Plan Review Details - Permit 19020640
Plan Review Stops For Permit 19020640
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-05 Cont ID  
Sent By jwitmer Date 2019-08-05 Time 09:08 Rev Time 0.00
Received By jwitmer Date 2019-08-05 Time 08:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-25 Cont ID  
Sent By jwitmer Date 2019-02-25 Time 10:49 Rev Time 0.00
Received By jwitmer Date 2019-02-25 Time 07:26 Sent To  
Notes
2019-02-25 10:49:262017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020640
 ADD: 6620 S. DIXIE HWY.
 CONT: K-CHAR INC.
 TEL: 561-924-2179
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 25/ 2018
 ACTION: DENIED
  
 1) THERE IS A DISCREPANCY OF THE SCOPE OF WORK BETWEEN
 THE CONTRACTOR FILLING OUT THE PERMIT APPLICATION,
 WINDOW REPLACEMENT, A/C & ELECTRICAL WORK AND THE
 ENGINEER OF RECORD STATING IT IS A CHANGE OF OCCUPANCY?
 SHEET 1 OF 4 STATES THIS PERMIT IS FOR A CHANGE OF
 OCCUPANCY. THE CONTRACTOR WILL NEED TO CHANGE THE
 DESCRIPTION OF WORK.
 FOR THIS REVIEW I AM GOING TO GO WITH THE ENGINEERS
 CODE ANALYSIS, SINCE THIS IS HOW THE PLANS WERE
 DEVELOPED.
  
 2) IN THE ENGINEERS TITLE BLOCK NEXT TO THE ENGINEERS
 CERTIFICATE OF AUTHORIZATION IS FOUND NOA 13-0222.02
 WHICH IS A LABORATORY CERTIFICATION FOR TURQUOISE
 ENGINEERING LLC, EXPIRED ON 3/21/2018.
  
 3) SHEET 1 OF 4 UNDER THE HEADING OF CODE ANALYSIS,
 EXISTING OCCUPANCY CLASSIFICATION THE PLANS STATE:
 EXISTING BUILDING CODE SECTIONS 1012 CHANGE OF
 OCCUPANCY
 CHAPTER 3 ALL COMPLIANCE METHODS.
  
 3A) UNDER THE 2017 EXISTING BUILDING CODE SECTION 1012
 IS A CHANGE OF OCCUPANCY IS TO BE USED IF ONLY A
 PORTION OF THE BUILDING IS UNDERGOING A PARTIAL CHANGE
 OF OCCUPANCY. WHEN GOING TO THE P. B. C. PROPERTY
 APPRAISERS SITE AND VIEW THE DIMENSIONS FOR THIS
 BUILDING, THE WHOLE BUILDING IS UNDERGOING A CHANGE OF
 OCCUPANCY AND SECTION 1001.2.2 SHOULD BE DECLARED.
  
 2017 EXISTING BUILDING CODE 1001.2.2 CHANGE OF
 OCCUPANCY CLASSIFICATION OR GROUP. WHERE THE OCCUPANCY
 CLASSIFICATION OF A BUILDING CHANGES, THE PROVISIONS OF
 SECTIONS 1002 THROUGH 1012 SHALL APPLY. THIS INCLUDES A
 CHANGE OF OCCUPANCY CLASSIFICATION AND A CHANGE TO
 ANOTHER GROUP WITHIN AN OCCUPANCY CLASSIFICATION.
  
 3B) THE SECOND ISSUE OF CHAPTER 3 OF THE 2017
 FBC-EXISTING BUILDING CODE: ALL COMPLIANCE METHODS.
 PLEASE REVIEW THE 2017 EXISTING BUILDING CODE SECTION
 301.1. THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY OF
 ALL EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE
 METHODS LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS
 SELECTED BY THE APPLICANT. SECTIONS 301.1.1 THROUGH
 301.1.3 SHALL NOT BE APPLIED IN COMBINATION WITH EACH
 OTHER.
  
 3B)(1) 301.1.1 PRESCRIPTIVE COMPLIANCE METHOD.
  
 3B)(2) 301.1.2 WORK AREA COMPLIANCE METHOD.
  
 3B)(3) 301.1.3 PERFORMANCE COMPLIANCE METHOD.
  
 4) SHEET 1 OF 4 UNDER THE HEADING OF PROPOSED NEW
 OCCUPANCY THE PLANS DO NOT DECLARE, A CHANGE IN
 OCCUPANCY NOR COMPLIANCE WITH 2017 EXISTING BUILDING
 CODE 1001.2.2 CHANGE OF OCCUPANCY CLASSIFICATION OR
 GROUP. WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 1002 THROUGH 1012
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION AND A CHANGE TO ANOTHER GROUP WITHIN AN
 OCCUPANCY CLASSIFICATION.
  
 5) SHEET 2 OF 4 DOES GIVE A PORTION OF THE WIND DESIGN
 CRITERIA, THE VULT WIND SPEED, MEAN ROOF HEIGHT,
 EXPOSURE D, (MORE RESTRICTIVE, THE DESIGNER CAN BE MORE
 RESTRICTIVE) BUT NOT THE PRESSURES, PLEASE PROVIDE IN
 VULT AND VASD SINCE ALL OF THE PRODUCT APPROVALS ARE IN
 VASD.
 MISSING: DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 6A) PLEASE NOTE SHEET 2 OF 4 THE 2 NOA THE DESIGN
 PROFESSIONAL LIST ARE NEWER PRODUCT APPROVALS THAN THE
 ONES SUBMITTED, SAME BRAND AND MODEL. PLEASE NOTE THAT
 THE MIAMI-DADE NOA 17-0614.11 AND AN OLDER SAME PRODUCT
 UNDER NOA 15-0528.26 BOTH EXPIRED ON 02/19/2019. PLEASE
 UPDATE THE PRODUCT APPROVAL.
  
 6B) EXPIRED NOA MIAMI-DADE NOA 17-0614.11 AND AN OLDER
 SAME PRODUCT UNDER NOA 15-0528.26 ARE BOTH FOR A SINGLE
 WINDOW, PLEASE IDENTIFY THE TYPE OF GLAZING TO BE
 INSTALLED, AND ANCHORS. PLEASE ALSO NOTE SHEET 2 OF 4
 NOTES 5, 6, & 7 WILL NEED MULLIONS, THERE IS NO
 MULLIONS INCLUDED IN THIS REPORT.
  
 6C) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(B) MULLIONS
  
 6D) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
  
 7) SHEET 2 OF 4 INDICATES THE WIDTH OF THE RESTROOMS AS
 10 FEET 2 INCHES ON THE FLOOR PLAN BUT THE ACCESSIBLE
 DETAIL INDICATES THE WIDTH OF 10 FEET 4 INCHES,
 DISCREPANCY IN PLANS OR DOES THE WALL THICKNESS CHANGE.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 8) SHEET 2 OF 4 SHOWS ACCESS TO A STORAGE ROOM THROUGH
 A RESTROOM. BOTH THE RESTROOM DOOR AS WELL AS THE
 STORAGE ROOM DOORS ARE INDICATED TO BE 26X68 DOORS OR
 ONLY 28 INCHES CLEARANCE BETWEEN THE DOOR AND JAMB WHEN
 OPENED AT 90 DEGREES. PLEASE NOTE THERE IS NO ACCESS TO
 THE STORAGE CLOSET. CLOSETS THAT ARE OVER 24 INCHES IN
 DEPTH ARE REQUIRED TO BE ACCESSIBLE.
 PLEASE REVIEW THE 2017 FBC-ACCESSIBILITY CODE SECTION
 404.2.3. OPENINGS MORE THAN 24 INCHES DEEP SHALL
 PROVIDE A CLEAR OPENING OF 36 INCHES MINIMUM. PLEASE
 ALSO REVIEW THE REQUIREMENT FOR MANEUVERING CLEARANCES
 FIGURE 404.2.4.1(H).
  
 9) SHEET 2 OF 4 DOES NOT SHOW THE EXIT LIGHTS. SHEET 4
 OF 4 DOES SHOW EXIT LIGHTS. PLEASE NOTE THAT THE EXIT
 LIGHT AT THE REAR OF THE BUILDING IN THE HALLWAY WILL
 NOT BE VISIBLE IN THE MAIN OPEN OFFICE AREA, A
 DIRECTIONAL EXIT LIGHT WILL NEED TO BE ADDED IN FRONT
 OF THE HALLWAY ENTRANCE. SEE 2017 FBC-B 1013.1 WHERE
 REQUIRED.
  
 10) SHEET 2OF 4 DOES NOT SHOW A BREAK ROOM BUT SHEET 4
 OF 4 DOES SHOW A BREAK ROOM IN THE UTILITY ROOM # 2. NO
 DETAILS WERE SHOWN THIS REVIEW COMPLIANCE WITH THE
 ACCESSIBILITY CODE SECTION 606 LAVATORIES AND SINKS
 COULD NOT BE DETERMINED.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2020-02-25 Cont ID  
Sent By jpearson Date 2020-02-25 Time 13:35 Rev Time 0.00
Received By jpearson Date 2020-02-25 Time 13:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2020-02-05 Cont ID  
Sent By jpearson Date 2020-02-05 Time 10:10 Rev Time 0.00
Received By jpearson Date 2020-02-05 Time 10:09 Sent To I
Notes
2020-02-05 10:09:56CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT ADDRESSED.)
 3. CORRECTED.
 4. CORRECTED.
 5. ARE THERE ANY LOADS BEING ADDED? SOME LOADS ARE
 LISTED, BUT NO LOAD CALCULATION IS PROVIDED. PROVIDE
 ACCURATE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED.)
 6. CORRECTED.
 7. CORRECTED.
  
 NEW COMMENTS:
  
 8. NEW SHEETS HAVE BEEN STAPLED TO PLAN SET. THESE
 SHEETS ARE NOT SIGNED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. PROVIDE CORRECTION. WPB FBC 105.1, 107.1,
 107.2.1
  
 FURTHER COMMENTS ARE POSSIBLE BASED ON THE RESPONSE
 RECEIVED FROM THESE COMMENTS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-10-30 Cont ID  
Sent By jpearson Date 2019-10-30 Time 15:38 Rev Time 0.00
Received By jpearson Date 2019-10-30 Time 15:38 Sent To M
Notes
2019-10-30 15:17:36CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. ELECTRICAL PLAN STATES: "FOR REFERENCE ONLY". PERMIT
 APPLICATION STATES THERE IS ELECTRICAL WORK TO BE
 COMPLETED, BUT PLAN PROVIDED DOES NOT PROPOSE ANY WORK.
 PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND SEALED
 BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5 (THERE ARE 2 SHEETS
 IN THE PACKAGE FOR ELECTRICAL. ONE STILL STATES FOR
 REFERENCE ONLY. THE OTHER SHEET HAS A STATEMENT THAT IT
 IS PREPARED BY AN ENGINEER AND STATES UNAUTHORIZED
 DUPLICATION IS NOT PERMITTED, THIS SHEET IS SIGNED BY
 THE ELECTRICAL CONTRACTOR IN VIOLATION OF THIS
 STATEMENT. PROVIDE CORRECTION.)
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT ADDRESSED.)
 3. PLAN DOES NOT INDICATE WHAT IS EXISTING AND WHAT IS
 NEW. PROVIDE CLARIFICATION. WPB FBC 107.2.1 (NOT
 ADDRESSED.)
 4. AN AIC CALCULATION WAS PROVIDED, BUT THE SERVICE IS
 SHOWN AS EXISTING. IS THIS A NEW SERVICE? PROVIDE
 CLARIFICATION. WPB FBC 107.2.1 (NOT ADDRESSED.)
 5. ARE THERE ANY LOADS BEING ADDED? SOME LOADS ARE
 LISTED, BUT NO LOAD CALCULATION IS PROVIDED. PROVIDE
 ACCURATE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30 (NOT ADDRESSED.)
 6. FOR CHANGE OF OCCUPANCY, IF LIGHTS ARE BEING ADDED
 THE CODE REQUIRES AUTOMATIC CONTROL OF THE LIGHTING.
 PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2 (NOT
 ADDRESSED.)
  
 NEW COMMENTS:
  
 7. THERE ARE NOW 2 ELECTRICAL PLANS IN SET, ONE BY A
 CONTRACTOR AND ONE BY THE ENGINEER. ONLY ONE SET SHOULD
 BE INCLUDED, FROM THE PERSON RESPONSIBLE FOR THE
 DESIGN. PROVIDE CORRECTION AND ANSWERS TO ABOVE
 QUESTIONS. WPB FBC 105.1, 107.1, 107.2.1
  
 FURTHER COMMENTS ARE POSSIBLE BASED ON THE RESPONSE
 RECEIVED FROM THESE COMMENTS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-08-09 Cont ID  
Sent By jpearson Date 2019-08-09 Time 09:06 Rev Time 0.00
Received By jpearson Date 2019-08-09 Time 07:43 Sent To  
Notes
2019-08-09 08:34:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. ELECTRICAL PLAN STATES: "FOR REFERENCE ONLY". PERMIT
 APPLICATION STATES THERE IS ELECTRICAL WORK TO BE
 COMPLETED, BUT PLAN PROVIDED DOES NOT PROPOSE ANY WORK.
 PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND SEALED
 BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5 (THERE ARE 2 SHEETS
 IN THE PACKAGE FOR ELECTRICAL. ONE STILL STATES FOR
 REFERENCE ONLY. THE OTHER SHEET HAS A STATEMENT THAT IT
 IS PREPARED BY AN ENGINEER AND STATES UNAUTHORIZED
 DUPLICATION IS NOT PERMITTED, THIS SHEET IS SIGNED BY
 THE ELECTRICAL CONTRACTOR IN VIOLATION OF THIS
 STATEMENT. PROVIDE CORRECTION.)
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT ADDRESSED.)
  
 NEW COMMENTS:
  
 3. PLAN DOES NOT INDICATE WHAT IS EXISTING AND WHAT IS
 NEW. PROVIDE CLARIFICATION. WPB FBC 107.2.1
 4. AN AIC CALCULATION WAS PROVIDED, BUT THE SERVICE IS
 SHOWN AS EXISTING. IS THIS A NEW SERVICE? PROVIDE
 CLARIFICATION. WPB FBC 107.2.1
 5. ARE THERE ANY LOADS BEING ADDED? SOME LOADS ARE
 LISTED, BUT NO LOAD CALCULATION IS PROVIDED. PROVIDE
 ACCURATE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30
 6. FOR CHANGE OF OCCUPANCY, IF LIGHTS ARE BEING ADDED
 THE CODE REQUIRES AUTOMATIC CONTROL OF THE LIGHTING.
 PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
  
 FURTHER COMMENTS ARE POSSIBLE BASED ON THE RESPONSE
 RECEIVED FROM THESE COMMENTS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-07 Cont ID  
Sent By jpearson Date 2019-03-07 Time 13:08 Rev Time 0.00
Received By jpearson Date 2019-03-06 Time 06:44 Sent To  
Notes
2019-03-07 13:08:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN STATES: "FOR REFERENCE ONLY". PERMIT
 APPLICATION STATES THERE IS ELECTRICAL WORK TO BE
 COMPLETED, BUT PLAN PROVIDED DOES NOT PROPOSE ANY WORK.
 PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND SEALED
 BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-07-23 Cont ID  
Sent By pleduc Date 2019-07-23 Time   Rev Time 0.00
Received By pleduc Date 2019-07-23 Time 09:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-02-20 Cont ID  
Sent By pleduc Date 2019-02-20 Time   Rev Time 0.00
Received By pleduc Date 2019-02-20 Time 14:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2020-02-05 Time   Rev Time 0.00
Received By lmarchan Date 2020-01-31 Time 13:27 Sent To  
Notes
2020-02-03 13:27:45RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-10-31 Cont ID  
Sent By cmontell Date 2019-10-31 Time 14:00 Rev Time 0.00
Received By cmontell Date 2019-10-31 Time 14:00 Sent To  
Notes
2019-10-28 14:28:03RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-12 Cont ID  
Sent By cmontell Date 2019-08-12 Time 11:26 Rev Time 0.00
Received By cmontell Date 2019-08-12 Time 11:26 Sent To  
Notes
2019-08-12 07:36:46GAVE TO CHRIS MONTELLO.
2019-07-22 13:07:01B10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-03-11 Time   Rev Time 0.00
Received By lmarchan Date 2019-02-14 Time 11:38 Sent To  
Notes
2019-02-15 11:38:12B33

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-10-31 Cont ID  
Sent By cmontell Date 2019-10-31 Time 13:59 Rev Time 0.00
Received By cmontell Date 2019-10-31 Time 13:59 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-08-12 Cont ID  
Sent By cmontell Date 2019-08-12 Time 11:24 Rev Time 0.00
Received By cmontell Date 2019-08-12 Time 11:24 Sent To I
Notes
2019-08-12 11:26:13MECHANICAL PLAN REVIEW FAIL
  
 1- ***********************NEED MECHANICAL PLANS
 107.1*********************************
  
 CHRIS MONTELLO
 561-805-6733

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-03-11 Cont ID  
Sent By ccole Date 2019-03-11 Time 10:00 Rev Time 0.00
Received By ccole Date 2019-03-11 Time 08:56 Sent To I
Notes
2019-03-11 10:12:511ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19020640
 3/11/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS HAVE BEEN SUBMITTED FOR REVIEW.
 PLEASE PROVIDE PLANS THAT CLEARLY SHOW THE SCOPE OF
 WORK FOR THE PROPOSED BUSINESS OFFICE- SECTION 107.1
 WPB.
  
 2) THE BUILDING PLANS EXAMINER HAS IDENTIFIED THE
 PROPOSED PROJECT AS A "CHANGE OF OCCUPANCY". PLEASE
 REFER TO SECTION 301.1 FBC EX AND INDICATE WHICH
 COMPLIANCE METHOD WILL BE APPLIED. PLEASE NOTE THAT IF
 CHOOSING THE WORK AREA METHOD (301.1.2) REFER TO
 SECTION 1009.1 FBC EX AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR THE SPACE- SEE TABLE 403.3.1.1 FBC M.
  
 3) REFER TO SECTION C505.1 FBC EC AND VERIFY COMPLIANCE
 PETAINING TO CHANGES IN ENERGY DEMAND. PLEASE NOTE THAT
 NEW MECHANICAL AND ELECTRCAL LIGHTING CHANGES MAY
 INCREASE THE DEMAND.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-07-30 Cont ID  
Sent By llouie Date 2019-07-30 Time 13:48 Rev Time 0.00
Received By llouie Date 2019-07-30 Time 13:48 Sent To  
Notes
2019-07-30 13:48:55* WINDOW REPLACEMENT, INTERIOR MODIFICATIONS AND A/C
 ONLY.
  
 * VALUE OF SCOPE DOES NOT EXCEED 50% VALUE OF THE
 STRUCTURE.
  
 * ZONE: NC

Review Stop Z ZONING
Rev No 1 Status P Date 2019-02-27 Cont ID  
Sent By llouie Date 2019-02-27 Time   Rev Time  
Received By llouie Date 2019-02-26 Time   Sent To  
Notes
2019-02-27 09:08:08* WINDOW REPLACEMENT, INTERIOR MODIFICATIONS AND A/C
 ONLY.
  
 * VALUE OF SCOPE DOES NOT EXCEED 50% VALUE OF THE
 STRUCTURE.
  
 * ZONE: NC