Plan Review Details - Permit 19020330
Plan Review Stops For Permit 19020330
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-28 Cont ID  
Sent By jduprey Date 2019-02-28 Time 11:38 Rev Time 0.00
Received By jduprey Date 2019-02-28 Time 10:40 Sent To  
Notes
2019-02-28 11:37:03BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE
 OF WORK. THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. YOU MAY PROVIDE A COPY OF THE
 CONTRACT SIGNED BY THE OWNER OR A LIST OF LABOR,
 MATERIALS AND EQUIPMENT RENTAL TO VERIFY VALUE. CITY OF
 WPB CHAPTER 109.3
  
 2. THE DRAWINGS MUST BE SIGN BY THE ENGINEER RESPOSABLE
 OF THE DESIGN.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
 3. PROVIDE THE STRUCTURAL CONNECTION DETAIL BETWEEN THE
 6"X6" COLUMNS AND WOOD JOISTS. FBC 107
  
 4. THE FOUNDATION DEPTH WAS NOT SPECIFIED. PER FBC
 1809.4 THE MINIMUN DEPTH OF FOOTINGS BELOW THE
 UNDISTURBED GROUND SURFACE SHALL BE 12 INCHES.
  
 5. THE STAIRWAYS DIMENSIONS AND HANDRAILS MUST MEET THE
 FBC R311.7. PLEASE PROVIDE DETAILS.
  
 6. THE DRAWINGS NOTES ARE REFERENCE THE "STANDARD
 BUILDING CODE", PLEASE REVISE DESIGN AND NOTES TO MEET
 THE CURRENT CODES MINIMUM STANDARDS.
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-28 Cont ID  
Sent By jduprey Date 2019-02-28 Time 11:38 Rev Time 0.00
Received By jduprey Date 2019-02-07 Time 14:24 Sent To  
Notes
2019-02-13 16:51:38ROUTED FROM ZONING TO PERMIT LIBRARIAN 2/14/2019 EL
2019-02-08 14:24:44ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status F Date 2019-02-13 Cont ID  
Sent By elevesqu Date 2019-02-13 Time 16:51 Rev Time 0.00
Received By elevesqu Date 2019-02-13 Time 16:49 Sent To B
Notes
2019-02-13 16:51:21PLEASE PROVIDE SURVEY OF PROPERTY .
  
 STAFF CANNOT SEE LOCATION OF STAIRS FROM AERIAL
 IMAGERY. ARE THESE NEW STAIRS OR REPLACING EXISTING
 STAIRS? PLEASE CLARIFY.
  
 PLEASE CLARIFY WHAT IS CONSIDERED "FRONT" ELEVATION AS
 FRONT OF HOUSE AT 425 8TH STREET DOES NOT APPEAR TO
 HAVE A DOORWAY ON THE SECOND FLOOR.
  
 PLEASE PROVIDE SITE PICTURES, THESE MAY HELP WITH
 CLARIFICATION.
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]