Date 2019-08-01 Time 15:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-14 Cont ID  
Sent By shill Date 2019-06-14 Time 14:48 Rev Time 0.00
Received By shill Date 2019-05-30 Time 12:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-18 Cont ID  
Sent By lmarchan Date 2019-03-18 Time 16:25 Rev Time 0.00
Received By lmarchan Date 2019-02-14 Time 16:19 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-03-11 Cont ID  
Sent By jwitmer Date 2019-03-11 Time 14:07 Rev Time 0.00
Received By jwitmer Date 2019-03-11 Time 10:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-08-09 Cont ID  
Sent By pvalenti Date 2019-08-09 Time 06:33 Rev Time 0.00
Received By ccole Date 2019-08-09 Time 06:33 Sent To  
Notes
2019-08-09 06:35:212ND MECHANICAL REVIEW
  
 APPROVED CHRIS COLE (REMOTELY)

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-06-10 Cont ID  
Sent By ccole Date 2019-06-10 Time 16:37 Rev Time 0.00
Received By ccole Date 2019-06-10 Time 12:52 Sent To  
Notes
2019-06-10 17:01:412ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19020657
 6/1019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE LOCATION INFORMATION ON THE HAZARDOUS
 MATERIALS REPORT- NAME AND ADDRESS OF THE FACILITY,
 FLOOR AND ROOM NUMBERS ETC. THE REPORT SHALL BEAR THE
 SIGNATURE AND TITLE OF THE PERSON WHO PREPARED THE
 REPORT, AND IF THE PERSON IS A FL. LICENSED DESIGN
 PROFESSIONAL, THEN THE REPORT SHALL ALSO BEAR HIS/HER
 OFFICIAL RAISED OR INK SEAL. THE ENGINEER OF RECORD FOR
 THE ENTIRE PROJECT SHALL REVIEW THE REPORT AND PROVIDE
 AN APPROVAL STAMP ON THE DOCUMENT- SECTION 107.1 WPB.
  
 2) M.102: CORRECT NOTE #7 WHICH IS INDICATING A LOW AIR
 EXHAUST GRILL INSTEAD OF A RETURN GRILL.
  
 3) M-501: THE FLORIDA BUILDING CODES DO NOT REFERENCE
 THE ISO FOR VENTILATION AND PRESSURE DESIGN PARAMETERS
 FOR PHARMACIES AND HAZARDOUS MATERIALS STIRAGE AND
 PROCESSING. THE CALCULATIONS MUST BE PERFORMED IN
 ACCORDANCE WITH THEASHRAE 170 AND/OR THE USP 797-800
 GUIDELINES WHICH ARE REFERENCED IN ASHRAE 170. PLEASE
 CORRECT THE TABLE ACCORDINGLY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-03-12 Cont ID  
Sent By ccole Date 2019-03-12 Time 17:00 Rev Time 0.00
Received By ccole Date 2019-03-12 Time 17:00 Sent To  
Notes
2019-03-12 17:34:211ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19020657
 3/12/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M101 & M102: REFER TO TABLE 7-1 ASHRAE 170-2008 AND
 PROVIDE A DESIGN PARAMETERS (PRESSURE RELATIONSHIPS
 ETC.) SCHEDULE FOR THE ROOMS AND SPACES IN THE WORK
 AREAS. I AM NOT SEEING A "PHARMACY" ON THE PLANS. IS
 THIS A GENERAL TERM FOR THE WORK AREA OR DOES IT REFER
 TO A SPECIFIC ROOM OR SPACE? - SECTION 107.2.1 WPB.
  
 2) SHEETS A102 & M102: THE LOCATIONS OF THE HAZARDOUS
 IV PREP AND NON-HAZARDOUS PREP IV ON THE MECHANICAL
 PLAN DO NOT MATCH THE LOCATIONS ON THE ARCHITECTURAL
 PLAN- SECTION 107.2.1 WPB.
  
 3) M102, NOTE #3: THE HAZARDOUS EXHAUST DUCT FROM THE
 LAB HOOD SHALL BE INDEPENDENT OF THE OTHER EXHAUST
 SYSTEMS- SECTION 510.4 FBC M. A) THE HAZARDOUS EXHAUST
 DUCT SHALL EXTEND DIRECTLY TO THE EXTERIOR OF THE
 BUILDING AND SHALL NOT EXTEND INTO OR THROUGH DUCTS AND
 PLENUMS- SECTION 510.6.7 FBC M. B) REFER TO SECTION
 510.9 AND INDICATE THE TYPE OF LAB HOOD EXHAUST DUCT
  
 TO BE INSTALLED. C) PROVIDE AN EQUIPMENT SCHEDULE FOR
 THE LAB HOOD AND SUBMIT MANUFACTURER'S SPECIFICATIONS
 WITH A SPEC SHEET STAMPED BY THE ENGINEER OF RECORD-
 SECTION 304.1 FBC M.
  
 4) REFER TO SECTION 414.1.3 FBC B: PROVIDE A HAZARDOUS
 MATERIALS REPORT THAT INCLUDES MATERIAL QUANTITIES, AND
 SUBMIT MSDS SHEETS FOR ALL MATERIALS TO BE STORED OR
 PROCESSED IN THE HAZARDOUS IV PREP ROOM AND ALL OTHER
 ROOMS AND SPACES.
  
 5) M102: WHAT IS THE PURPOSE OF THE EXHAUST SYSTEM IN
 THE UNPACK ROOM- SEE TABLE 7-1 ASHRAE 170-2008 AND
 INCLUDE THE ROOM IN THE DESIGN PARAMETERS SCHEDULE.
  
 6) M102: THE PLAN APPEARS TO SHOW THE RETURN DUCTS IN
 THE HAZADOUS AND NON-HAZARDOUS ROOMS CONNECTING INTO
 THE SUPPLY DUCT TO THE FFU'S- PLEASE CLARIFY
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-08-07 Cont ID  
Sent By jwitmer Date 2019-08-07 Time 15:57 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-06-06 Cont ID  
Sent By gjohnson Date 2019-06-06 Time 14:55 Rev Time 0.00
Received By gjohnson Date 2019-06-05 Time 14:12 Sent To  
Notes
2019-06-06 14:55:192ND REVIEW: 19020657
  
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT A103 THE ALCOVE FOR THE LAVATORY IN THE THE
 PATIENT TOILET IS TO SMALL FOR THE REQUIRED 30"X 48"
 CLEAR FLOOR SPACE THE ALCOVE SHALL BE A MIN OF 30" PER
 FBC ACC 606.2. 305, 306
  
 2. SHOW THE CLEAR FLOOR FOR THE LAVATORY , TOILET AND
 THE TURNING SPACE. PER FBC ACC 603.2.1, 606.2
  
 3. SHT. P901 SHOW THE REQUIRED SHUT OFF VALVES ON ALL
 THE DROPS. PER FBC PL 606.1(5)
  
 4. THE NEW HOT WATER SHALL COMPLY WITH FBC PL 607.2 HOT
 OR TEMPERED WATER SUPPLY TO FIXTURES.THE DEVELOPED
 LENGTH OF HOT OR TEMPERED WATER PIPING, FROM THE SOURCE
 OF HOT WATER TO THE FIXTURES THAT REQUIRE HOT OR
 TEMPERED WATER, SHALL NOT EXCEED 50 FEET .
 RECIRCULATING SYSTEM PIPING AND HEAT-TRACED PIPING
 SHALL BE CONSIDERED TO BE SOURCES OF HOT OR TEMPERED
 WATER.
  
 5. THE NEW HOT WATER PIPING SHALL BE INSULATED PER FBC
 PL E] 607.5
  
 6. A MIN OF 1 SINK IN THE EXAM ROOMS SHALL COMPLY FBC
 ACC 212.3, 606.2, 606.3
  
 .
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-09 Cont ID  
Sent By gjohnson Date 2019-03-09 Time 11:49 Rev Time 0.00
Received By gjohnson Date 2019-03-09 Time 10:51 Sent To  
Notes
2019-03-09 12:08:251ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE SANITARY AND WATER ISOMETRIC DRAWINGS
 FOR NEW PIPING. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 3. BACKFLOW DEVISE REQUIRED ON SUPPLY TO ICE MAKERS,
 WATER FILTERS AND COFFEE MAKERS. PER FBC PL 608.3,
 608.16.10
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-08-09 Cont ID  
Sent By pvalenti Date 2019-08-09 Time 06:35 Rev Time 0.00
Received By pvalenti Date 2019-08-09 Time 06:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-06-14 Cont ID  
Sent By shill Date 2019-06-14 Time 14:47 Rev Time 0.00
Received By shill Date 2019-06-14 Time 14:47 Sent To  
Notes
2019-06-04 11:24:23ELECTRICAL SHEETS GOOD.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-03-25 Cont ID  
Sent By shill Date 2019-03-25 Time 12:44 Rev Time 0.00
Received By shill Date 2019-03-25 Time 12:44 Sent To  
Notes
2019-03-25 12:45:12SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. STRUCTURAL PAGES INCLUDE A SIGNATURE AND SEAL BY AN
 ENGINEER FROM OHIO (ALPESH K. CHAVDA). A FLORIDA
 LICENSE IS REQUIRED TO PRACTICE ENGINEERING IN FLORIDA,
 FS471.
  
 2. THE TITLE BLOCK FOR THE ARCHITECT AND ENGINEER LACK
 THE BUSINESS LICENSE NUMBERS REQUIRED BY FS471, FS481.
  
 3. THE PLUMBING AND MECHANICAL PLANS DIGITAL SIGNATURES
 ARE OK, BUT IT IS NOT CLEAR WHERE THE TITLE BLOCK FOR
 THIS INDIVIDUAL IS (NEVENA G. PARSONS, PE). IS THIS
 ENGINEER PRACTICING THROUGH OSBORN ENGINEERING OR
 BOSTWICK DESIGN PARTNERSHIP, OR SHOULD THIS ENGINEER
 HAVE THEIR OWN TITLE BLOCK? SEE ALSO ITEM #2.
  
 4. THE ELECTRICAL, TECH DEMO, TECHNOLOGY PLANS DIGITAL
 SIGNATURES ARE OK, BUT IT IS NOT CLEAR WHERE THE TITLE
 BLOCK FOR THIS INDIVIDUAL IS SEAN M. JOHNSON, PE). IS
 THIS ENGINEER PRACTICING THROUGH OSBORN ENGINEERING OR
 BOSTWICK DESIGN PARTNERSHIP, OR SHOULD THIS ENGINEER
 HAVE THEIR OWN TITLE BLOCK? SEE ALSO ITEM #2.
  
 5. SEE BUILDING REVIEW, ARCHITECTURAL PAGES ARE NOT
 DIGITALLY SIGNED. STRUCTURAL PAGES ARE ALSO NOT
 DIGITALLY SIGNED (SEE ALSO ITEM 1).
  
 PLEASE CONTACT ME IF YOU WISH TO DISCUSS.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-08-06 Cont ID  
Sent By eschneid Date 2019-08-06 Time 13:13 Rev Time 0.25
Received By eschneid Date 2019-08-06 Time 13:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-06-03 Cont ID  
Sent By eschneid Date 2019-06-03 Time 15:46 Rev Time 0.25
Received By eschneid Date 2019-06-03 Time 15:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-03-18 Cont ID  
Sent By eschneid Date 2019-03-18 Time 16:10 Rev Time 0.75
Received By eschneid Date 2019-03-18 Time 16:10 Sent To  
Notes
2019-03-18 16:10:51FAILED
  
 PROVIDE WRITTEN RESPONSE.
  
 1) THE PERMIT IS FOR EXAM ROOMS (PHARMACY). PLEASE
 EXPLAIN WHAT IS MEANT BY PHARMACY. IS THIS A LOCATION
 WHERE CUSTOMERS WILL COME TO FILL PRESCRIPTIONS? RETAIL
 TRANSACTIONS WILL REQUIRE A USE CHANGE FROM THE CURRENT
 OFFICE USE TO RETAIL USE WITHIN THE CITYPLACE DRI
 MONITORING TABLE.
  
 2) THE PHYSICAL DEMOLITION AND CONSTRUCTION COMPLY WITH
 ZONING REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  
  