Plan Review Details - Permit 19020375
Plan Review Stops For Permit 19020375
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-04-25 Cont ID  
Sent By pvalenti Date 2019-04-25 Time 16:35 Rev Time 0.00
Received By pvalenti Date 2019-04-25 Time 16:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-04-10 Cont ID  
Sent By pvalenti Date 2019-04-10 Time 12:58 Rev Time 0.00
Received By pvalenti Date 2019-04-10 Time 07:02 Sent To  
Notes
2019-04-10 13:56:18***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND BUILDING REVIEW DENIED:
  
 1. FBC B 107.2.1 PLEASE CONFIRM STATUS OF FIRE
 SPRINKLERS.
 2. OK
 3. OK
 4.A. FBC B 1609.1.2, & 1609.6.4.4.1 PLEASE SUBMIT THE
 PRODUCT APPROVALS FOR WINDOWS AND PRE-ENGINEERED A/C
 STANDS.
 4.B. WPB AMENDMENTS 107.3.4 WHEN SUBMITTING, PLEASE
 PROVIDE REVIEW STAMP AND SIGNATURE BY THE DESIGNER OF
 RECORD ON PRODUCT APPROVALS.
 5. FBC B 107.2.1 PLEASE PROVIDE WELDING INFORMATION (ON
 PLAN) FOR THE ROOF TOP STAND TO THE ROOF FRAMING
 MEMBERS; AND IN ADDITION TO THE REQUIRED WELDING
 INFORMATION ON PLANS PLEASE PROVIDE A (PROVISO REQUIRED
 AT TIME OF INSPECTION) WELD PROCEDURE SPECIFICATION AND
 WELDER
 PERFORMANCE QUALIFICATION RECORD AS PER AWS D1.1 CLAUSE
 3.1 AND 4.15.
 6. FBC B 107.2.1/FBC M 306.5 PLEASE SHOW DETAILS FOR
 ROOF ACCESS, INCLUDING MATERIAL, CONNECTIONS, AND
 LOCATIONS.
 7. WHEN RESUBMITTING PLANS, PLEASE INDICATE THE
 REVISION AND REMOVE ANY VOIDED SHEETS AND REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-27 Cont ID  
Sent By jwitmer Date 2019-02-27 Time 08:01 Rev Time 0.00
Received By jwitmer Date 2019-02-26 Time 14:01 Sent To  
Notes
2019-02-27 08:01:362017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020375
 ADD: 5786 PREMIER PARK DR.
 CONT: DUKE INDIANA CONSTRUCTION
 TEL: 954-453-5660
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 27/ 2019
 ACTION: DENIED
  
 1) THE ORIGINAL PERMIT FOR THIS TENANT SPACE 10040216
 AND THE APPLIED FOR PERMIT / PLANS INDICATE THAT THIS
 IS A FIRE SPRINKLERED BUILDING. LESS THAN 50 HEADS A
 FIRE SPRINKLER CONTRACTOR CAN DESIGN THE ADDITIONAL
 HEADS IN AN EXISTING FIRE SPRINKLER SYSTEM. A
 CONTRACTOR I, CONTRACTOR II OR CONTRACTOR IV, CERTIFIED
 UNDER SECTION 633.521, FLORIDA STATUTE MAY DESIGN A
 FIRE SPRINKLER SYSTEM OF 49 OR FEWER HEADS AND MAY
 DESIGN THE ALTERATION OF AN EXISTING FIRE SPRINKLER
 SYSTEM.
  
 2) NOTICE: SHEET A2.1 DOES INDICATE THERE WILL BE
 FUTURE RACK STORAGE UNDER A SEPARATE PERMIT. NOTING
 THAT RACK STORAGE IS NOT PART OF THIS PERMIT.
  
 3) SHEET A-2 DOES INDICATE THE EXTERIOR CONCRETE WALL
 WILL BE CUT AND SEE SHEET S-1. PLEASE ALSO REVIEW SHEET
 M-1, THE PLAN SHOWS A SECOND 12 X 12 INCH PENETRATION
 OF THE EXTERIOR WALL FOR INTAKE OF OUTSIDE AIR. SHEET
 S-1 DOES NOT INDICATE THE 2ND PENETRATION AND WILL NEED
 TO UPDATE THE PLANS. 107.2.1.2 ADDITIONAL INFORMATION
 IS REQUIRED. PLEASE ALSO INCLUDE THE PRESSURES FOR THE
 INTAKE LOUVER.
  
 4A) PLEASE PROVIDE COMPLIANCE WITH: 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS
 (C) WALL LOUVERS
 (G) PRE-ENGINEERED A/C STANDS
  
 4B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) SHEETS E-1 & M-1 BOTH SHOW A NEW ROOF TOP A/C
 COMPRESSOR, SHEET M2 HAS CODE LANGUAGE FROM THE 2007
 FBC-B ABOUT ROOF MOUNTED A/C UNITS AND THE MINIMUM
 HEIGHT OF THE STANDS LISTING TABLE 1509.7. PLEASE
 UPDATE THE PLANS TO THE 2017 FBC-B TABLE 1510.10. IF
 THE PIPE STAND DETAIL FOUND ON M2 IS TO BE USED THEN
 PLEASE PROVIDE THE WELD INFORMATION MISSING FROM THE
 PLANS AS WELL TO WHAT WIND SPEED DESIGN WAS USED FOR
 THE ANCHORING OF THE ROOF TOP STAND TO THE ROOF FRAMING
 MEMBERS AND THE ROOF TOP UNIT TO THE STAND.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 WELDED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2) QUALIFICATIONS OF WELDING PERSONAL
  
 6) THE ARCHITECTURAL SHEETS DOES NOT SHOW A ROOF PLAN
 BUT THE MECHANICAL SHEET M-1 DOES SHOW THE NEW ROOF TOP
 COMPRESSOR. THE PLANS DO NOT INDICATE HOW YOU ARE TO
 GAIN ACCESS ONTO THE ROOF. SHOW COMPLIANCE WITH:
 2017 FBC-M 306.5 EQUIPMENT AND APPLIANCES ON ROOFS OR
 ELEVATED STRUCTURES. WHERE EQUIPMENT REQUIRING ACCESS
 OR APPLIANCES ARE LOCATED ON AN ELEVATED STRUCTURE OR
 THE ROOF OF A BUILDING SUCH THAT PERSONNEL WILL HAVE TO
 CLIMB HIGHER THAN 16 FEET (4877 MM) ABOVE GRADE TO
 ACCESS SUCH EQUIPMENT OR APPLIANCES, AN INTERIOR OR
 EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED. SUCH ACCESS
 SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER
 THAN 30 INCHES (762 MM) IN HEIGHT OR WALKING ON ROOFS
 HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN 12
 UNITS HORIZONTAL (33-PERCENT SLOPE). SUCH ACCESS SHALL
 NOT REQUIRE THE USE OF PORTABLE LADDERS. WHERE ACCESS
 INVOLVES CLIMBING OVER PARAPET WALLS, THE HEIGHT SHALL
 BE MEASURED TO THE TOP OF THE PARAPET WALL.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-11 Cont ID  
Sent By jpearson Date 2019-04-11 Time 11:21 Rev Time 0.00
Received By jpearson Date 2019-04-11 Time 10:58 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-03-07 Cont ID  
Sent By jpearson Date 2019-03-07 Time 12:50 Rev Time 0.00
Received By jpearson Date 2019-03-06 Time 06:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-03-29 Cont ID  
Sent By pleduc Date 2019-03-29 Time   Rev Time 0.00
Received By pleduc Date 2019-03-29 Time 11:32 Sent To  
Notes
2019-03-29 11:33:09THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) SHEET A 2.1 - THERE IS AN INDICATION OF FUTURE
 RACKING.
  
 ANY RACK INSTALLATION SHALL BE UNDER SEPARATE SHOP
 DRAWINGS TO INCLUDE, HEIGHT, RACK MANUFACTURER'S SPEC
 SHEETS, STORAGE COMMODITY TYPE, WRAPPINGS, PALLETS,
 SHELVING, FASTENER'S TO THE SLAB. AND A FIRE SPRINKLER
 PRTOTECTION REVIEW BY A CERTIFIED FIRE SPRINKLER
 CONTRACTOR OR LICENSED ENGINEER.
  
 RACK SPRINKLERS MAY BE REQUIRED.
  
  
  
 2) SHEET E 1 - NEW CEILING FANS INSTALLATIONS ARE
 INDICATED.
  
 NEW CEILING FANS SHALL NOT ONSTRUCT FIRE SPRINKLERS.
  
 PLEASE CONSULT A FIRE SPRINKLER CONTRACTOR PRIOR AND
 AFTER INSTALLTION TO ENSURE COMPLIANCE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-02-20 Cont ID  
Sent By pleduc Date 2019-02-20 Time   Rev Time 0.00
Received By pleduc Date 2019-02-20 Time 13:43 Sent To  
Notes
2019-02-20 13:49:10THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) SHEET A 2.1 - THERE IS AN INDICATION OF FUTURE
 RACKING.
  
 ANY RACK INSTALLATION SHALL BE UNDER SEPARATE SHOP
 DRAWINGS TO INCLUDE, HEIGHT, RACK MANUFACTURER'S SPEC
 SHEETS, STORAGE COMMODITY TYPE, WRAPPINGS, PALLETS,
 SHELVING, FASTENER'S TO THE SLAB. AND A FIRE SPRINKLER
 PRTOTECTION REVIEW BY A CERTIFIED FIRE SPRINKLER
 CONTRACTOR OR LICENSED ENGINEER.
  
 RACK SPRINKLERS MAY BE REQUIRED.
  
  
  
 2) SHEET E 1 - NEW CEILING FANS INSTALLATIONS ARE
 INDICATED.
  
 NEW CEILING FANS SHALL NOT ONSTRUCT FIRE SPRINKLERS.
  
 PLEASE CONSULT A FIRE SPRINKLER CONTRACTOR PRIOR AND
 AFTER INSTALLTION TO ENSURE COMPLIANCE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-04-25 Cont ID  
Sent By pvalenti Date 2019-04-25 Time 16:36 Rev Time 0.00
Received By pvalenti Date 2019-04-18 Time 14:08 Sent To  
Notes
2019-04-19 14:09:10RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-04-11 Time   Rev Time 0.00
Received By lmarchan Date 2019-03-27 Time 15:11 Sent To  
Notes
2019-03-28 15:11:13B13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-19 Cont ID  
Sent By cpuell Date 2019-03-19 Time 11:59 Rev Time 0.00
Received By cpuell Date 2019-02-14 Time 11:43 Sent To  
Notes
2019-02-15 11:44:05B34

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-02-27 Cont ID  
Sent By jwitmer Date 2019-02-27 Time 07:11 Rev Time 0.00
Received By jwitmer Date 2019-02-27 Time 07:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-04-10 Cont ID  
Sent By ccole Date 2019-04-10 Time 16:57 Rev Time 0.00
Received By ccole Date 2019-04-10 Time 16:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-03-12 Cont ID  
Sent By ccole Date 2019-03-12 Time 18:14 Rev Time 0.00
Received By ccole Date 2019-03-12 Time 17:56 Sent To  
Notes
2019-03-12 18:22:171ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19020375
 3/12/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW OFFICE AC SYSTEM- SECTION C403.2.1 FBC EC.
  
 2) SUBMIT ENERGY CALCULATIONS FOR THE NEW CONDITIONED
 ENCLOSED SPACE- SECTION C503.2 FBC EC. REFER TO SECTION
 C402.2.2: INSULATION INSTALLED ON THE SUSPENDED CEILING
 SHALL BNOT BE CONSIDERED PART OF THE MINIMUM THERMAL
 RESISTANCE OF THE ROOF INSULATION.
  
 3) SUBMIT FL. PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S
 FOR THE ROOF STAND AND LOUVER.
  
 4) M-1: PROVIDE AN AUTOMATICALLY CONTROLLED SHUTOFF
 DAMPER FOR THE O/A INTAKE DUCT- SECTION C403.2.4.3
 FBC-17 EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-04-25 Cont ID  
Sent By eschneid Date 2019-04-25 Time 15:23 Rev Time 0.25
Received By eschneid Date 2019-04-25 Time 14:12 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2019-04-09 Cont ID  
Sent By eschneid Date 2019-04-09 Time 12:28 Rev Time 0.25
Received By eschneid Date 2019-04-08 Time 17:13 Sent To  
Notes
2019-04-09 12:29:36FAILED - THIS WILL NOT COUNT AS A ZONING REVIEW CYCLE.
  
 1) REPEAT COMMENT: ORDINANCE NO. 3987-06, DEVELOPMENT
 REGULATIONS FOR THE PREMIER PARK OF COMMERCE CPD
 REQUIRE THE FOLLOWING ITEMS TO BE SUBMITTED AS PART OF
 THIS PERMIT APPLICATION:
  
 A. A USE CHART SHALL BE SUBMITTED TO THE PLANNING AND
 ZONING AND CONSTRUCTION SERVICES DEPARTMENTS CONCURRENT
 WITH ALL BUILDING PERMIT AND/OR OCCUPATIONAL LICENSE
 APPLICATIONS STATING THE SQUARE FOOTAGE DEVOTED TO THE
 USES WITHIN BUILDINGS 1, 2 AND 3. THE SPECIFIC SQUARE
 FOOTAGE USE WITHIN EACH BUILDING MAY NOT EXCEED THE
 ALLOWANCES OUTLINED IN THE BUILDING USE SQUARE FOOTAGE
 TABLE, UNLESS THE PROPERTY OWNER PROVIDES A TRAFFIC
 EQUIVALENCY STATEMENT, PREPARED BY A LICENSED TRAFFIC
 ENGINEER, DEMONSTRATING THAT THE APPROVED TRAFFIC
 CONCURRENCY FOR THE PROJECT IS NOT EXCEEDED.
  
 B. A TRAFFIC STATEMENT, PREPARED BY A LICENSED TRAFFIC
 ENGINEER, SHALL BE SUBMITTED TO THE PLANNING AND ZONING
 AND CONSTRUCTION SERVICES DEPARTMENTS CONCURRENT WITH
 ALL BUILDING PERMIT APPLICATIONS OUTLINING THE NUMBER
 OF DAILY TRIPS, AM TRIPS AND PM TRIPS GENERATED FOR
 EACH USE AND ITS SQUARE FOOTAGE FOR EACH BUILDING. THE
 TRAFFIC STATEMENT SHALL INCLUDE THE TRIPS ASSOCIATED
 WITH THE SPECIFIC USE AND A CUMULATIVE TABLE FOR ALL OF
 THE USES APPROVED IN THE PREMIER PARK OF COMMERCE CPD.
  
 2) THE PLANS THEMSELVES MEET ZONING REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-03-19 Cont ID  
Sent By eschneid Date 2019-03-19 Time 09:52 Rev Time 0.25
Received By eschneid Date 2019-03-19 Time 09:38 Sent To PC
Notes
2019-03-19 11:10:47FAILED
  
 1) ORDINANCE NO. 3987-06, DEVELOPMENT REGULATIONS FOR
 THE PREMIER PARK OF COMMERCE CPD REQUIRE THE FOLLOWING
 ITEMS TO BE SUBMITTED AS PART OF THIS PERMIT
 APPLICATION:
  
 A. A USE CHART SHALL BE SUBMITTED TO THE PLANNING AND
 ZONING AND CONSTRUCTION SERVICES DEPARTMENTS CONCURRENT
 WITH ALL BUILDING PERMIT AND/OR OCCUPATIONAL LICENSE
 APPLICATIONS STATING THE SQUARE FOOTAGE DEVOTED TO THE
 USES WITHIN BUILDINGS 1, 2 AND 3. THE SPECIFIC SQUARE
 FOOTAGE USE WITHIN EACH BUILDING MAY NOT EXCEED THE
 ALLOWANCES OUTLINED IN THE BUILDING USE SQUARE FOOTAGE
 TABLE, UNLESS THE PROPERTY OWNER PROVIDES A TRAFFIC
 EQUIVALENCY STATEMENT, PREPARED BY A LICENSED TRAFFIC
 ENGINEER, DEMONSTRATING THAT THE APPROVED TRAFFIC
 CONCURRENCY FOR THE PROJECT IS NOT EXCEEDED.
  
 B. A TRAFFIC STATEMENT, PREPARED BY A LICENSED TRAFFIC
 ENGINEER, SHALL BE SUBMITTED TO THE PLANNING AND ZONING
 AND CONSTRUCTION SERVICES DEPARTMENTS CONCURRENT WITH
 ALL BUILDING PERMIT APPLICATIONS OUTLINING THE NUMBER
 OF DAILY TRIPS, AM TRIPS AND PM TRIPS GENERATED FOR
 EACH USE AND ITS SQUARE FOOTAGE FOR EACH BUILDING. THE
 TRAFFIC STATEMENT SHALL INCLUDE THE TRIPS ASSOCIATED
 WITH THE SPECIFIC USE AND A CUMULATIVE TABLE FOR ALL OF
 THE USES APPROVED IN THE PREMIER PARK OF COMMERCE CPD.
  
 2) THE PLANS THEMSELVES MEET ZONING REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  