| 2019-03-11 09:19:15 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19020631 |
| | 3/11/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE GENERAL CONTRACTOR NEEDS TO CLARIFY WITH WPB |
| | BUILDING DEPT. IF THE PRIVATE PROVIDER WILL BE |
| | PROVIDING BOTH PLAN REVIEW AND INSPECTIONS ON THE |
| | PROPOSED PROJECT. |
| | |
| | 2) SHEET GM401 OF THE MAIN GARAGE PLANS (PERMIT |
| | #18090262) SHOW THE CO AND NO2 SENSORS LOCATED IN THE |
| | BASEMENT LEVEL CONNECTING TO CONTROLLER SCD-103 TO |
| | ACTIVATE STROBE LIGHT ALARM DEVICES. PLEASE CLARIFY IF |
| | THIS SYSTEM IS CONNECTED TO THE MAIN FIRE ALARM SYSTEM. |
| | THE CONTROLLER IS NOT SHOWN ON THE PLAN (SHEET FA-02). |
| | |
| | 3) PROVIDE A SUBMITTAL FOR THE LEAD ACID BATTERY |
| | CABINETS, AND REFER TO SECTION 502.5 FBC M. THE BATTERY |
| | CABINETS ARE REQUIRED TO BE VENTILATED IN ACCORDANCE |
| | WITH SECTION 502.5. THE CABINETS WERE NOT SHOWN ON THE |
| | MAIN MECHANICAL PLANS. PLEASE CONTACT THE GENERAL |
| | CONTRACTOR AND THE ENGINEER OF RECORD AS A REVISION TO |
| | THE MAIN PLANS MAY BE REQUIRED FOR THE VENTILATION |
| | SYSTEMS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |