Plan Review Details - Permit 19020344
Plan Review Stops For Permit 19020344
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-15 Cont ID  
Sent By pvalenti Date 2019-02-15 Time 09:38 Rev Time 0.00
Received By pvalenti Date 2019-02-15 Time 09:38 Sent To  
Notes
2019-02-15 09:39:56THE SUBMITTED TEST RESULTS FOR THE CORK UNDERLAYMENT
 ARE OK. APPROVED

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-11 Cont ID  
Sent By pvalenti Date 2019-02-11 Time 17:48 Rev Time 0.00
Received By pvalenti Date 2019-02-11 Time 17:48 Sent To  
Notes
2019-02-11 18:08:20****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVAL IS PENDING:
  
 FBC B 603.1 ITEM 2 EXCEPTION 2; SUBMIT THE FLAME SPREAD
 INDEX SPECIFICATIONS (NOT MORE THAN 200) OR SUBMIT A
 DIFFERENT PRODUCT THAT HAS BEEN TESTED FOR FLAME SPREAD
 PER ASTM E 84 OR UL 723.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-11 Cont ID  
Sent By pvalenti Date 2019-02-11 Time 18:08 Rev Time 0.00
Received By pvalenti Date 2019-02-08 Time 14:20 Sent To  
Notes
2019-02-11 14:20:44REVISION ROUTED TO PVALENTI