| 2019-02-12 11:01:06 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: |
| | PLAN REVIEW FEES WERE NOT PAID. NEED TO PAY PLAN REVIEW |
| | FEES PRIOR TO RE-SUBMITTAL. |
| | |
| | |
| | 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL9487-R5 |
| | SUBMITTED. SELECTED SYSTEM W-13 DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES. NEED TO PROVIDE PRODUCT |
| | APPROVAL THAT MEETS THE DESIGN PRESSURES FOR ALL ROOF |
| | ZONES BASED ON THE BUILDING HEIGHT AND BUILDING |
| | EXPOSURE. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 2- PROVIDE COMPLETE PRODUCT APPROVAL REPORT FOR THE |
| | SHINGLES TO BE INSTALLED. . ONLY THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGES FL10450-R9 WERE SUBMITTED.. |
| | FAC 61G20-3.001. |
| | |
| | 3- PROVIDE COMPLETE PRODUCT APPROVAL REPORT FOR THE |
| | SHINGLES UNDERLAYMNET TO BE INSTALLED. . ONLY THE |
| | FLORIDA PRODUCT APPROVAL COVER PAGES FL10674-R13 WERE |
| | SUBMITTED. |
| | FAC 61G20-3.001. |
| | |
| | 4- PROVIDE 2 COPIES OF EACH PRODUCT APPROVAL AS |
| | REQUIRED BY SEC. 107.1 CITY AMENDMENTS. ONLY ONE COPY |
| | WAS SUBMITTED. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |