Plan Review Details - Permit 19011379
Plan Review Stops For Permit 19011379
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-03-19 Cont ID  
Sent By dbattles Date 2019-03-19 Time 14:10 Rev Time 0.00
Received By dbattles Date 2019-03-19 Time 14:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-02-13 Cont ID  
Sent By jwitmer Date 2019-02-13 Time 08:23 Rev Time 0.00
Received By jwitmer Date 2019-02-13 Time 06:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-03-19 Cont ID  
Sent By jpearson Date 2019-03-19 Time 14:25 Rev Time 0.00
Received By jpearson Date 2019-03-19 Time 14:25 Sent To I
Notes
2019-03-19 14:25:18PASSED WITH PROVISO:
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. HOLD PLACED
 ON PERMIT UNTIL VALUE IS CONFIRMED. WPB FBC 109.3
  
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-25 Cont ID  
Sent By jpearson Date 2019-02-25 Time 10:04 Rev Time 0.00
Received By jpearson Date 2019-02-25 Time 09:56 Sent To I
Notes
2019-02-25 10:04:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-03-08 Cont ID  
Sent By pleduc Date 2019-03-08 Time   Rev Time 0.00
Received By pleduc Date 2019-03-08 Time 10:17 Sent To  
Notes
2019-03-08 10:18:16THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS.
  
  
 3) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-02-04 Cont ID  
Sent By pleduc Date 2019-02-04 Time   Rev Time 0.00
Received By pleduc Date 2019-02-04 Time 14:00 Sent To  
Notes
2019-02-04 14:01:39THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS.
  
  
 3) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-03-19 Time   Rev Time 0.00
Received By lmarchan Date 2019-03-06 Time 14:41 Sent To  
Notes
2019-03-07 14:41:43B16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-02-25 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-31 Time 13:09 Sent To  
Notes
2019-02-01 13:10:03B09

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-03-19 Cont ID  
Sent By jesmith Date 2019-03-19 Time 11:59 Rev Time 0.00
Received By jesmith Date 2019-03-19 Time 11:18 Sent To  
Notes
2019-03-19 11:59:07 
 APPROVED
 SEE REDLINED COMMENTS ON MB PLUMBING NARRATIVE,AND PLAN
 SHEETS LS-1 AND A-1

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-02-21 Cont ID  
Sent By jesmith Date 2019-02-21 Time 11:30 Rev Time 0.00
Received By jesmith Date 2019-02-21 Time 08:19 Sent To  
Notes
2019-02-21 11:29:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW: DENIED
 A. SCOPE OF WORK IS GREATER THAN NOTED ON THE PERMIT
 APPLICATION AND VALUE APPEARS TO BE LOW. SCOPE APPEARS
 TO BE AT LEAST A MINIMUM, REMOVAL OF EXISTING KITCHEN
 TYPE SINK, ADDING A THREE COMPARTMENT SINK AND HAND
 SINK AS WELL AS REPLACING AN EXISTING WATER COOLER AND
 WATER HEATER. PLEASE REVISE APPLICATION AND PROVIDE A
 VALUE THAT REFLECTS THE WORK TO BE DONE. A REVIEW OF
 COMMENTS BELOW SHOULD ALSO BE USED TO HELP DEFINE THE
 SCOPE AND VALUE.PLEASE NOTE, THE VALUE IS TO REFLECT
 THE COST OF THE TOTAL PROJECT.
 B. PER WPB FBC 107.2.1 AND/OR WPB FBC 107.3.5.1.3,
 PROVIDE THE FOLLOWING:
 1. A CODE COMPLIANT SANITARY RISER DIAGRAM AND WATER
 RISER DIAGRAM, SHOWING THE EXTENT OF THE NEW WORK. SHOW
 IN FLOOR PLAN AS WELL.
 2. NEW THREE COMPARTMENT SINK SHALL DISCHARGE THROUGH
 AN INDIRECT WASTE IN ACCORDANCE WITH FBC PL 802. SHOW
 ON PLUMBING PLANS AND PROVIDE A DETAIL SHOWING
 COMPLIANCE WITH FBC PL 802.1 AND 802.2 AS APPLICABLE.
 3. IS THE ORIGINAL DRINKING FOUNTAIN ADJACENT TO THE
 TOILET ROOM TO REMAIN IN PLACE? PLEASE CLARIFY ON
 PLANS. PROVIDE A DETAIL SHOWING COMPLIANCE WITH FBC ACC
 306 AND 602 FOR THE NEW ADA COMPLIANT WATER COOLER IS
 IN A DIFFERENT LOCATION FROM THE REPLACED EXISTING
 WATER COOLER. SHOW ON PLUMBING PLANS AND
 4. PROVIDE HOT WATER RECIRC PUMP AND HOT WATER RETURN
 TO COMPLY WITH FBC PL 607.2. PROVIDE SPEC (HP,
 ELECTRICAL CHARACTERISTICS, SIZE) AND DETAIL.
 5. PROVIDE WATER HEATER SPEC (STORAGE CAPACITY AND
 ELECTRICAL CHARACTERISTICS) AND DETAIL, SHOWING
 COMPLIANCE WITH THE REQUIREMENTS OF FBC PL CHAPTER 5
 AND FBC PL 607.3 THERMAL EXPANSION CONTROL. PROVIDE
 SIZING OF THERMAL EXPANSION CONTROL DEVICE.
 6. A MOP SINK IS REQUIRED PER FBC PL TABLE 403.1.
 PROVIDE, OR IF ONE IS IN PLACE THEN IDENTIFY ON THE
 PLANS.
 7. PROVIDE TEMPERED WATER FOR LAVATORIES AS APPLICABLE
 PER FBC 416.5.
 8. EXISTING ADA TOILET ROOMS SHALL CONFORM TO FBC ACC
 SECTIONS 304, 604 AND 606. CONFIRM AND PROVIDE A NOTE
 STATING SAID COMPLIANCE.
  
  
 SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS,
 ESPECIALLY AS A RESULT OF RESPONSE TO BUILDING REVIEW
 COMMENTS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  