Plan Review Details - Permit 19020028
Plan Review Stops For Permit 19020028
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-03-07 Cont ID  
Sent By rmcdouga Date 2019-03-07 Time 14:37 Rev Time 0.00
Received By rmcdouga Date 2019-03-07 Time 14:05 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-04 Cont ID  
Sent By rmcdouga Date 2019-02-04 Time 17:29 Rev Time 0.00
Received By rmcdouga Date 2019-02-04 Time 16:25 Sent To M
Notes
2019-02-04 17:29:48PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE REQUIRED OPENING PRESSURES AND WINDLOAD
 DATA ON THE PLANS. FBC 1603.1.4
  
 2) PROVIDE STRUCTURAL DETAILS FOR THE WALL INFILL WHERE
 THE EXISTING DOUBLE DOOR IS BEING REPLACED WITH A
 SINGLE DOOR. FBC 1603.1

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-02-04 Cont ID  
Sent By jleahy Date 2019-02-04 Time 13:27 Rev Time 0.00
Received By jleahy Date 2019-02-04 Time 13:27 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-03-07 Cont ID  
Sent By cmontell Date 2019-03-08 Time 13:53 Rev Time 0.00
Received By tklarge Date 2019-03-07 Time 06:19 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-02-07 Cont ID  
Sent By tklarge Date 2019-02-07 Time 07:22 Rev Time 0.00
Received By tklarge Date 2019-02-06 Time 06:03 Sent To  
Notes
2019-02-07 07:22:49SHOW THE SIZE OF THE GAS LINE DOWNSTREAM OF THE
 SECONDARY REGULATOR.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-08 Cont ID  
Sent By cmontell Date 2019-03-08 Time 13:53 Rev Time 0.00
Received By cmontell Date 2019-03-08 Time 13:53 Sent To G
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-07 Cont ID  
Sent By tklarge Date 2019-02-07 Time 07:23 Rev Time 0.00
Received By tklarge Date 2019-02-01 Time 15:03 Sent To  
Notes
2019-02-01 15:03:56REVISION ROUTED TO JLEAHY

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-03-08 Cont ID  
Sent By cmontell Date 2019-03-08 Time 13:52 Rev Time 0.00
Received By cmontell Date 2019-03-08 Time 13:52 Sent To I
Notes
2019-03-08 13:50:32MECHANICAL PLAN REVIEW PASS
  
 CALL 604 BE FOR EXHAUST PIPE IS INSULATED.
 WELDING CERTS REQUIRED.
 CALL 602 AFTER PIPE IS INSULATED.
  
 CHRIS MONTELLO
 805-6733

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-02-05 Cont ID  
Sent By hmoser Date 2019-02-05 Time 09:19 Rev Time 0.00
Received By hmoser Date 2019-02-05 Time 08:03 Sent To  
Notes
2019-02-05 09:19:24PLAN PASS
 CALL 604 BE FOR EXHAUST PIPE IS INSULATED.
 WELDING CERTS REQUIRED.
 CALL 602 AFTER PIPE IS INSULATED.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676