Plan Review Details - Permit 19020363
Plan Review Stops For Permit 19020363
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-08-27 Cont ID  
Sent By cthroop Date 2019-08-27 Time 12:16 Rev Time 0.00
Received By cthroop Date 2019-08-27 Time 11:27 Sent To  
Notes
2019-12-23 08:51:12UPDATED FORM BOARD SURVEY DATED 12/22/2019. NO
 ENCROACHMENT INTO FLOOD ZONE. NO NFIP REVIEW REQUIRED.
 CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-08-09 Cont ID  
Sent By cthroop Date 2019-08-09 Time 10:20 Rev Time 0.00
Received By cthroop Date 2019-08-08 Time 08:32 Sent To  
Notes
2019-08-09 10:24:55BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE WINDOW AND DOOR SCHEDULE. INCLUDE ROUGH
 OPENINGS AND DESIGN PRESSURES OF EACH OPENING.
 FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
 R301.2.1 WIND DESIGN CRITERIA.
  
 2. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND DOORS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-08 Cont ID  
Sent By jgomez Date 2019-03-08 Time 12:20 Rev Time 0.00
Received By jgomez Date 2019-03-07 Time 13:25 Sent To  
Notes
2019-03-08 12:21:34RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PLANS SHOW EXISTING KITCHEN, FAMILY ROOM AND DINING
 ROOM AREA. THIS AREA USED TO BE THE GARAGE AREA. THERE
 ARE NO PERMITS SHOWING THAT CONVERSION WAS ALLOWED.
 ALSO, PLANS SHOW THREE EXISTING BATHROOMS. ORIGINAL
 HOUSE HAD ONLY ONE BATHROOM. THERE ARE NO PERMITS FOR
 THE ADDITIONAL BATHROOMS. CLARIFY HOW CAN YOU HAVE
 THREE BATHROOMS IF THERE IS ONLY ONE BEDROOM?. THERE IS
 AN OPEN PERMIT APPLICATION ( PERMIT #18120043) THAT
 INCLUDES WORK TO LEGALIZE CONVERSION OF GARAGE TO
 LIVING AREA. THIS PERMIT HAVE NOT BEEN ISSUED AND IS
 NOT CLEAR IF CONTRACTOR IS GOING TO ADDRESS THE
 COMMENTS TO GET THAT PERMIT. SINCE CONTRACTOR FOR THAT
 PERMIT IS THE SAME CONTRACTOR APPLYING FOR THE
 ADDITION, THEN IT MAY BE POSSIBLE TO COMBINE THE TWO
 PERMITS INTO THIS ONE. THIS WAY THAT PERMIT CAN BE
 REVOKED AND THERE WILL BE NO OUTSTANDING PERMIT ON THIS
 PROPERTY. CONTRACTOR TO ADVICE IF HE WANTS TO ADD THAT
 SCOPE OF WORK TO THIS PERMIT. NOTE: PLANS NEED TO BE
 CORRECTED ACCORDINGLY SHOWING ALL THE EXISTING
 ALTERATIONS THAT WERE DONE WITHOUT PERMIT AS NEW AND
 NOT AS EXISTING. SEC. 107.2.1 CITY AMENDMENTS.
  
 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. 1106 FBC-EXISTING BUILDING. AND SEC. R101.4.2
 AND R101.5 FBC-ENERGY CONSERVATION.
  
 3- PROVIDE SOIL TEST REPORT (2 COPIES) AS REQUIRED BY
 SEC. R401.4 FBC-RESIDENTIAL.
  
 4- ACCORDING TO NEW FEMA FLOOD MAPS MAPS EFFECTIVE
 OCTOBER 5, 2017 THIS PROPERTY IS LOCATED IN FLOOD ZONE
 AE. CURRENTLY, THE EXISTING BUILDING IS NOT TOUCHING
 THE CONTOUR LINE OF THE FLOOD ZONE AE. BUT PROPOSED
 ADDITION MAY BE TOUCHING THIS FLOOD ZONE AE. PROVIDE
 CURRENT SURVEY (TWO COPIES)SHOWING THE PROPOSED
 ADDITION AND LOCATION OF THE FLOOD ZONE AE CONTOUR LINE
 TO VERIFY IF PROPOSED ADDITION AND EXISTING HOUSE NEED
 TO COMPLY WITH CURRENT REQUIREMENTS FOR BUILDINGS
 LOCATED IN FLOOD ZONES. NOTE: BUILDINGS ON FLOOD ZONES
 NEED TO HAVE A FINISH FLOOR ELEVATION 2' ABOVE THE BASE
 FLOOD ELEVATION.
 CITY ORDINANCE 4729-17 SEC. 18-34.
  
 5- BEDROOM EGRESS WINDOWS DON'T COMPLY WITH SEC.
 R310.2.1 FBC-RESIDENTIAL. WINDOW #1 SHOWS A 4'-3" HIGH
 SINGLE HUNG WINDOW. THIS WINDOW DOESN'T PROVIDE THE
 MIN. CLEAR HEIGHT OPENING OF 24". REVISE AS REQUIRED.
  
 6- IT LOOKS LIKE NEW ENTRY DOORS DON'T COMPLY WITH
 EGRESS SEC. R11.2 FBC-RESIDENTIAL. NEED AT LAST ONE
 DOOR THAT PROVIDES MIN. 32" CLEAR OPENING. REVISE SIZE
 OF DOORS.
  
 7- A) DESIGN PARAMETERS ON SHEET A1 SPECIFIED THAT
 BUILDING IS LOCATED IN EXPOSURE "D". WINDOWS DESIGN
 PRESSURES SHOWN ON THE EXTERIOR ELEVATIONS ON SHEET A2
 DON'T CORRESPOND TO EXPOSURE "D". REVISE AS REQUIRED.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 B) PROVIDE THE DESIGN PRESSURES FOR EXTERIOR DOORS.
 SEC. R301.2.1 FBC-RESIDENTIAL. ONLY THE DESIGN
 PRESSURES FOR WINDOWS WERE GIVEN.
  
 8- REVISE THE MINIMUM COMPRESSIVE STRENGTH OF CONCRETE
 SLAB SPECIFIED ON THE SECTION A ON SHEET A1 AND
 FOUNDATION PLAN ON SHEET A3. 2,000PSI IS TOO LOW. SEE
 SEC. R402.2 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 9- SPECIFY ROOF CROSS VENTILATION AS REQUIRED BY SEC.
 R806 FBC-RESIDENTIAL. SPECIFY SIZE AND LOCATION OF
 VENTS. SECTION A ON SHEET A1 DOESN'T PROVIDE THIS
 INFORMATION.
  
 10- ROOF PITCH OF 2:12 TO LESS THAN 4:12 REQUIRES TWO
 LAYERS OF UNDERLAYMENT AS REQUIRED BY SEC. R905.1.1
 FBC-RESIDENTIAL. PROVIDE SPECIFICATIONS ON PLANS.
  
 11- SPECIFY ATTIC ACCESS SIZE AND LOCATION FOR THE
 PROPOSED ADDITION. SEC. R307.1 FBC-RESIDENTIAL.
  
 12-SHOW ON PLANS CARBON MONOXIDE ALARMS BY ALL THE
 BEDROOMS AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
  
 13- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) INSWING ENTRY DOORS WITH TRANSOM ABOVE AS SHOWN ON
 PLANS.
  
 B)SINGLE HUNG WINDOWS.
  
 C) WINDOW MULLIONS AS SHOWN ON PLANS. REQUIRED: CLEARLY
 SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE
 WITH THE CALCULATED DESIGN PRESSURES.
  
 D) ROOF FINISH MATERIAL.
  
 E) PRECAST LINTELS AS SHOWN ON PLANS.
  
 14- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 15- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $126,363. THE
 PERMIT FEE BALANCE IS $2828.90
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-08-27 Cont ID  
Sent By cthroop Date 2019-08-27 Time 12:17 Rev Time 0.00
Received By cthroop Date 2019-08-27 Time 11:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-08-05 Cont ID  
Sent By jleahy Date 2019-08-05 Time 14:37 Rev Time 0.00
Received By jleahy Date 2019-08-05 Time 14:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-01 Cont ID  
Sent By jpearson Date 2019-03-01 Time 10:42 Rev Time 0.00
Received By jpearson Date 2019-03-01 Time 08:30 Sent To  
Notes
2019-03-01 10:42:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN SHOWS EXISTING RENOVATION AND NEW ADDITION
 AREAS. PLEASE CLARIFY. IS THIS AN EXISTING RENOVATION
 THAT IS BEING REVISED, OR IS THIS A NEW PERMIT FOR AN
 ADDITION? THE PLAN REVIEWER DOES NOT SEE AN EXISTING
 RENOVATION PERMIT IN OUR SYSTEM. WPB FBC 107.2.1
 2. PROVIDE RISER DIAGRAM OF EXISTING AND PROPOSED
 SERVICE, SHOWING ALL DETAILS OF SERVICE EQUIPMENT,
 UNDERGROUND OR OVERHEAD SERVICE, WIRE AND BREAKER SIZES
 FOR SERVICE AND FEED TO ANY SUB-PANEL(S). SHOW GEC SIZE
 AND SYSTEM, SHOW INTERSYSTEM BONDING TERMINATION POINT.
 NEC 215.5, 230, 250.50, 250.94, 408.30; FBC RE E3706.1,
 E3608.1, E3609.3; WPB FBC 107.2.1
 3. SHOW LOCATION OF ELECTRICAL SERVICE AND PANEL ON
 PLAN. WPB FBC 107.2.1
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 5. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
 6. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
 7. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 8. NOTE 2 STATES THE 2011 NEC AS BASIS FOR DESIGN,
 WHICH IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC
 PREFACE
 9. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 10. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-27 Cont ID  
Sent By cthroop Date 2019-08-27 Time 14:46 Rev Time 0.00
Received By lmarchan Date 2019-08-20 Time 13:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-12 Cont ID  
Sent By lmarchan Date 2019-08-12 Time 10:22 Rev Time 0.00
Received By lmarchan Date 2019-07-17 Time 15:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-11 Cont ID  
Sent By cthroop Date 2019-03-11 Time 12:14 Rev Time 0.00
Received By cthroop Date 2019-02-08 Time 11:21 Sent To  
Notes
2019-03-11 08:08:293/11 TO CT DESK / S.HILL
  
2019-02-11 11:21:24R13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-09-10 Cont ID  
Sent By lmarchan Date 2019-09-10 Time 14:42 Rev Time 0.00
Received By lmarchan Date 2019-08-27 Time 16:35 Sent To  
Notes
2019-09-10 11:49:28RECEIPT MU-2019-0911-106 - $427.67 - PAID
2019-08-27 16:35:508/27/19 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-03-08 Cont ID  
Sent By jgomez Date 2019-03-08 Time 12:22 Rev Time 0.00
Received By jgomez Date 2019-03-08 Time 12:21 Sent To  
Notes
2019-03-08 12:22:33IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-08-27 Cont ID  
Sent By cthroop Date 2019-08-27 Time 12:18 Rev Time 0.00
Received By cthroop Date 2019-08-27 Time 11:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-08-09 Cont ID  
Sent By cthroop Date 2019-08-09 Time 10:13 Rev Time 0.00
Received By cthroop Date 2019-08-08 Time 08:32 Sent To  
Notes
2019-08-09 10:18:01MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE ENERGY SUBMITTAL FOR ADDITION.
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
  
 2. DESIGNER OF RECORD TO SIGN PLAN.
 FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT,
 INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR
 DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
  
 DIGITAL REVIEW
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-03-11 Cont ID  
Sent By cthroop Date 2019-03-11 Time 12:14 Rev Time 0.00
Received By cthroop Date 2019-03-11 Time 09:42 Sent To  
Notes
2019-03-11 12:19:49MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CANNOT DETERMINE IF ADDITION ENCROACHES INTO THE
 SPECIAL FLOOD HAZARD AREA TRANSECTING THE PROPERTY.
 2. PROVIDE SURVEY AND SITE PLAN.
 3. IF ADDITION QUALIFIES STRUCTURE AS A SUBSTANTIAL
 IMPROVEMENT, ALL MECHANICAL EQUIPTMENT AND UTILITIES
 SHALL BE ELEVATED AT OR ABOVE THE DESIGN FLOOD
 ELEVATION.
  
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY.
  
 ADVISORY: RETURN AIR GRILLS SHOULD BE LOCATED ON
 OPPOSITE SIDE OF ROOM THAT SUPPLY AIR IS LOCATED.
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-08-27 Cont ID  
Sent By cthroop Date 2019-08-27 Time 12:16 Rev Time 0.00
Received By cthroop Date 2019-08-27 Time 11:27 Sent To  
Notes
2019-08-27 12:17:29A VIDEO OF THE UNDERSLAB PIPING SHALL BE MADE AND
 PRESENTED TO THE PLUMBING INSPECTOR FOR REVIEW. CT

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-08-06 Cont ID  
Sent By jesmith Date 2019-08-06 Time 15:00 Rev Time 0.00
Received By jesmith Date 2019-08-06 Time 15:00 Sent To  
Notes
2019-08-06 15:00:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 96= STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2NDT REVIEW
 PLUMBING COMMEMTS: DENIED
 1. UPON REVIEW OF THE PLANS UNDER PERMIT #97011131 AND
 19030705, THE FOLLOWING SHALL APPLY:
  
 A. PER WPB FBC 107.2.1, PROVIDE ADDITIONAL
 CLARIFICATION ON PLAN SHEET A1; CLOUD EACH
 NON-PERMITTED RECONFIGURATION AND ADDITION. CLARIFY
 BATH AS BUILT AS ADDED BATH. PROVIDE PLAN SHOWING THE
 EXISTING KITCHEN, LAUNDRY AND BATH CONFIGURATION AND
 LOCATIONS AT THE TIME OF THE ISSUANCE OF PERMIT
 #97011131. SEE PERMIT #97011131 PLAN SHEETS 2 AND 3.
 B. PER WPB FBC 107.2.1, THE GAS TANKLESS WATER HEATER
 SHALL BE SHOWN AND IDENTIFIED ON PLAN SHEET A1.
 C. SEE PLUMBING NOTES ON PLAN SHEET A2; PER WPB FBC
 107.2.1, THE PLUMBING SHALL COMPLY WITH FLORIDA
 RESIDENTIAL BUILDING CODE 2017.
 D. SEE PLUMBING PIPING ON PLAN SHEET A2; PER FBC RES
 P3104.3 AND P3104.4, DRY VENT SHALL CONNECT ABOVE THE
 CENTERLINE OF THE HORIZONTAL DRAIN PIPE AND RISE
 VERTICALLY TO NOT LESS THAN 6? ABOVE THE FLOOD LEVEL
 RIM OF THE HIGHEST FIXTURE BEING VENTED.
 E. IS THE NEW ADDITION TO BE BUILT OVER THE EXISTING
 SANITARY SEWER/BUILDING DRAIN? SHOW LOCATION OF
 EXISTING SANITARY SEWER/BUILDING DRAIN AND WHERE ADDED
 BATH WILL CONNECT INTO THE SAME.
  
 2. AS A PROVISO TO AN APPROVED PERMIT, A VIDEO OF THE
 UNDERSLAB PIPING SHALL BE MADE AND PRESENTED TO THE
 PLUMBING INSPECTOR AT THE FIRST PLUMBING INSPECTION,
 WHICH SHALL BE REVIEWED BY THE CHIEF PLUMBING INSPECTOR
 FOR CODE COMPLIANCE.
 3. SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19020363 936 UPLAND RD
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-07 Cont ID  
Sent By jesmith Date 2019-03-07 Time 16:43 Rev Time 0.00
Received By jesmith Date 2019-03-07 Time 11:07 Sent To  
Notes
2019-03-07 11:08:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW: DENIED
 PLUMBING COMMENTS:
 1. PER WPB FBC 107.2.1, PROVIDE A PLAN SHOWING THE
 EXISTING KITCHEN CONFIGURATION AND THE PROPOSED KITCHEN
 CONFIGURATION OR STATE ON PLAN SHEET A1 "SCOPE OF WORK"
 NOTE 5 THAT THERE IS NO RECONFIGURATION OF SINK AND
 APPLIANCE RELOCATION AND THAT ALL FIXTURES AND
 APPLIANCES REQUIRING WATER AND WASTE CONNECTIONS SHALL
 CONNECT TO EXISTING SUPPLY LINES AND OUTLETS AS DEFINED
 BY WPB FBC 105.2 WORK EXEMPT FROM PERMIT.
 2. WHAT DOES THE TERM EXISTING RENOVATION APPLY TO?
 THERE DOES NOT APPEAR TO HAVE BEEN A PREVIOUS PERMITTED
 RENOVATION ON THIS PROPERTY. PLEASE CLARIFY PER WPB FBC
 107.2.1
 3. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST PLUMBING. WPB FBC 109.3
  
  
 END OF PLUMBING COMMENTS
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2019-08-27 Cont ID  
Sent By cthroop Date 2019-08-27 Time 12:15 Rev Time 0.00
Received By cthroop Date 2019-08-27 Time 11:27 Sent To  
Notes
2019-08-27 12:15:50PROVISO - ROOFING PRODUCT APPROVALS SHALL BE SUBMITTED
 FOR REVIEW PRIOR TO INSTALLATION. CT

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2019-08-09 Cont ID  
Sent By cthroop Date 2019-08-09 Time 10:18 Rev Time 0.00
Received By cthroop Date 2019-08-08 Time 08:32 Sent To  
Notes
2019-08-09 10:20:15BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR PROPOSED ROOFING
 SYSTEM COMPONENTS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-03-08 Cont ID  
Sent By jgomez Date 2019-03-08 Time 12:23 Rev Time 0.00
Received By jgomez Date 2019-03-08 Time 12:22 Sent To  
Notes
2019-03-08 12:23:451- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) ROOF FINISH MATERIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-08-27 Cont ID  
Sent By cthroop Date 2019-08-27 Time 12:16 Rev Time 0.00
Received By cthroop Date 2019-08-27 Time 11:27 Sent To  
Notes
2019-08-26 13:54:298/26/19 DIGITALLY SIGNED COVER SHEET IN "SIGNATURES"
 FOLDER.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-08-09 Cont ID  
Sent By cthroop Date 2019-08-09 Time 10:25 Rev Time 0.00
Received By cthroop Date 2019-08-08 Time 08:32 Sent To  
Notes
2019-08-09 10:27:28BUILDING PLAN REVIEW - DIGITAL SIGNATURES AND SEALS
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTE: ORIGINAL PAPER SUBMITTAL HAS BEEN CHANGED TO
 ELETRONIC SUBMITTAL.
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
  
  
  
2019-08-02 15:28:028/2/19 HARD COPIES OF PLANS LOCATED IN LIBRARY. LEM

Review Stop Z ZONING
Rev No 4 Status P Date 2019-08-28 Cont ID  
Sent By awooten Date 2019-08-28 Time   Rev Time 0.00
Received By awooten Date 2019-08-28 Time   Sent To  
Notes
2019-08-28 14:11:26*********************************************ZONING
 PROVISO*********************************
  
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 THE FOLLOWING
 CONDITIONS SHALL BE ADDRESSED:
  
 1. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN,
 SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW.
  
 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL
 LANDSCAPE INSPECTION.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 2019-08-27 Cont ID  
Sent By awooten Date 2019-08-27 Time   Rev Time 0.00
Received By awooten Date 2019-08-27 Time   Sent To  
Notes
2019-08-27 13:17:40***********************ZONING REVIEW
 FAILED**********************
  
 THE AMENDED PROJECT VALUE TRIGGERS THE LANDSCAPE CODE.
 PLEASE PROVIDE THE FOLLOWING LANDSCAPE REQUIREMENTS.
  
 PROVIDE LANDSCAPING.
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2019-08-12 Cont ID  
Sent By awooten Date 2019-08-12 Time   Rev Time 0.00
Received By awooten Date 2019-08-12 Time   Sent To  
Notes
2019-08-12 10:09:48***********************ZONING REVIEW
 FAILED**********************
  
 THE AMENDED PROJECT VALUE TRIGGERS THE LANDSCAPE CODE.
 PLEASE PROVIDE THE FOLLOWING LANDSCAPE REQUIREMENTS.
  
 PROVIDE LANDSCAPING.
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2019-02-15 Cont ID  
Sent By awooten Date 2019-02-15 Time   Rev Time  
Received By awooten Date 2019-02-15 Time   Sent To  
Notes
2019-02-15 16:33:47*************************************ZONING REVIEW
 FAILED******************************
  
 IS THE FOOTPRINT OF THE EXISTING HOME EXPANDING?
  
 PROVIDE A SURVEY AND SITE PLAN OF PROPERTY SHOWING ALL
 (EXISTING AND NEW) SETBACKS.
  
 ADDITIONAL COMMENTS MAY FOLLOW FURTHER REVIEW.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]