Plan Review Details - Permit 19020311
Plan Review Stops For Permit 19020311
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-02-27 Cont ID  
Sent By jduprey Date 2019-02-27 Time 13:46 Rev Time 0.00
Received By jduprey Date 2019-02-27 Time 13:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-15 Cont ID  
Sent By jpearson Date 2019-04-15 Time 13:30 Rev Time 0.00
Received By jpearson Date 2019-04-15 Time 13:07 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-23 Cont ID  
Sent By fgiaquin Date 2019-03-23 Time 10:24 Rev Time 0.00
Received By fgiaquin Date 2019-03-23 Time 09:59 Sent To I
Notes
2019-03-23 10:24:11ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.PROVIDE ACCURATE LOAD CALCULATION OF EXISTING LOADS
 AND ANY NEW ADDITIONAL LOADS ( NEW EM LIGHT CIRCUIT).
 NEC 220. FBC 107.2.1
  
 INFORMATIONAL NOTE: L.E.D. LIGHING LOADS ARE CALCULATED
 BY AMPERAGE DRAWN, NOT WATTS. PLEASE SEE NEC 220.18B
  
 2. SIGNATURE AND SEAL FROM DESIGN PROFESSIONAL ON
 ELECTRICAL DRAWINGS ARE COPIES. COPIES OF SIGNATURES
 ARE NOT CONSIDERED TO BE SIGNED AND SEALED PER FLORIDA
 STATUTES. PLEASE SEE REQUIREMENTS BELOW FOR SIGNATURE
 AND SEALS.
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  
 AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED
 DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A
 WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART
 OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO
 PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT
 THE SIGNATURE IS NOT MADE ILLEGIBLE.
 CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN
 USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN
 EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-04-08 Cont ID  
Sent By pleduc Date 2019-04-08 Time   Rev Time 0.00
Received By pleduc Date 2019-04-08 Time 14:45 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-03-21 Cont ID  
Sent By pleduc Date 2019-03-21 Time   Rev Time 0.00
Received By pleduc Date 2019-03-21 Time 15:05 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-02-12 Cont ID  
Sent By fstal Date 2019-02-12 Time   Rev Time 0.00
Received By pleduc Date 2019-02-12 Time   Sent To B
Notes
2019-02-12 16:51:56FFPC 1-1.14,2015 PLAN REVIEW:
 1.14.1 WHERE REQUIRED BY THE AHJ FOR NEW CONSTRUCTION,
 MODIFICATION, OR REHABILITATION, CONSTRUCTION DOCUMENTS
 AND SHOP DRAWINGS SHALL BE SUBMITTED, REVIEWED, AND
 APPROVED PRIOR
 TO THE START OF SUCH WORK AS PROVIDED IN SECTION 1.14.
 1.14.2 THE APPLICANT SHALL BE RESPONSIBLE TO ENSURE
 THAT THE FOLLOWING CONDITIONS ARE MET:
 (1) THE CONSTRUCTION DOCUMENTS INCLUDE ALL OF THE FIRE
 PROTECTION REQUIREMENTS.
 (2) THE SHOP DRAWINGS ARE CORRECT AND IN COMPLIANCE
 WITH THE APPLICABLE CODES AND STANDARDS.
 (3) THE CONTRACTOR MAINTAINS AN APPROVED SET OF
 CONSTRUCTION
 DOCUMENTS ON SITE.
  
 PROVIDE THE FOLLOWINGS:
 A.LIST THE TYPE OF COMMODITIES THAT WOULD BE STORED IN
 THE RACKS.
 B.HOW WOULD THE COMMODITIES BE PACKAGED- ON WOOD ARE
 PLASTIC PALLETS. ENCAPSULATED WITH PLASTIC WRAP.
 C.THE BUILDING HAS A FIRE SPRINKLER SYSTEM. FIRE
 SPRINKLER CONTRACTOR SHALL PROVIDE A LETTER STATING
 THAT THE FIRE PROTECTION SYSTEM WILL PROTECT THE
 STORAGE HAZARD PER FFPC 2015 AND NFPA 13. THE CODE MAY
 REQUIRE ADDITIONAL PROTECTION IN THE RACKS. IF SO THE
 CONTRACTOR SHALL SUBMIT FIRE PROTECTION DRAWINGS TO THE
 BUILDING DEPARTMENT FOR APPROVAL.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-04-15 Time   Rev Time 0.00
Received By lmarchan Date 2019-04-02 Time 15:25 Sent To  
Notes
2019-04-03 15:25:14RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-23 Cont ID  
Sent By fgiaquin Date 2019-03-23 Time 10:24 Rev Time 0.00
Received By fgiaquin Date 2019-03-18 Time 14:08 Sent To  
Notes
2019-03-19 14:08:55RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-27 Cont ID  
Sent By jduprey Date 2019-02-27 Time 13:46 Rev Time 0.00
Received By jduprey Date 2019-02-07 Time 14:34 Sent To  
Notes
2019-02-08 14:34:13ROUTED TO FIRE INBOX