Plan Review Details - Permit 19020507
| Plan Review Stops For Permit 19020507 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-02-28 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-02-28 |
Time |
06:46 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-02-28 |
Time |
06:28 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-02-21 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-02-21 |
Time |
06:28 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-02-21 |
Time |
06:19 |
Sent To |
I |
|
| Notes |
| 2019-02-21 06:28:00 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. NO UL OR OTHER NRTL (NATIONALLY RECOGNIZED TESTING | | | LABRATORY) LISTING FOR WAP'S OR CAMERAS. CUT SHEETS | | | PROVIDED HAVE NO INFORMATION ON LISTING. PLEASE PROVIDE | | | LISTINGS. FBC 107.2.1 NEC 90.7,110.2,110.3B | | | | | | SPEC SHEETS CAN BE EMAILED TO REVIEWER, CUSTOMER DOES | | | NOT HAVE TO COME DOWN TO RESUBMIT. PLEASE CONTACT | | | REVIEWER BY EMAIL. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-02-21 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-02-21 |
Time |
06:28 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-02-12 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2019-02-13 11:01:47 | ROUTED TO ELECTRICAL INBOX |
|
|
|