| 2019-02-11 18:40:54 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- PERMIT APPLICATION INDICATES THAT THERE IS A FLAT |
| | ROOF AREA TO BE RE-ROOFED ALSO. THERE WAS NO |
| | INFORMATION SUBMITTED FOR THE FLAT ROOF. PROVIDE |
| | PRODUCT APPROVAL (2 COPIES) FOR FLAT ROOF AND CLEARLY |
| | MARK WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED |
| | TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| | R301.1 FBC-RESIDENTIAL. NOTE: IF THE SELECTED ASSEMBLY |
| | DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, |
| | THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE |
| | REQUIRED. |
| | FAC 61G20-3.001. |
| | |
| | 2- SPECIFY SHINGLES ROOF PITCH AS REQUIRED BY CITY |
| | POLICY FOR ALL ROOFING PERMITS TO VERIFY COMPLIANCE |
| | WITH SEC. R905.2.2 FBC-RESIDENTIAL. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |