| 2019-03-05 08:14:52 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19020378 |
| | ADD: 2970 N MILITARY TRAIL / CANOPY/ ANNEXATION IN |
| | PROGRESS |
| | CONT: TBD / TO BE DETERMINED |
| | TEL: ??????????????? |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: TUES. MARCH 5/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) THIS PERMIT APPLICATION FOR A CANOPY IS FOR PROPERTY |
| | BEING ANNEXED INTO THE CITY OF WEST PALM BEACH. NO |
| | PERMIT CAN BE ISSUED UNTIL THIS PROCESS IS COMPLETE. |
| | THE OTHER ISSUE IS A CONTRACTOR WILL NEED TO SIGN ON AS |
| | THE CONTRACTOR OF RECORD FOR THE REMOVAL OF THIS |
| | BUILDING. 2017 FLORIDA BUILDING CODE W 2017 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION 105.1 REQUIRED. |
| | |
| | 2) THE SOILS REPORT BY GFA INTERNATIONAL FOUND THE |
| | GROUND WATER TABLE APPROXIMATELY 3.08? TO 4.5 ? BELOW |
| | GRADE. THE BOTTOM OF THE CANOPY IS 6.75? BELOW GRADE. |
| | THE REPORT DOES INDICATE UNDER THE HEADING OF 3.2.2 |
| | SITE PREPARATION COMMENT # 8 DOES INDICATE DEWATERING |
| | OR REMOVAL TEMPORARY PERCHED WATER MAY NEED TO OCCUR. |
| | THE SUBMITTED SOILS REPORT DOES NOT ADDRESS THE NEEDED |
| | DEWATERING FOR THE CANOPY FOOTINGS NOR THE EXCAVATION |
| | REQUIRED FOR THE 3 UNDERGROUND STORAGE TANKS. PLEASE |
| | PROVIDE A DEWATERING PLAN FOR BOTH THE CANOPY |
| | FOUNDATION AS WELL AS FOR THE 3 UNDERGROUND STORAGE |
| | TANKS. 1803.5.4. GROUND WATER TABLE. |
| | |
| | 3) PLEASE ALSO INCLUDE THE SEQUENCE OR SCHEDULING OF |
| | THE CANOPY FOUNDATION AND UNDERGROUND TANK INSTALLATION |
| | BECAUSE OF THE DEPTH OF THE TANKS UNDERGROUND AND THE |
| | CLOSENESS TO THE CANOPY FOUNDATIONS. SHOW HOW |
| | COMPLIANCE WITH SECTION EXCAVATION NEAR FOUNDATIONS |
| | WILL BE COMPLIED WITH. |
| | THIS IS CRUCIAL SINCE THERE MAYBE 2 DIFFERENT |
| | CONTRACTORS INVOLVED, A BUILDING OR GENERAL CONTRACTOR |
| | FOR THE CANOPY AND A POLLUTANT STORAGE SYSTEM |
| | CONTRACTOR FOR THE UNDERGROUND TANKS, AND UNDERGROUND |
| | PIPING ASSOCIATED WITH THIS INSTALLATION. |
| | |
| | 2017 FBC-B 1803.5.7 EXCAVATION NEAR FOUNDATIONS. WHERE |
| | EXCAVATION WILL REDUCE SUPPORT FROM ANY FOUNDATION, A |
| | REGISTERED DESIGN PROFESSIONAL SHALL PREPARE AN |
| | ASSESSMENT OF THE STRUCTURE AS DETERMINED FROM |
| | EXAMINATION OF THE STRUCTURE, THE REVIEW OF AVAILABLE |
| | DESIGN DOCUMENTS AND, IF NECESSARY, EXCAVATION OF TEST |
| | PITS. THE REGISTERED DESIGN PROFESSIONAL SHALL |
| | DETERMINE THE REQUIREMENTS FOR UNDERPINNING AND |
| | PROTECTION AND PREPARE SITE-SPECIFIC PLANS, DETAILS AND |
| | SEQUENCE OF WORK FOR SUBMISSION. SUCH SUPPORT SHALL BE |
| | PROVIDED BY UNDERPINNING, SHEETING AND BRACING, OR BY |
| | OTHER MEANS ACCEPTABLE TO THE BUILDING OFFICIAL. |
| | |
| | 4) PLEASE NOTE NONE OF THE SITE PLANS, SURVEY, CANOPY |
| | FOUNDATION, ROOF PLAN, CANOPY MISC. PLAN NOR THE FUEL |
| | CANOPY PLAN AND ELEVATIONS ARE ELECTRONICALLY SIGNED |
| | AND SEALED. |
| | 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING |
| | ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS. |
| | |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| | SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE |
| | OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON |
| | ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 5A) PLEASE NOTE ON THE FOUNDATION PLAN 004_CANOPY |
| | FOUNDATION PLAN UNDER THE FIGURE C-1 THERE IS A COLUMN |
| | SCHEDULE C-1 THROUGH C-8 THAT IS BLANK IT WOULD APPEAR |
| | IT NEEDS TO BE FILED IN.107.2.1.2 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 5B) PLEASE NOTE ON THE FOUNDATION PLAN 004_CANOPY |
| | FOUNDATION PLAN UNDER APPROVALS FOR THE CANOPY IT WOULD |
| | APPEAR THAT A DESIGN PROFESSIONAL IS TO APPROVE THESE |
| | DRAWINGS WITH AS SUBMITTED OR APPROVED WITH NOTED |
| | CHANGES AND APPROVED BY ??????? AND DATED. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 6) THE CANOPY PLAN AND CANOPY MISC. DETAIL PLAN SHOWS |
| | MISC. CANOPY ROOFING MATERIALS (CANOPY METAL DECKING) |
| | AND ANCHORS, PLEASE SUPPLY PRODUCT APPROVALS FOR THESE |
| | SYSTEMS. |
| | 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31(D) ROOFING PRODUCTS AND ASSEMBLIES, |
| | |
| | 7) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 8) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 9) SHEET 004_CANOPY FOUNDATION PLAN HAS A HEADING FOR |
| | GENERAL NOTES AND WITHIN THESE NOTES THERE IS THE |
| | INFORMATION FOR THE WIND DESIGN CRITERIA, AND THE |
| | BUILDING IS DESIGNED AS A OPEN BUILDING, BUT THE |
| | MISSING INFORMATION WOULD BE THE POSITIVE/ NEGATIVE |
| | PRESSURES FOR ROOF ZONES 1, 2 & 3. |
| | 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| | 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS. |
| | |
| | 10) INFORMATIONAL ONLY, THE CANOPY WILL NOT NEED TO GO |
| | FOR IMPACT FEE REVIEW, BUT THE GAS/ DIESEL PUMPS WILL |
| | NEED TO GO FOR IMPACT FEE REVIEW, POINT OF SALE. |
| | |
| | 11) WELDED OR BOLTED CONNECTIONS |
| | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION. |
| | 2017 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2) QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | |
| | 12) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |