| 2019-02-27 10:03:58 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19011369 |
| | 2/27/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC FP- FLORIDA FIRE PREVENTION CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | IN ADDITION TO THE CODES IN EFFECT LISTED ABOVE, THE |
| | PROPOSED PROJECT SHALL ALSO BE IN COMPLIANCE WITH NFPA |
| | 37- 2015 AND THE FLORIDA FIRE PREVENTION CODE SIXTH |
| | EDITION 2017- SEE SECTIONS 915.1 AND 1301.1 OF THE FBC |
| | M, |
| | |
| | PLEASE REVIEW THE COMMENTS LISTED BELOW, AND CORRECT |
| | THE PLANS ACCORDINGLY. |
| | |
| | 1) PROVIDE ENLARGED DIMENSIONED DRAWINGS OF THE |
| | GENERATOR ROOM DRAWN TO A MINIMUM 1/8" SCALE SHOWING |
| | THE LOCATIONS OF THE NEW TANK, EXISTING GENERATOR AND |
| | ALL OTHER ASSOCIATED EQUIPMENT INCLUDING EMERGENCY |
| | ELECTRICAL PANELS ETC. PLEASE PROVIDE ON THE DRAWINGS: |
| | A) FIRE SPRINKLER DESIGN SPECIFICATIONS. B) |
| | FIRE-RESISTANCE RATING OF THE WALLS, FLOOR AND CEILING |
| | ENCLOSING THE ROOM. C) FIRE-RESISTANCE RATING OF THE |
| | EXISTING DOOR. D) REQUIRED INSTALLATION CLEARANCES FOR |
| | ALL EQUIPMENT. E) FUEL AND VENT PIPING RUNS AND |
| | SPECIFICATIONS INCLUDING FILL PIPING LOCATIONS. E) |
| | LOCATIONS OF EXISTING VENTILATION FANS AND OTHER |
| | VENTILATION OPENINGS AND EXHAUST OUTLETS- SEE |
| | SECTION107.2.1. WPB, AND SECTION 66.9.7 FBC FP. |
| | |
| | 2) REFER TO SECTION AND TABLE 66.9.6.1 FBC FP AND |
| | PROVIDE THE FLAMMABLE LIGUID CLASS OF THE FUEL OIL AND |
| | THE TOTAL AMOUNT OF LIQUID TO BE INSTALLED IN THE |
| | GENERATOR ROOM. THE TOTAL AMOUNT SHALL INCLUDE THE |
| | GALLON CAPACITY OF THE GENERATOR'S INTEGRAL BELLY TANK |
| | (IF APPLICABLE). |
| | |
| | 3) CLARIFY HOW CONTAINMENT, DRAINAGE, AND SPILL CONTROL |
| | ARE BEING PROVIDED FOR THE TANK- REFER TO SECTION |
| | 66.9.13 FBC FP AND PROVIDE DETAILS AND NOTES ON THE |
| | PLAN. |
| | |
| | 4) CLARIFY HOW ADEQUATE VENTILATION WILL BE PROVIDED |
| | FOR THE GENERATOR/TANK ROOM. SEE SECTION 24.10 NFPA |
| | 30-2015 AND PROVIDE A VENTILATION SYSTEM IN COMPLIANCE, |
| | OR VERIFY THE EXISTING SYSTEM IS IN COMPLIANCE. (CODE |
| | REFERENCES: SECTION 11.7.5.2 FBC FP WHICH REFERENCES |
| | NFPA 110 FOR EMERGENCY GENERATORS AND SECTION 7.9.1.1 |
| | NFPA 110- 2016 WHICH REFERENCES NFPA 30 FOR |
| | INSTALLATION OF THE FUEL TANK IN THE GENERATOR ROOM). |
| | |
| | 5) REFER SECTION 66.9.12.1 FBC FP AND VERIFY THE |
| | ELECTRICAL SYSTEMS IN THE GENERATOR/TANK ROOM ARE IN |
| | COMPLIANCE. |
| | |
| | 6) PLEASE NOTE THAT THE SUBMITTED REDUCED-IN- SIZE |
| | ARCHITECTURAL PLANS BY QUINCY JOHNSON ARCHITECTS CAN BE |
| | USED FOR REFERENCE ONLY BECAUSE THEY DO NOT BEAR THE |
| | ORIGINAL SIGNATURE AND SEAL OF THE ARCHITECT OF RECORD- |
| | SECTION 61G14-16.003 FAC. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |