Plan Review Details - Permit 19011386
Plan Review Stops For Permit 19011386
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-02-28 Cont ID  
Sent By skennedy Date 2019-02-28 Time 11:35 Rev Time 0.00
Received By skennedy Date 2019-02-28 Time 11:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-02-23 Cont ID  
Sent By tklarge Date 2019-02-23 Time 07:34 Rev Time 0.00
Received By tklarge Date 2019-02-23 Time 06:03 Sent To  
Notes
2019-02-23 07:34:211) INDICATE ON BOTH SETS OF PLANS THE TYPE OF FLOORING
 THAT IS BEING INSTALLED. THE PERMIT APPLICATION STATES"
 NEW FLOORING."WPB AMEND. TO FBC SEC. 107.2.1. 2ND
 REQUEST.
 2) TWO DIFFERENT DOCUMENTS HAVE BEEN SUBMITTED FOR
 FLOORING UNDERLAYMENT.ONE IS FOR "FLOORMUFFLER" AND THE
 OTHER IS FOR "SENTINEL". WHICH PRODUCT IS PLANNED ON
 BEING USED? CLARIFY. WPB AMEND. TO FBC SEC.
 107.2.1.REMOVE ANY OLD DOCUMENTS FROM THE PERMIT
 PACKAGE THAT DO NOT APPLY.2ND REQUEST.
 4) THE FLOOR UNDRELAYMENT SHALL COMPLY WITH THE
 REQUIREMENTS OF THE 2017 FBC SEC. 1207.2 FOR AIR-BORNE
 SOUND FOR THE TYPE OF FLOORING MATERIAL BEING
 INSTALLED. 2ND REQUEST.
 5) THE FLOOR UNDERLAYMENT SHALL COMPLY WITH THE
 REQUIREMENTS OF 2017 FBC SEC.1207.3 FOR STRUCTURE-BORNE
 SOUND FOR THE TYPE OF FLOORING MATERIAL BEING
 INSTALLED. 2ND REQUEST.
 6) SUBMIT TWO COPIES OF THE NONCOMBUSTIBILITY TEST FOR
 THE UNDERLAYMENT AS REQUIRED BY 2017 FBC SECS.703.5.1
 AND 703.5.2. 2ND REQUEST.
 7) SHOW THE WALL AREAS ON THE PLANS WHERE THE DRYWALL
 WILL BE REPLACED. 2ND REQUEST.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-13 Cont ID  
Sent By tklarge Date 2019-02-13 Time 11:58 Rev Time 0.00
Received By tklarge Date 2019-02-13 Time 11:22 Sent To  
Notes
2019-02-13 11:24:441) SUBMIT TWO COPIES OF THE FLOOR PLANS FOR THE WORK TO
 BE DONE. ONLY ONE COPY WAS IN THE APPLICATION
 PACKAGE.WPB AMEND. TO FBC SEC. 107.1, 107.2.1.
 2) INDICATE ON BOTH SETS OF PLANS THE TYPE OF FLOORING
 THAT IS BEING INSTALLED. THE PERMIT APPLICATION STATES"
 NEW FLOORING."WPB AMEND. TO FBC SEC. 107.2.1.
 3) TWO DIFFERENT DOCUMENTS HAVE BEEN SUBMITTED FOR
 FLOORING UNDERLAYMENT.ONE IS FOR "FLOORMUFFLER" AND THE
 OTHER IS FOR "SENTINEL". WHICH PRODUCT IS PLANNED ON
 BEING USED? CLARIFY. WPB AMEND. TO FBC SEC. 107.2.1.
 4) THE FLOOR UNDRELAYMENT SHALL COMPLY WITH THE
 REQUIREMENTS OF THE 2017 FBC SEC. 1207.2 FOR AIR-BORNE
 SOUND FOR THE TYPE OF FLOORING MATERIAL BEING
 INSTALLED.
 5) THE FLOOR UNDERLAYMENT SHALL COMPLY WITH THE
 REQUIREMENTS OF 2017 FBC SEC.1207.3 FOR STRUCTURE-BORNE
 SOUND FOR THE TYPE OF FLOORING MATERIAL BEING
 INSTALLED.
 6) SUBMIT TWO COPIES OF THE NONCOMBUSTIBILITY TEST FOR
 THE UNDERLAYMENT AS REQUIRED BY 2017 FBC SECS.703.5.1
 AND 703.5.2.
 7) SHOW THE WALL AREAS ON THE PLANS WHERE THE DRYWALL
 WILL BE REPLACED AND SHOW THE TYPE OF BACKER BOARD THAT
 WILL BE INSTALLED IN THE SHOWER AREA.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-23 Cont ID  
Sent By tklarge Date 2019-02-23 Time 07:40 Rev Time 0.00
Received By tklarge Date 2019-02-15 Time 13:39 Sent To  
Notes
2019-02-19 13:39:37RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-13 Cont ID  
Sent By tklarge Date 2019-02-13 Time 12:54 Rev Time 0.00
Received By tklarge Date 2019-01-31 Time 09:15 Sent To  
Notes
2019-02-01 09:16:25ROUTED TO PLUMBING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-02-23 Cont ID  
Sent By abelisle Date 2019-02-23 Time 05:41 Rev Time 0.00
Received By abelisle Date 2019-02-23 Time 05:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-02-13 Cont ID  
Sent By tklarge Date 2019-02-13 Time 12:53 Rev Time 0.00
Received By tklarge Date 2019-02-13 Time 11:58 Sent To  
Notes
2019-02-13 12:55:53SUBMIT TWO SETS OF PLANS FOR REVIEW. WPB AMEND. TO FBC
 SEC. 107.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  