 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PLUMBING RISER PLAN SHOWS SHOWER AND TOILET
 COMPARTMENT IN REVERSE LOCATION THAN INDICATED ON
 FRAMING PLAN.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 2. EXHAUST FAN REQUIRED
 R303.3BATHROOMS.
 BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR
 ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN
 WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.3 M2),
 ONE-HALF OF WHICH MUST BE OPENABLE.
 EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE
 ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE
 PROVIDED. THE MINIMUM LOCAL EXHAUST RATES SHALL BE
 DETERMINED IN ACCORDANCE WITH SECTION M1507. EXHAUST
 AIR FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE
 OUTDOORS.
  
 3. R702.4.2 BACKER BOARDS.
 MATERIALS USED AS BACKERS FOR WALL TILE IN TUB AND
 SHOWER AREAS AND WALL PANELS IN SHOWER AREAS SHALL BE
 OF MATERIALS LISTED IN TABLE R702.4.2, AND INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER?S RECOMMENDATIONS.
  
 4. R307.2 BATHTUB AND SHOWER SPACES.
 BATHTUB AND SHOWER FLOORS AND WALLS ABOVE BATHTUBS WITH
 INSTALLED SHOWER HEADS AND IN SHOWER COMPARTMENTS SHALL
 BE FINISHED WITH A NONABSORBENT SURFACE. SUCH WALL
 SURFACES SHALL EXTEND TO A HEIGHT OF NOT LESS THAN 6
 FEET (1829 MM) ABOVE THE FLOOR.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-25 Cont ID  
Sent By jpearson Date 2019-02-25 Time 11:15 Rev Time 0.00
Received By jpearson Date 2019-02-25 Time 10:50 Sent To  
Notes
2019-02-25 11:15:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. WPB FBC 107.2.1, 107.3.5;
 FS 471, 481.229
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-26 Cont ID  
Sent By cthroop Date 2019-02-26 Time 16:31 Rev Time 0.00
Received By cthroop Date 2019-02-07 Time 14:30 Sent To  
Notes
2019-02-08 14:30:09R08

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-02-26 Cont ID  
Sent By jesmith Date 2019-02-26 Time 14:47 Rev Time 0.00
Received By jesmith Date 2019-02-26 Time 14:36 Sent To  
Notes
2019-02-26 14:47:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW: DENIED
 PLUMBING COMMENTS
 1. PROVIDE A CODE COMPLIANT SANITARY RISER DIAGRAM
 SHOWING SIZED BUILDING DRAIN, FIXTURE DRAINS, TRAPS AND
 VENTS PER WPB FBC 107.3.5.3(12).
 2. PROVIDE A NORTH ORIENTATION ON FLOOR PLANS PER WPB
 FBC 107.2.1.
 3. THERE SEEMS TO BE A DISCREPENCY IN THE PATHROOM
 LAYOUT AS TO WHICH END HAS THE TOILET AND WHICH END HAS
 THE SHOWER. PLEASE CLARIFY.
 4. PLEASE NOTE THAT IF YOUR NEW HOT WATER PIPING FROM
 THE EXISTING WATER HEATER EXCEEDS 50' THA,T PER FBC RES
 P2601.1 AND FBC PL 607.2 YOU WILL BE REQUIRED TO
 INSTALL A HOT WATER PUMPED RECIRC LINE OR HEAT TRACING
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715