Plan Review Details - Permit 19020050
Plan Review Stops For Permit 19020050
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-06-04 Cont ID  
Sent By pvalenti Date 2019-06-04 Time 07:56 Rev Time 0.00
Received By pvalenti Date 2019-06-04 Time 07:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-04-05 Cont ID  
Sent By pvalenti Date 2019-04-05 Time 08:36 Rev Time 0.00
Received By pvalenti Date 2019-04-05 Time 06:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-13 Cont ID  
Sent By jwitmer Date 2019-02-13 Time 09:17 Rev Time 0.00
Received By jwitmer Date 2019-02-13 Time 06:20 Sent To  
Notes
2019-02-13 09:17:142017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020050
 ADD: 801 VILLAGE BLVD., SUITE: 305
 CONT: BLUE DOLPHIN CONSTRUCTION LLC
 TEL: 786-205-1242
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 13/ 2019
 ACTION: DENIED
  
 1) SHEET A102 INDICATES THE TRAVEL DISTANCE FROM THE
 FRONT OF THE SUITE TO THE REAR IS OVER 75 FEET, AN
 OCCUPANT LOAD OF 45 FIRE SPRINKLERED FOR A MERCANTILE/
 BUSINESS OCCUPANCY THE 2017 FBC-B TABLE 1006.2.1 COMMON
 PATH OF TRAVEL IS LIMITED TO 75 FEET WHICH WILL REQUIRE
 TWO EXITS. PLEASE SHOW COMPLIANCE WITH:
  
 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 2) IF THE REAR EXIT IS NOT ACCESSIBLE, THEN SHOW HOW UP
 TO $5,000.00 DOLLARS COULD BE SPENT ON ACCESSIBLE
 UPGRADES, SEE THE ORDER IN WHICH THE FUNDS ARE TO BE
 SPENT.
 2017 ACCESSIBILITY CODE SECTION 202.4.1DISPROPORTIONATE
 COST. ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 EITHER THE DESIGN PROFESSIONAL OR CONTRACTOR ON THEIR
 LETTERHEAD NEEDS TO SHOW AN ITEMIZED DOLLAR AMOUNT FOR
 ACCESSIBLE UPGRADES TO REACH EITHER CODE COMPLIANCE OR
 THE DISPROPORTIONATE COST OF $5,000.00 IN VALUE.
  
 3) PLEASE NOTE SHEET A001 THE LIFE SAFETY PLAN NOR A102
 DO NOT SHOW DETAILS FOR NEITHER THE BREAK ROOM SINK OR
 THE RESTROOM. SHEET A102 DOES SHOW A DETAIL 1/A203 FOR
 THE RESTROOM, BUT THERE IS NO SUCH SHEET LISTED IN THE
 SHEET INDEX NOR IS THERE SUCH SHEET IN THE SET OF
 PLANS. CODE COMPLIANCE FOR THESE ELEMENTS CANNOT BE
 REVIEWED FOR THIS REVIEW. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED. THE ACCESSIBILITY REQUIREMENTS
 FOUND IN CHAPTER 6 OF THE ACCESSIBILITY CODE CANNOT BE
 REVIEWED.
  
 4) THE M101 & M200 SHOW A MAKE-UP AIR WALL LOUVER
 REQUIRED, PLEAS PROVIDE THE PRODUCT APPROVAL FOR THIS
 PRODUCT. PLEASE COMPLY WITH: / 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31? WALL LOUVERS
  
 5) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THE WALL
 LOUVER, NOT FOUND ON EITHER THE ARCHITECTURAL OR
 MECHANICAL SHEETS.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 6.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 6.2. RISK CATEGORY.
  
 6.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 6.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 6.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-06-03 Cont ID  
Sent By jpearson Date 2019-06-03 Time 07:51 Rev Time 0.00
Received By jpearson Date 2019-06-03 Time 06:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-03-28 Cont ID  
Sent By jleahy Date 2019-03-28 Time 08:09 Rev Time 0.00
Received By jleahy Date 2019-03-28 Time 08:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-02-21 Cont ID  
Sent By jleahy Date 2019-02-21 Time 11:11 Rev Time 0.00
Received By jleahy Date 2019-02-21 Time 11:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-05-20 Cont ID  
Sent By pleduc Date 2019-05-20 Time   Rev Time 0.00
Received By pleduc Date 2019-05-20 Time 09:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-03-20 Cont ID  
Sent By pleduc Date 2019-03-20 Time   Rev Time 0.00
Received By pleduc Date 2019-03-20 Time 11:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-02-04 Cont ID  
Sent By pleduc Date 2019-02-04 Time   Rev Time 0.00
Received By pleduc Date 2019-02-04 Time 14:16 Sent To  
Notes
2019-02-04 14:21:08THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) ENSURE THAT THERE IS FIRE SPRINKLER ALARM DEVICE IS
 INSTALLED IN THIS SUITE. THE DEVICE IS TO TIED INTO THE
 ENTIRE BUILDING FIRE SPRINKLER ALARM.
  
  
 PER NFPA 101, CHAPTER 37, EXISTING MERCANTILE
 OCCUPANCIES
  
 37.4.5.4.3 OCCUPANT NOTIFICATION. DURING ALL TIMES THAT
 THE MERCANTILE
 OCCUPANCY IS OCCUPIED, THE REQUIRED FIRE ALARM SYSTEM,
 ONCE INITIATED,
 SHALL PERFORM ONE OF THE FOLLOWING FUNCTIONS:
 (1) IT SHALL ACTIVATE AN ALARM IN ACCORDANCE WITH 9.6.3
 THROUGHOUT THE
 MERCANTILE OCCUPANCY, AND POSITIVE ALARM SEQUENCE IN
 ACCORDANCE
 WITH 9.6.3.4 SHALL BE PERMITTED.
 (2) OCCUPANT NOTIFICATION SHALL BE PERMITTED TO BE MADE
 VIA A VOICE
 COMMUNICATION OR PUBLIC ADDRESS SYSTEM IN ACCORDANCE
 WITH
 9.6.3.9.2.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-06-04 Cont ID  
Sent By pvalenti Date 2019-06-04 Time 07:57 Rev Time 0.00
Received By pvalenti Date 2019-05-14 Time 13:40 Sent To  
Notes
2019-05-15 13:40:50B28

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-04-09 Time   Rev Time 0.00
Received By lmarchan Date 2019-03-18 Time 14:31 Sent To  
Notes
2019-03-19 14:32:03B32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-07 Cont ID  
Sent By cpuell Date 2019-03-07 Time 16:26 Rev Time 0.00
Received By cpuell Date 2019-02-01 Time 16:06 Sent To  
Notes
2019-02-01 16:06:10B23

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-02-13 Cont ID  
Sent By jwitmer Date 2019-02-13 Time 09:17 Rev Time 0.00
Received By jwitmer Date 2019-02-13 Time 06:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-05-31 Cont ID  
Sent By ccole Date 2019-05-31 Time 08:30 Rev Time 0.00
Received By ccole Date 2019-05-31 Time 07:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-04-09 Cont ID  
Sent By ccole Date 2019-04-09 Time 12:53 Rev Time 0.00
Received By ccole Date 2019-04-09 Time 12:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-02-27 Cont ID  
Sent By ccole Date 2019-02-27 Time 16:54 Rev Time 0.00
Received By ccole Date 2019-02-27 Time 16:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-05-22 Cont ID  
Sent By gjohnson Date 2019-05-22 Time 08:07 Rev Time 0.00
Received By gjohnson Date 2019-05-22 Time 07:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-04-04 Cont ID  
Sent By thunt Date 2019-04-04 Time 11:22 Rev Time 0.00
Received By thunt Date 2019-04-04 Time 08:07 Sent To  
Notes
2019-04-04 11:22:31PLUMBING 2ND REVIEW**DENIED**
  
  
 1) THE FOLLOWING SHEETS HAVE THE P.E SIGNATURE AND SEAL
 AS COPIES.61G15-23.001 SHALL ACQUIRE A SEAL WITH WHICH
 SHE OR HE SHALL IDENTIFY ALL PLANS, SPECIFICATIONS OR
 REPORTS PREPARED OR ISSUED BY HER OR HIM AND FILED FOR
 PUBLIC RECORD. THE SEAL SHALL BE CAPABLE OF LEAVING A
 PERMANENT INK REPRESENTATION OR OTHER FORM OF EMBOSSING
 OR OPAQUE AND PERMANENT IMPRESSION, WHICH ALSO MAY BE
 COMPUTER GENERATED IMPRESSIONS, ON THE SURFACE OF
 PRINTS OR OTHER DUPLICATIONS OF DRAWINGS, AND, AS
 APPROPRIATE, UPON SPECIFICATION PAGES, AND OTHER
 ARTICLES OF SERVICE. WHERE REQUIRED, ELECTRONIC FILES
 MAY BE SEALED IN ACCORDANCE WITH RULE 61G15-23.001,
 F.A.C.SHT.A00,001,102,203,E200,M100,P100,101,200.
 PLEASE CORRECT AND RESUBMIT
  
 2) SHT A-203 DETAIL #3 GRAB BAR TO BE MOUNTED @ 36" TO
 CENTER. GRAB BARS SHALL BE MOUNTED 33"-36" TO THE TOP
 GRIPPING SURFACE. FCB-A 609.4
  
 3) SHT. P-200 SHOW THE TOILET AS BEING DRY VENTED AND
 HAS THE DRINKING FOUNTAIN DISCHARGING INTO THE BATHROOM
 GROUP WET VENT. FBC 912.1
  
 4) THE DOOR SWING INTO THE CLEAR FLOOR SPACE OF THE LAV
 IS NOT PERMITTED UNLESS YOU COMPLY ALSO WITH FBC-A
 305.3. FBC-A 603.2.3
  
 5) SHOW TOILET DISPENCER MEASURMENT FROM THE FRONT OF
 THE TOILET BOWL AS 7"-9". FBC-A 604.7
  
 6) P-101 DETAIL 5 PROVIDE NOTE THAT TEMPERING VALVE
 SHALL BE ASSE 1070. FBC-P 607.1.2
  
 7) LIST BACKFLOW AS REQUIRING A SEPERATE PERMIT. WPB
 ORD TO THE FBC 105.1
  
 8) PROVIDE SUPPORT DOCS SHOWING WATER HEATER SHELF WILL
 SUPORT THE WEIGHT OF THE WATER WITH IT FULL OF WATER.
 FBC 107.2.1
  
 9) SHT.A-203 PROVIDE MEASUREMENT SHOW THE GRAB BAR IS
 TO BE MOUNTED 12" FROM THE CENTER LINE OF THE TOILET.
 FBC-A 604.5.2
  
 10) SHT A-203 SHOW DIMENSIONS FOR SIDE GRAB BAR AS
 42"MIN LONG, AND THE OVERALL @54" FROM BACKWALL. FBC-A
 604.5.1
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-02-26 Cont ID  
Sent By jesmith Date 2019-02-26 Time 15:48 Rev Time 0.00
Received By jesmith Date 2019-02-26 Time 15:48 Sent To  
Notes
2019-02-26 15:48:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 PLUMBING COMMENTS
 1. A102 REFERENCES A DETAIL ON A203 FOR THE BATHROOM.
 THAT PLAN SHEET IS MISSING.
 2. IS THERE A BREAKROOM WITH A SINK? PLEASE CLARIFY AND
 PROVIDE DETAILS PER WPB FBC 107.2.1.
 3. PROVIDE DETAILS OF ADA COMPLIANT FIXTURES COMPLYING
 WITH FBC ACC CHAPTER 6 PER WPB FBC 107.2.1.
 4. PER WPB FBC 107.3.5.1.3 AND 107.2.1, PROVIDE THE
 FOLLOWING:
 A. PLUMBING FIXTURE SCHEDULE
 B. CODE COMPLIANT SANITARY AND WATER RISER DIAGRAMS
 C. SANITARY AND WATER LAYOUT (FLOOR PLAN)
 D. WATER HEATER SCHEDULE AND LOCATION.
 E. IDENTIFY PLUMBING FIXTURES ON PLUMBING FLOOR PLAN
 AND RISER DIAGRAMS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop Z ZONING
Rev No 3 Status P Date 2019-05-17 Cont ID  
Sent By eschneid Date 2019-05-17 Time 14:19 Rev Time 0.25
Received By eschneid Date 2019-05-17 Time 14:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-04-02 Cont ID  
Sent By eschneid Date 2019-04-02 Time 16:34 Rev Time 0.25
Received By eschneid Date 2019-04-02 Time 16:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-03-06 Cont ID  
Sent By eschneid Date 2019-03-06 Time 16:58 Rev Time 0.25
Received By eschneid Date 2019-03-06 Time 16:58 Sent To PC
Notes
***NONE***