| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | |
| | NEW COMMENTS: |
| | |
| | 3. PANEL C SHOWS CIRCUIT 40 AND 42 AS FEEDING A |
| | GENERATOR RECEPTACLE. THIS RECEPTACLE IS NOT SHOWN IN |
| | ANY OTHER LOCATION ON THE PLAN. WHAT IS THE PRURPOSE OF |
| | THIS RECEPTACLE? IF THIS IS A PLUG FOR A STAND BY |
| | GENERATOR, A MEANS TO ISOLATE THE GENERATOR FEED FROM |
| | THE POWER COMPANY FEED IS REQUIRED. PROVIDE CORRECTION. |
| | NEC 702.5 |
| | 4. RISER DIAGRAM SHOWS AN ATS WITH THE NOTE THAT AN ATS |
| | IS NOT EXISTING AND THIS IS A PASS THROUGH DEVICE ONLY. |
| | PROVIDE CLARIFICATION. WHAT TYPE OF DEVICE IS LOCATED |
| | HERE? IS THIS A JUNCTION BOX WITH PULL THROUGH WIRES |
| | ONLY, OR IS THERE SOME TYPE OF DEVICE HERE? LABEL |
| | CORRECTLY. WPB FBC 107.2.1 |
| | 5. WHY IS THERE A LOAD OF 10 KW SPECIFIED FOR THE |
| | GENERATOR RECEPTACLE? IS THIS AN ACTUAL LOAD, OR A |
| | GENERATOR FEEDING THE PANEL? PROVIDE ACCURATE LOAD |
| | CALCULATION. NEC 220; WPB FBC 107.2.1 |
| | 6. IF THIS IS A GENERATOR FEEDING THE PANEL, HOW WILL A |
| | SINGLE PHASE GENERATOR PROVIDE THE NECESSARY POWER FOR |
| | THREE PHASE LOADS? PROVIDE CLARIFICATION. NEC 110.3; |
| | WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |