Plan Review Details - Permit 19020019
Plan Review Stops For Permit 19020019
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-06-19 Cont ID  
Sent By dbattles Date 2019-06-19 Time 08:22 Rev Time 0.00
Received By dbattles Date 2019-06-19 Time 08:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-03-29 Cont ID  
Sent By jduprey Date 2019-03-29 Time 08:00 Rev Time 0.00
Received By jduprey Date 2019-03-28 Time 10:11 Sent To  
Notes
2019-03-29 08:09:32BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR
 SUBMITTALS, OR INDICATE IF THIS SUBMITTAL ARE GOING TO
 BE DEFERRED.
  
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 2. PLEASE SUBMITT THE OWNER-BUILDER AFFIDAVIT. FCB 107
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-04 Cont ID  
Sent By jduprey Date 2019-02-04 Time 16:05 Rev Time 0.00
Received By jduprey Date 2019-02-04 Time 15:05 Sent To  
Notes
2019-02-04 16:05:06BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. NO INFORMATION WAS PROVIDED IN REGARDS, INSULATION,
 NEW CEILING, ELECTRICAL AND MECHANICAL ITEMS. WE
 UNDERSTAND THE INSTALLATION OF A NEW ROOF WILL HAVE AN
 IMPACT TO THIS ITEMS. PLEASE PROVIDE INFORMATION IN
 REGARDS THESE AND SUBMIT THE CORRESPONDENT PERMIT
 APPLICATIONS. FBC 107
  
 2. THE DRAWING PAGE A1 UNDER BUILDING CODES INDICATES
 2010 EDITION. THE CURRENT EXISTING BUILDING CODE IS THE
 2017 6TH EDITION. PLEASE HAVE THIS CHANGE.
  
 3. CONSTRUCTION AND CONNECTION DETAILS FOR THE GIRDER
 TRUSS WERE NOT PROVIDED. PLEASE PROVIDE THE REQUIRED
 CONSTRUCTION DETAILS. FBC 107
  
 4. ON DRAWING SHEET A2 "NEW KNEE WALL SECTION" IS NOT
 CLEAR WHAT IS GOING TO BE USE TO COVER THE WOOD STUDS
 FROM THE EXTERIOR. PLEASE PROVIDE THIS INFORMATION,
 THIS MUST MEET FBC RESIDENTIAL 703.7.3
  
 5. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE
 OF WORK. THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. YOU MAY PROVIDE A COPY OF THE
 CONTRACT SIGNED BY THE OWNER OR A LIST OF LABOR,
 MATERIALS AND EQUIPMENT RENTAL TO VERIFY VALUE. CITY OF
 WPB CHAPTER 109.3.
  
 6. AN OWNER/BUILDER APPLICATION WAS SUBMITTED HOWEVER
 IS NOT SIGN BY THE REGISTERED OWNER EDGARDO NIBORSKI.
 FOR OWNER/BUILDER APPLICATIONS THE OWNER MUST COME TO
 THE BUILDING DEPARTMENT TO SIGN THE APPLICATION AND
 AFFIDAVIT IN PERSON. FLORIDA STATUTE 489.103
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-06-06 Cont ID  
Sent By jleahy Date 2019-06-06 Time 15:28 Rev Time 0.00
Received By jleahy Date 2019-06-06 Time 15:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-04-04 Cont ID  
Sent By jleahy Date 2019-04-04 Time 14:48 Rev Time 0.00
Received By jleahy Date 2019-04-04 Time 14:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-06-28 Cont ID  
Sent By tklarge Date 2019-06-28 Time 11:50 Rev Time 0.00
Received By tklarge Date 2019-06-21 Time 14:40 Sent To  
Notes
2019-06-24 14:40:25RESUB ROUTED TO HMOSER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-06-19 Cont ID  
Sent By dbattles Date 2019-06-19 Time 08:23 Rev Time 0.00
Received By dbattles Date 2019-05-28 Time 10:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-04 Cont ID  
Sent By jleahy Date 2019-04-04 Time 14:48 Rev Time 0.00
Received By jleahy Date 2019-03-21 Time 14:54 Sent To  
Notes
2019-03-22 14:55:04R19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-04 Cont ID  
Sent By jduprey Date 2019-02-04 Time 16:05 Rev Time 0.00
Received By jduprey Date 2019-02-01 Time 16:47 Sent To  
Notes
2019-02-01 16:47:15MISC 1

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-06-28 Cont ID  
Sent By hmoser Date 2019-06-28 Time 08:36 Rev Time 0.00
Received By hmoser Date 2019-06-28 Time 08:20 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-06-07 Cont ID  
Sent By cmontell Date 2019-06-07 Time 11:02 Rev Time 0.00
Received By cmontell Date 2019-06-07 Time 11:23 Sent To  
Notes
2019-06-07 10:39:23MECHANICAL PLAN REVIEW PASS
  
 1 - PLEASE PROVIDE VERIFICATION FOR BEDROOM 3 SUPPLY
 DUCT PER WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, 6TH EDITION (2017), CHAPTER 1,
 ADMINISTRATION, 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 2 - JOB VALUE SEEMS LOW: PROVIDE ACTUAL COST SO AS TO
 COMPLY WITH 109.3 BUILDING PERMIT VALUATIONS. IF, IN
 THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT
 SHALL BE DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE APPROVAL
 OF THE BUILDING OFFICIAL. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 CHRIS MONTELLO
 805-6733

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-04 Cont ID  
Sent By cmontell Date 2019-04-04 Time 13:51 Rev Time 0.00
Received By cmontell Date 2019-04-04 Time 13:49 Sent To  
Notes
2019-04-04 13:51:40MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED MECHANICAL PLAN
  
 CHRIS MONTELLO
 805-6733

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-06-28 Cont ID  
Sent By tklarge Date 2019-06-28 Time 11:50 Rev Time 0.00
Received By tklarge Date 2019-06-28 Time 11:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-06-11 Cont ID  
Sent By thunt Date 2019-06-11 Time 07:22 Rev Time 0.00
Received By thunt Date 2019-06-10 Time 17:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-01 Cont ID  
Sent By thunt Date 2019-04-01 Time 10:42 Rev Time 0.00
Received By thunt Date 2019-04-01 Time 10:42 Sent To  
Notes
2019-04-01 10:41:59PLUMBING 1ST REVIEW**DENIED**
  
 1) JOB VALUE SEEMS LOW: PROVIDE ACTUAL COST SO AS TO
 COMPLY WITH 109.3 BUILDING PERMIT VALUATIONS. IF, IN
 THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT
 SHALL BE DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE APPROVAL
 OF THE BUILDING OFFICIAL. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) WASHING MACHINE IS MISSING FROM THE SANITARY RISER
 DRAWING. TOILET ARE SHOW AS 2" AND THE TUB IS NOT
 PERMITTED TO BE VENTED BY THE KITCHEN SINK. THE FITTING
 MUST BE IN DIRECTION OF FLOW. PLEASE PROVIDE A CODE
 COMPLIANT ISOMETRIC. FBC 107.3.5
  
 3) PROVIDE MANUFACTURES INSTALLATION MAUNAL SHOWING THE
 NEW WATER HEATER WITH MEET THE D.O.E ENERGY MIN OF .92
 U.E.F
  
 4) PROVIDE FLOW RATED, PRESSURE AND G.P.M SHOWING HOW
 YOUR COMPLYING WITH FBC-R P 2903.1 BEING ALL OF YOUR
 WATER PIPING IS 1/2"
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-06-18 Cont ID  
Sent By ajones Date 2019-06-18 Time 14:33 Rev Time 0.00
Received By ajones Date 2019-06-18 Time 14:33 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-04-04 Cont ID  
Sent By mcurz Date 2019-04-04 Time 10:45 Rev Time 0.00
Received By mcruz Date 2019-04-04 Time 10:42 Sent To E
Notes
***NONE***