Plan Review Details - Permit 19020470
Plan Review Stops For Permit 19020470
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-05-14 Cont ID  
Sent By pvalenti Date 2019-05-09 Time 16:20 Rev Time 0.00
Received By pvalenti Date 2019-05-09 Time 16:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-04-24 Cont ID  
Sent By pvalenti Date 2019-04-24 Time 10:05 Rev Time 0.00
Received By pvalenti Date 2019-04-24 Time 07:06 Sent To  
Notes
2019-04-24 10:31:14***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND BUILDING PLAN REVIEW DENIED:
  
 1. FAIL, PLEASE CORRECT THE PERMIT APPLICATION PAGE;
 THE APPLICATION PAGE SHOULD INDICATE LEVEL 14 NOT SUITE
 100.
 2. OK
 3. OK
 4. OK
 4 A. OK
 4 B. FAIL, THIS ITEM HAS BEEN ACKNOWLEDGED BY THE
 DESIGN PROFESSIONAL BUT THE THRESHOLD INSPECTION FORMS
 STILL NEED TO BE SIGNED AND NOTARIZED BY ALL PARTIES
 WITH INTEREST PRIOR TO ISSUANCE OF PERMIT.
 4 C. OK
 4 D. FAIL, THIS ITEM HAS BEEN ACKNOWLEDGED BY THE
 DESIGN PROFESSIONAL BUT THE RESUME FROM THE SPECIAL
 INSPECTOR IS REQUIRED FOR REVIEW.
 4 E. FAIL, THE CONTRACTOR HAS TO PROVIDE A JOB SUMMARY
 OR HISTORY OF WORKING WITH THIS TYPE OF CONSTRUCTION.
 4 F. OK ACKNOWLEDGED BY DESIGNER OF RECORD
 4 G. OK ACKNOWLEDGED BY DESIGNER OF RECORD
 4 H. OK ACKNOWLEDGED BY DESIGNER OF RECORD
 4 I. OK
 5. OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-25 Cont ID  
Sent By jwitmer Date 2019-02-25 Time 14:10 Rev Time 0.00
Received By jwitmer Date 2019-02-25 Time 13:04 Sent To  
Notes
2019-02-25 14:08:382017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020470
 ADD: 525 OKEECHOBEE BLVD. SUITE # 100/ ??????????????
 CONT: TBD/ TO BE DETERMINED
 TEL: ?????????????????
 E-MAIL: [email protected] JIM PITZER
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 25TH/ 2019
 ACTION: DENIED
  
 1) PLEASE CONFIRM WHERE THE WORK IS GOING TO TAKE PLACE
 WITHIN THE SCOPE OF THIS PERMIT. THE PERMIT APPLICATION
 INDICATES THE WORK WILL TAKE PLACE ON THE 1ST FLOOR,
 SUITE 100. WHEREAS THE COVERSHEET DRAWING INDEX
 REFERENCES FOR ALL OF THE TRADES THE 14 FLOOR IS WHERE
 THE WORK WILL TAKE PLACE? ADDITIONAL INFORMATION IS
 REQUIRED TO DETERMINE THE AREA OF WORK FOR THIS PERMIT?
 THE LIFE SAFETY SHEET, TITLE BLOCK DOES NOT STATE IF
 THE FLOOR IS THE 1ST FLOOR OR 14TH FLOOR.
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED
 AND DRAWN UPON SUITABLE MATERIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 2) IN THE SUPPORTING DOCUMENT FILE WE FIND 2 REPORTS
 (VOLUME 1 & 2) AND OR BINDERS BY THE OSBORN ENGINEERING
 COMPANY AND WHAT APPEARS TO BE A COPIED SEAL BY
 ARCHITECT ROBERT BOSTWICK. NOT AN ELECTRONIC SIGNATURE.
 PLEASE SHOW COMPLIANCE WITH: ARCHITECT DIGITAL SIGNING
 & SEALING PLANS. 61G1-16.005 PROCEDURES FOR DIGITALLY
 SIGNING AND SEALING AND FOR ELECTRONICALLY TRANSMITTING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 3) THE ARCHITECTURAL SHEETS AND STRUCTURAL SHEETS
 APPEAR TO HAVE BEEN PAPER PLANS THAT WERE SCANNED INTO
 THE COMPUTER, NONE OF THESE SHEETS HAVE ELECTRONIC
 SIGNATURES THAT WILL OPEN AND ALLOW VARICATION OF THE
 SIGNATURES.
  
 ARCHITECT DIGITAL SIGNING & SEALING PLANS. 61G1-16.005
 PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR
 ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 4) SHEET 009_S-001 HAS NOTES IN REGARDS TO STRUCTURAL
 TEST AND SPECIAL INSPECTIONS PER THE IBC. IN THE 2017
 FBC-B THESE CODE SECTIONS ARE RESERVED. THE TERM
 SPECIAL INSPECTOR FOUND WITHIN FLORIDA STATUTE
 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
 PLEASE SHOW COMPLIANCE WITH:
 4A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 4B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 FORMS SENT TO: : [email protected] 02/25/2019
 2:02 PM.
  
 4C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 4D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 4E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 4F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 4G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 4H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 4I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-05-03 Cont ID  
Sent By jleahy Date 2019-05-03 Time 15:29 Rev Time 0.00
Received By jleahy Date 2019-05-03 Time 15:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-04-05 Cont ID  
Sent By jpearson Date 2019-04-05 Time 12:41 Rev Time 0.00
Received By jpearson Date 2019-04-05 Time 12:30 Sent To  
Notes
2019-04-05 12:41:40ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 COMMENT RESPONSE NOT RECEIVED, NO APPARENT CORRECTIONS
 PROVIDED. SEE PREVIOUS REVIEW BELOW AND ADDRESS.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
  
 1. NEED LOAD CALCULATION DONE IN ACCORDANCE WITH
 ARTICLE 220 OF THE NEC LOADS ON P4 OR P5 EXCEED RATING
 AND NOT ALL LOADS SHOWN.
  
 2. PANELS P4 AND P5 LOOK OVER LOADED PER LOADS SHOWN,
 CHECK ALL LOADS TO COORDINATE WITH ELECTRIC SHOWN ON
 DRAWINGS. 0 LOAD SHOWN ON PANEL SCHEDULE NOT
 ACCEPTABLE.
  
 3. ELECTRIC TO NEW NUCLEAR CAMERA ROOMS AR TREATMENT
 ROOMS AND SHALL BE TREATED AS SUCH 517.13(A)(B)
  
 4. RISER DIAGRAM NEEDED AND SIGN SHALL BE POSTED AT
 EACH PANEL SHOWING WHERE IT IS FED FROM 408.4 PLEASE
 SHOW NOTE ON PLANS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-27 Cont ID  
Sent By jleahy Date 2019-02-27 Time 14:54 Rev Time 0.00
Received By jleahy Date 2019-02-27 Time 14:39 Sent To  
Notes
2019-03-26 08:24:52ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED LOAD CALCULATION DONE IN ACCORDANCE WITH ARTICLE
 220 OF THE NEC LOADS ON P4 OR P5 EXCEED RATING AND NOT
 ALL LOADS SHOWN.
  
 PANELS P4 AND P5 LOOK OVER LOADED PER LOADS SHOWN,
 CHECK ALL LOADS TO CORODINATE WITH ELECTRIC SHOWN ON
 DRAWINGS 0 LOAD ON PANEL SCHEDULE NOT ACCEPTABLE.
  
 ELECTRIC TO NEW NUCLEAR CAMERA ROOMS AR TREATMENT ROOMS
 AND SHALL BE TREATED AS SUCH 517.13(A)(B)
  
 RISER DIAGRAM NEEDED AND SIGN SHALL BE POSTED AT EACH
 PANEL SHOWING WHERE IT IS FED FROM 408.4 PLEASE SHOW
 NOTE ON PLANS .

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-04-03 Cont ID  
Sent By scaldero Date 2019-04-03 Time 08:19 Rev Time 0.00
Received By scaldero Date 2019-04-03 Time 08:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-02-14 Cont ID  
Sent By scaldero Date 2019-02-14 Time 13:46 Rev Time 0.00
Received By scaldero Date 2019-02-14 Time 13:11 Sent To  
Notes
2019-02-14 13:46:26PERMIT # 19020470
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-05-17 Cont ID  
Sent By pvalenti Date 2019-05-17 Time 14:52 Rev Time 0.00
Received By pvalenti Date 2019-05-15 Time 11:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-09 Cont ID  
Sent By pvalenti Date 2019-05-09 Time 17:14 Rev Time 0.00
Received By pvalenti Date 2019-04-29 Time 08:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-24 Cont ID  
Sent By pvalenti Date 2019-04-24 Time 10:59 Rev Time 0.00
Received By pvalenti Date 2019-04-02 Time 14:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-20 Cont ID  
Sent By lmarchan Date 2019-03-20 Time 16:56 Rev Time 0.00
Received By lmarchan Date 2019-02-11 Time 13:42 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-02-25 Cont ID  
Sent By jwitmer Date 2019-02-25 Time 14:08 Rev Time 0.00
Received By jwitmer Date 2019-02-25 Time 13:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-05-17 Cont ID  
Sent By ccole Date 2019-05-17 Time 14:47 Rev Time 0.00
Received By ccole Date 2019-05-17 Time 10:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-05-02 Cont ID  
Sent By ccole Date 2019-05-02 Time 11:14 Rev Time 0.00
Received By ccole Date 2019-05-02 Time 11:13 Sent To  
Notes
2019-05-02 11:24:293RD REVIEW FBC-2017 MECHANICAL
 PERMIT #19020470
 5/2/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M101: REFER TO TABLE 7-1 ASHRAE 170-2008 AND
 PROVIDE AN EXHAUST SYSTEM FOR THE NUCLEAR CAMERA ROOM.
 ALL AIR SHALL BE EXHAUSTED FROM THE ROOM AND
 RECIRCULATION IS NOT ALLOWED.
  
 2) M101: AN AUTOMATIC SHUTOFF DAMPER, EITHER MOTORIZED
 OR GRAVITY, SHALL BE PROVIDED FOR THE O/A DUCT
 SUPPLYING AIR TO THE NEW WHP- 14-1- SECTION C403.2.4.3
 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-04-16 Cont ID  
Sent By ccole Date 2019-04-16 Time 08:25 Rev Time 0.00
Received By ccole Date 2019-04-15 Time 17:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-03-11 Cont ID  
Sent By ccole Date 2019-03-11 Time 15:20 Rev Time 0.00
Received By ccole Date 2019-03-11 Time 15:20 Sent To  
Notes
2019-03-11 15:28:391ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19020470
 3/11/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO TABLE 7-1 ASHRAE 170-2008 AND PROVIDE THE
 DESIGN PARAMETERS (PRESSURE RELATIONSHIPS ETC.) FOR THE
 ROOMS- NUCLEAR CAMERA, INJECT, STRESS TEST, AND STRESS
 ECHO. PLEASE LABEL ALL ROOMS IN THE WORK AREAS ON THE
 MECHANICAL PLANS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-05-01 Cont ID  
Sent By gjohnson Date 2019-05-01 Time 16:51 Rev Time 0.00
Received By gjohnson Date 2019-05-01 Time 16:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-10 Cont ID  
Sent By gjohnson Date 2019-04-10 Time 12:56 Rev Time 0.00
Received By gjohnson Date 2019-04-10 Time 11:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-03-07 Cont ID  
Sent By gjohnson Date 2019-03-07 Time 17:03 Rev Time 0.00
Received By gjohnson Date 2019-03-07 Time 17:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-05-17 Cont ID  
Sent By pvalenti Date 2019-05-17 Time 14:50 Rev Time 0.00
Received By pvalenti Date 2019-05-17 Time 14:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2019-05-09 Cont ID  
Sent By pvalenti Date 2019-05-09 Time 17:12 Rev Time 0.00
Received By pvalenti Date 2019-05-09 Time 17:12 Sent To  
Notes
2019-05-14 10:54:02NEW MECHANICAL PAGES NEED SIGNATURE REVIEW NEXT CYCLE
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-04-24 Cont ID  
Sent By pvalenti Date 2019-04-24 Time 10:46 Rev Time 0.00
Received By pvalenti Date 2019-04-24 Time 10:46 Sent To  
Notes
2019-04-24 10:59:08***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND REVIEW DENIED:
  
 1. OK
  
 2. FAIL, THE TITLE BLOCK FOR THE ARCHITECT AND ENGINEER
 LACK
 THE BUSINESS LICENSE NUMBERS REQUIRED BY FS471, FS481.
  
 3. FAIL, THE PLUMBING AND MECHANICAL PLANS DIGITAL
 SIGNATURES
 ARE OK, BUT IT IS NOT CLEAR WHERE THE TITLE BLOCK FOR
 THIS INDIVIDUAL IS (NEVENA G. PARSONS, PE). IS THIS
 ENGINEER PRACTICING THROUGH OSBORN ENGINEERING OR
 BOSTWICK DESIGN PARTNERSHIP, OR SHOULD THIS ENGINEER
 HAVE THEIR OWN TITLE BLOCK? SEE ALSO ITEM #2.
  
 4. FAIL, THE ELECTRICAL, TECH DEMO, TECHNOLOGY PLANS
 DIGITAL
 SIGNATURES ARE OK, BUT IT IS NOT CLEAR WHERE THE TITLE
 BLOCK FOR THIS INDIVIDUAL IS SEAN M. JOHNSON, PE). IS
 THIS ENGINEER PRACTICING THROUGH OSBORN ENGINEERING OR
 BOSTWICK DESIGN PARTNERSHIP, OR SHOULD THIS ENGINEER
 HAVE THEIR OWN TITLE BLOCK? SEE ALSO ITEM #2.
  
  
  
2019-04-05 12:42:11ELECTRICAL SHEETS OK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-03-25 Cont ID  
Sent By shill Date 2019-03-25 Time 12:02 Rev Time 0.00
Received By shill Date 2019-03-25 Time 12:02 Sent To  
Notes
2019-03-25 12:04:34SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. STRUCTURAL PAGES INCLUDE A SIGNATURE AND SEAL BY AN
 ENGINEER FROM OHIO (ALPESH K. CHAVDA). A FLORIDA
 LICENSE IS REQUIRED TO PRACTICE ENGINEERING IN FLORIDA,
 FS471.
  
 2. THE TITLE BLOCK FOR THE ARCHITECT AND ENGINEER LACK
 THE BUSINESS LICENSE NUMBERS REQUIRED BY FS471, FS481.
  
 3. THE PLUMBING AND MECHANICAL PLANS DIGITAL SIGNATURES
 ARE OK, BUT IT IS NOT CLEAR WHERE THE TITLE BLOCK FOR
 THIS INDIVIDUAL IS (NEVENA G. PARSONS, PE). IS THIS
 ENGINEER PRACTICING THROUGH OSBORN ENGINEERING OR
 BOSTWICK DESIGN PARTNERSHIP, OR SHOULD THIS ENGINEER
 HAVE THEIR OWN TITLE BLOCK? SEE ALSO ITEM #2.
  
 4. THE ELECTRICAL, TECH DEMO, TECHNOLOGY PLANS DIGITAL
 SIGNATURES ARE OK, BUT IT IS NOT CLEAR WHERE THE TITLE
 BLOCK FOR THIS INDIVIDUAL IS SEAN M. JOHNSON, PE). IS
 THIS ENGINEER PRACTICING THROUGH OSBORN ENGINEERING OR
 BOSTWICK DESIGN PARTNERSHIP, OR SHOULD THIS ENGINEER
 HAVE THEIR OWN TITLE BLOCK? SEE ALSO ITEM #2.
  
 PLEASE CONTACT ME IF YOU WISH TO DISCUSS.
  
  
  
  
  
  
  
  
  
  
  
2019-02-25 14:10:46ARCHITECTURAL , STRUCTURAL SHEETS NOT ELECTRONICALLY
 SIGNED AND SEALED NOR THE PROJECT MANUALS VOLUME 1 & 2.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status P Date 2019-05-14 Cont ID  
Sent By pvalenti Date 2019-05-14 Time 11:00 Rev Time 0.00
Received By pvalenti Date 2019-05-14 Time 10:59 Sent To  
Notes
2019-05-14 11:06:07PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 NOTE:
  
 THE THRESHOLD INSPECTOR AND INSPECTOR REPRESENTATIVE
 HAVE BEEN APPROVED. PLEASE SUBMIT THE COMPLETED
 INFORMATION ON OUR UPDATED THRESHOLD AGREEMENT FORMS
 FORMS (NOT COPIES) AT TIME OF PICKING UP PERMIT.

Review Stop Z ZONING
Rev No 3 Status P Date 2019-05-03 Cont ID  
Sent By eschneid Date 2019-05-03 Time 14:43 Rev Time 0.25
Received By eschneid Date 2019-05-03 Time 14:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-04-08 Cont ID  
Sent By eschneid Date 2019-04-08 Time 10:22 Rev Time 0.25
Received By eschneid Date 2019-04-08 Time 10:22 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-03-20 Cont ID  
Sent By eschneid Date 2019-03-20 Time 15:39 Rev Time 0.25
Received By eschneid Date 2019-03-20 Time 15:39 Sent To  
Notes
2019-03-20 15:41:03FAILED
  
 1) PLEASE CLARIFY THE LOCATION OF WORK. THE PLANS ALL
 SHOW THE 14TH FLOOR, BUT THE APPLICATION IS FOR THE 1ST
 FLOOR.
  
 2) IF NO WORK IS OCCURRING ON THE 1ST FLOOR, THEN IT
 MEETS ZONING REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.