Plan Review Details - Permit 19011355
Plan Review Stops For Permit 19011355
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-03-06 Cont ID  
Sent By pvalenti Date 2019-03-06 Time 16:24 Rev Time 0.00
Received By pvalenti Date 2019-03-06 Time 11:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-13 Cont ID  
Sent By jwitmer Date 2019-02-13 Time 06:52 Rev Time 0.00
Received By jwitmer Date 2019-02-13 Time 06:19 Sent To  
Notes
2019-02-13 06:51:512017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19011355
 ADD: 1511 N FLAGLER DR. SUITE: 502
 CONT: SIEGEL DESIGN GROUP
 TEL: 561-965-3744
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 13/ 2019
 ACTION: DENIED
  
 1) THE SUBMITTED PLAN SHEET 1/1 INDICATES WITH NOTE #
 14 THE INSTALLATION OF LVT PLANK FLOORING WITH AN
 ATTACHED PAD WITH A RATING OF 63 STC / 60 IIC, WITH AN
 UNDERLAYMENT PROFLEX 250 WITH A RATING OF 56 STC / 54
 IIC RATING.
 SUBMITTED IS THE MANUFACTURERS CUT SHEET WHICH IS NOT
 THE REQUIRED TEST. THE DESIGN PROFESSIONAL ALSO STATES
 THAT LVT IS GOING TO BE INSTALLED. THE SUBMITTED CUT
 SHEET WAS ONLY TESTED FOR TILE ON A CONCRETE 6 INCH
 SLAB.
 I HAVE VERIFIED THE SLADE AT 1551 N. FLAGLER UNDER
 PERMIT 03020961 DOES HAVE A 7 ? INCH THICK POST TENSION
 SLAB ON SHEET S-12 OF THIS PERMIT.
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL (LVT) OR (LVP) AND WOOD
 FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT
 TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND
 MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE
 STANDARDS FOR A 8 INCH CONCRETE FLOOR ASSEMBLY/ NO
 DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-03-18 Cont ID  
Sent By jpearson Date 2019-03-18 Time 13:12 Rev Time 0.00
Received By jpearson Date 2019-03-18 Time 13:12 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-25 Cont ID  
Sent By jpearson Date 2019-02-25 Time 10:45 Rev Time 0.00
Received By jpearson Date 2019-02-25 Time 09:56 Sent To I
Notes
2019-02-25 10:45:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. PER FLORIDA
 STATUTES, INTERIOR DESIGN DOCUMENTS THAT ARE PREPARED
 AND SEALED BY A REGISTERED INTERIOR DESIGNER MAY, IF
 REQUIRED BY A PERMITTING BODY, BE SUBMITTED FOR THE
 ISSUANCE OF A BUILDING PERMIT FOR INTERIOR CONSTRUCTION
 EXCLUDING DESIGN OF ANY STRUCTURAL, MECHANICAL,
 PLUMBING, HEATING, AIR-CONDITIONING, VENTILATING,
 ELECTRICAL, OR VERTICAL TRANSPORTATION SYSTEMS OR THAT
 MATERIALLY AFFECT LIFESAFETY SYSTEMS PERTAINING TO
 FIRESAFETY PROTECTION SUCH AS FIRE-RATED SEPARATIONS
 BETWEEN INTERIOR SPACES, FIRE-RATED VERTICAL SHAFTS IN
 MULTISTORY STRUCTURES, FIRE-RATED PROTECTION OF
 STRUCTURAL ELEMENTS, SMOKE EVACUATION AND
 COMPARTMENTALIZATION, EMERGENCY INGRESS OR EGRESS
 SYSTEMS, AND EMERGENCY ALARM SYSTEMS.FS 471.003(2)(H);
 471.025, 481.2131(1); WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-03-08 Cont ID  
Sent By pleduc Date 2019-03-08 Time   Rev Time 0.00
Received By pleduc Date 2019-03-08 Time 10:07 Sent To  
Notes
2019-03-08 10:07:49THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING AREA
 MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE FIRE
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY A
 CERTIFIED FIRE SPRINKLER CONTRACTOR.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEMS SHALL
 BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY A CERTIFIED
 FIRE SPRINKLER CONTRACTOR.
  
 3) THE FIRE SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-02-05 Cont ID  
Sent By pleduc Date 2019-02-05 Time   Rev Time 0.00
Received By pleduc Date 2019-02-05 Time 11:28 Sent To  
Notes
2019-02-05 11:32:52THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING AREA
 MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE FIRE
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY A
 CERTIFIED FIRE SPRINKLER CONTRACTOR.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEMS SHALL
 BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY A CERTIFIED
 FIRE SPRINKLER CONTRACTOR.
  
 3) THE FIRE SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-03-18 Time   Rev Time 0.00
Received By lmarchan Date 2019-02-28 Time 15:18 Sent To  
Notes
2019-03-01 15:18:57B03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-02-25 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-31 Time 12:58 Sent To  
Notes
2019-02-01 12:59:06B03

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-03-15 Cont ID  
Sent By thunt Date 2019-03-15 Time 10:37 Rev Time 0.00
Received By thunt Date 2019-03-15 Time 10:37 Sent To  
Notes
2019-03-15 10:37:28**PLUMBING PROVISO**
  
 1) BEING THAT THIS SHOWER WILL BE CURB-LESS AND IS TO
 BE SEAL USING HYDRA-LOCK THE ENTIRE BATHROOM MUST BE
 WATER FLOOD TEST PER FLORIDA BUILDING CODE (PLUMBING)
 312.9
  
 2) THE ENTIRE BATHROOM IS TO REMAIN FAIR HOUSING
 COMPLIANT (FHA) WITH ALL CLEAR FLOOR SPACES AND BACKING
 TO REMAIN. SINK SHOULD BE MAX 34" TO TOP OF SINK
 FIXTURE. FHA.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 561-248-2703

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-02-21 Cont ID  
Sent By jesmith Date 2019-02-21 Time 12:35 Rev Time 0.00
Received By jesmith Date 2019-02-21 Time 12:27 Sent To  
Notes
2019-02-21 12:35:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW: DENIED
 1.PER WPB FBC 107.2.1 AND/OR WPB FBC 107.3.5.1.3,
 PROVIDE THE FOLLOWING:
 A. PLEASE NOTE ON THE PLANS WHETHER OR, NOT PROPOSED
 MODIFICATIONS COMPLY WITH THE FAIR HOUSING ACT AS
 AMENDED, EFFECTIVE MARCH12, 1989.
 B. A CROSS SECTIONAL DETAIL OF THE SHOWER COMPARTMENT
 SHOWING COMPLIANCE WITH FBC PL 417.5.2. THE NOTED
 DELETED SHOWER CURB CREATES PROBLEMS WHICH NEED TO BE
 ADDRESSED. SHOW HOW SHOWER WATER IS TO BE CONTAINED IN
 A MANNER THAT IT WILL NOT ADVERSELY AFFECT FLOORS BELOW
 OR ADJOINING AREAS.
 C. PROVIDE THE MATERIAL TYPE OF UNDER FLOOR DRAIN PIPE
 D. PROVIDE DETAIL FOR FIRE-SAFEING OF SHOWER DRAIN
 THROUGH FLOOR PENETRATION.
  
  
 SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS,
 ESPECIALLY AS A RESULT OF RESPONSE TO BUILDING REVIEW
 COMMENTS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715