Plan Review Details - Permit 19020026
Plan Review Stops For Permit 19020026
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-02-05 Cont ID  
Sent By jduprey Date 2019-02-05 Time 12:03 Rev Time 0.00
Received By jduprey Date 2019-02-05 Time 12:03 Sent To  
Notes
2019-02-21 10:12:00PROVISO
  
 THE CONTRACTOR MUST SCHEDULE PERIODIC INSPECTIONS EVERY
 WEEK
  
 MUST PROVIDE CONSTRUCTION SAFE GUARDS AND PEDESTRIAN
 PROTECTION WHERE REQUIRED PER FBC 3302; FBC 3306

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-20 Cont ID  
Sent By jduprey Date 2019-02-20 Time 14:05 Rev Time 0.00
Received By jduprey Date 2019-02-20 Time 14:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-05 Cont ID  
Sent By jduprey Date 2019-02-05 Time 12:06 Rev Time 0.00
Received By jduprey Date 2019-02-01 Time 14:19 Sent To  
Notes
2019-02-01 14:20:07BLDG MISC 1

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2019-02-20 Cont ID  
Sent By jduprey Date 2019-02-20 Time 14:05 Rev Time 0.00
Received By jduprey Date 2019-02-20 Time 14:05 Sent To  
Notes
2019-02-20 14:07:04PROVISO
  
 THE CONTRACTOR MUST SCHEDULE PERIODIC INSPECTIONS EVERY
 WEEK
  
 MUST PROVIDE CONSTRUCTION SAFE GUARDS AND PEDESTRIAN
 PROTECTION WHERE REQUIRED PER FBC 3302; FBC 3306

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2019-02-05 Cont ID  
Sent By jduprey Date 2019-02-05 Time 12:06 Rev Time 0.00
Received By jduprey Date 2019-02-05 Time 12:03 Sent To  
Notes
2019-02-05 12:06:14BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THE SPECIA INSPECTION AGREEMENT WAS SUBMITTED ON THE
 OLD FORM. EMAIL WAS SENT TO THE CLIENT WITH THE NEW
 FORM TO RE-SUBMITT. FBC 110.8
  
 CHAPTER 1, SECTION 110.8 OF THE CITY OF WEST PALM
 BEACH, CHAPTER 1 AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 553.79 OF FLORIDA STATUTES; AND CHAPTER
 468, PART XII
  
 1. SPECIAL INSPECTOR AGREEMENT SHALL BE COMPLETED AND
 SUBMITTED IN TRIPLICATE.
  
 2. PROVIDE RESUME OF JOB INSPECTOR (P.E., ARCH. OR 468
 INSPECTOR).
  
 3. PROVIDE LIST OF SIMILAR PROJECTS COMPLETED BY
 CONTRACTOR.
  
  
  