Plan Review Details - Permit 19011248
| Plan Review Stops For Permit 19011248 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2019-05-17 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-05-17 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-05-17 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2019-05-17 09:39:17 | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | APPROVED WITH PROVISO: | | | | | | PROVIDE THE FLAME SPREAD SPECIFICATIONS FOR FLOORING | | | UNDERLAYMENT AT TIME OF FLOORING UNDERLAYMENT | | | INSPECTION AS PER THE FBC B SECTION 603. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2019-05-07 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-05-07 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-05-07 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2019-05-07 14:58:00 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 3RD REVIEW DENIED: | | | | | | 1A. FAIL, ON SHEET 1?1, THE OCCUPANCY STILL SHOWS AS | | | R?3; THE OCCUPANCY SHOULD BE R?2. (UNDER DESIGN | | | CRITERIA OF PAGE 1-1 THE PLANS HAVE NOT CHANGED) | | | | | | 1B. OK | | | | | | 1C. OK | | | | | | 2. OK | | | | | | 3A. FAIL, SHEET 1?1 WAS CORRECTED, HOWEVER WE STILL | | | NEED THE STRUCTURE?BORNE SOUND SPECIFICATIONS. PLEASE | | | SUBMIT THE SOUND INSULATION IMPACT TEST | | | SPECIFICATIONS/RESULTS FOR THE CHOSEN FLOORING | | | UNDERLAYMENT AS PER ASTM E 492. | | | | | | 3B. FAIL, SHEET 1?1 WAS CORRECTED, HOWEVER WE STILL | | | NEED THE AIR?BORNE SOUND SPECIFICATIONS. PLEASE SUBMIT | | | THE SOUND TRANSMISSION TEST SPECIFICATIONS/RESULTS FOR | | | THE CHOSEN FLOORING UNDERLAYMENT AS PER ASTM E 90. | | | | | | 3C. FAIL, SHEET 1?1 WAS CORRECTED, HOWEVER WE STILL | | | NEED THE FLAME SPREAD SPECIFICATIONS. PLEASE SUBMIT THE | | | FLAME SPREAD TEST SPECIFICATIONS/RESULTS AS PER ASTM E | | | 84 OR UL 723. | | | | | | 4. OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-04-24 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-04-24 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-04-24 |
Time |
15:49 |
Sent To |
|
|
| Notes |
| 2019-04-24 16:17:01 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 2ND BUILDING REVIEW DENIED: | | | | | | 1A. FAIL, ON SHEET 1-1, THE OCCUPANCY STILL SHOWS AS | | | R-3; THE OCCUPANCY SHOULD BE R-2. | | | 1B. OK | | | 1C. OK | | | | | | 2. OK | | | | | | 3A. FAIL, SHEET 1-1 WAS CORRECTED, HOWEVER WE STILL | | | NEED THE STRUCTURE-BORNE SOUND SPECIFICATIONS. PLEASE | | | SUBMIT THE SOUND INSULATION IMPACT TEST | | | SPECIFICATIONS/RESULTS FOR THE CHOSEN FLOORING | | | UNDERLAYMENT AS PER ASTM E 492. | | | 3B. FAIL, SHEET 1-1 WAS CORRECTED, HOWEVER WE STILL | | | NEED THE AIR-BORNE SOUND SPECIFICATIONS. PLEASE SUBMIT | | | THE SOUND TRANSMISSION TEST SPECIFICATIONS/RESULTS FOR | | | THE CHOSEN FLOORING UNDERLAYMENT AS PER ASTM E 90. | | | 3C. FAIL, SHEET 1-1 WAS CORRECTED, HOWEVER WE STILL | | | NEED THE FLAME SPREAD SPECIFICATIONS. PLEASE SUBMIT THE | | | FLAME SPREAD TEST SPECIFICATIONS/RESULTS AS PER ASTM E | | | 84 OR UL 723. | | | | | | 4. OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-02-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2019-02-11 |
Time |
11:59 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2019-02-11 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2019-02-11 11:57:23 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19011248 | | | ADD: 2400 PRESIDENTIAL WAY, SUITE: 401 | | | CONT: SUNSTREAM BUILDING ENTERPRISE | | | TEL: 954-234-0892 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: MON. FEB. 11/ 2019 | | | ACTION: DENIED | | | | | | 1) SHEET 1-1 UNDER THE HEADING DESIGN CRITERIA LIST | | | THE: | | | | | | 1A) OCCUPANCY TYPE AS R-3. PLEASE NOTE UNDER THE 2017 | | | FBC-B SECTION 310.5 IS FOR SINGLE FAMILY DWELLINGS NOT | | | FOR UNITS IN HIGHRISE BUILDINGS. SECTION 310.4 LIST | | | APARTMENTS (LONG TERM NON-TRANSIENT)AND CONDOS AS R2 | | | UNITS, PLEASE UPDATE PLANS. | | | | | | 1B) THIS SHEET LIST THE CONSTRUCTION TYPE AS V-B. | | | PLEASE UPDATE THE PLANS, THIS BUILDING IS A HIGHRISE | | | AND WILL NEED TO SHOW A CONSTRUCTION TYPE: I-A | | | NON-SPRINKLERED FOOTNOTE D. 2017 FBC-B TABLE 506.2. | | | | | | 1C) THE PLAN ALSO INDICATES AN ALTERATION LEVEL I. | | | PLEASE NOTE THIS ALTERATION LEVEL IS CONSIDERED A LEVEL | | | II ALTERATION. PLEASE REVIEW THE 2017 FBC-EXISTING | | | BUILDING CODE SECTION 504.1 LEVEL 2 ALTERATION. LEVEL 2 | | | ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE, THE | | | ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW, THE | | | RECONFIGURATION OR EXTENSION OF ANY SYSTEM, OR THE | | | INSTALLATION OF ANY ADDITIONAL EQUIPMENT. | | | THE RELOCATION OF THE STOVE AND DISH WASHER WOULD BE | | | THE RECONFIGURATION OR EXTENSION OF A SYSTEM. | | | | | | 2) SHEET 1-1 UNDER THE HEADING APPLICABLE CODES THE | | | 2017 RESIDENTIAL CODE IS STATED. PLEASE NOTE THE ONLY | | | TIME THE RESIDENTIAL CODE IS USED IS IN ONE & TWO | | | FAMILY DWELLINGS NOT WHEN IN HIGH-RISES. | | | 2017 FBC-RESIDENTIAL CODE, R101.2 SCOPE. THE PROVISIONS | | | OF THE FLORIDA BUILDING CODE, RESIDENTIAL SHALL APPLY | | | TO THE CONSTRUCTION, ALTERATION, MOVEMENT, ENLARGEMENT, | | | REPLACEMENT, REPAIR, EQUIPMENT, USE AND OCCUPANCY, | | | LOCATION, REMOVAL AND DEMOLITION OF DETACHED ONE- AND | | | TWO-FAMILY DWELLINGS AND TOWNHOUSES NOT MORE THAN THREE | | | STORIES ABOVE GRADE PLANE IN HEIGHT WITH A SEPARATE | | | MEANS OF EGRESS AND THEIR ACCESSORY STRUCTURES NOT MORE | | | THAN THREE STORIES ABOVE GRADE PLANE IN HEIGHT. | | | | | | 3) SHEET 1-1 UNDER THE HEADING SCOPE OF WORK LIST | | | REMOVE EXISTING FLOOR TILES AND INSTALL NEW LAMINATE | | | FLOOR OVER SOUND INSULATION. PLEASE SHOW CONFORMANCE | | | WITH: | | | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B | | | 2017) | | | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL | | | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR | | | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE | | | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A | | | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: | | | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: | | | | | | 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2019-05-07 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-05-07 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-05-07 |
Time |
13:21 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2019-04-18 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-04-18 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-04-18 |
Time |
08:51 |
Sent To |
|
|
| Notes |
| 2019-04-18 11:19:03 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | | 109.3 (NOT PROVIDED.) | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-02-21 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-02-21 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-02-21 |
Time |
10:30 |
Sent To |
I |
|
| Notes |
| 2019-02-21 15:04:07 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | | 109.3 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2019-05-16 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-05-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-05-16 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2019-05-16 13:38:20 | 5/16/19 | | | | | | | | | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) THERE IS NO INDICATION OF A SMOKE ALARM IN TWO | | | BEDROOMS, PER NFPA 101, A SMOKE ALARM IS REQUIRED IN | | | EACH. | | | | | | | | | NFPA 101, CHAPTER 31,EXISTING APARTMENT BUILDINGS | | | | | | 31.3.4.5 SMOKE ALARMS. | | | | | | 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED | | | THROUGHOUT WITH AN | | | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM, | | | SMOKE ALARMS | | | SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS | | | MODIFIED BY 31.3.4.5.2, | | | OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY | | | OF THE BEDROOMS | | | AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING | | | BASEMENTS. | | | | | | 31.3.4.5.3 IN BUILDINGS OTHER THAN THOSE EQUIPPED | | | THROUGHOUT WITH AN | | | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM OR | | | A COMPLETE, | | | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE | | | WITH 31.3.5, | | | SMOKE ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA | | | IN | | | ACCORDANCE WITH 9.6.2.10, AS MODIFIED BY 31.3.4.5.4. | | | | | | 31.3.4.5.4 SMOKE ALARMS REQUIRED BY 31.3.4.5.3 SHALL BE | | | PERMITTED TO BE | | | BATTERY POWERED. | | | | | | | | | PLEASE INSTALL A SMOKE ALARM IN THE MASTER BEDROOM | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-04-02 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-04-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-04-02 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2019-04-02 14:01:14 | 4/2/19 | | | | | | | | | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) THERE IS NO INDICATION OF A SMOKE ALARM IN TWO | | | BEDROOMS, PER NFPA 101, A SMOKE ALARM IS REQUIRED IN | | | EACH. | | | | | | | | | NFPA 101, CHAPTER 31,EXISTING APARTMENT BUILDINGS | | | | | | 31.3.4.5 SMOKE ALARMS. | | | | | | 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED | | | THROUGHOUT WITH AN | | | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM, | | | SMOKE ALARMS | | | SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS | | | MODIFIED BY 31.3.4.5.2, | | | OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY | | | OF THE BEDROOMS | | | AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING | | | BASEMENTS. | | | | | | 31.3.4.5.3 IN BUILDINGS OTHER THAN THOSE EQUIPPED | | | THROUGHOUT WITH AN | | | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM OR | | | A COMPLETE, | | | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE | | | WITH 31.3.5, | | | SMOKE ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA | | | IN | | | ACCORDANCE WITH 9.6.2.10, AS MODIFIED BY 31.3.4.5.4. | | | | | | 31.3.4.5.4 SMOKE ALARMS REQUIRED BY 31.3.4.5.3 SHALL BE | | | PERMITTED TO BE | | | BATTERY POWERED. | | | | | | | | | PLEASE INSTALL A SMOKE ALARM IN THE MASTER BEDROOM | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2019-02-04 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-02-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-02-04 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2019-02-04 14:30:59 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) THERE IS NO INDICATION OF A SMOKE ALARM IN TWO | | | BEDROOMS, PER NFPA 101, A SMOKE ALARM IS REQUIRED IN | | | EACH. | | | | | | | | | NFPA 101, CHAPTER 31,EXISTING APARTMENT BUILDINGS | | | | | | 31.3.4.5 SMOKE ALARMS. | | | | | | 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED | | | THROUGHOUT WITH AN | | | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM, | | | SMOKE ALARMS | | | SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS | | | MODIFIED BY 31.3.4.5.2, | | | OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY | | | OF THE BEDROOMS | | | AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING | | | BASEMENTS. | | | | | | 31.3.4.5.3 IN BUILDINGS OTHER THAN THOSE EQUIPPED | | | THROUGHOUT WITH AN | | | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM OR | | | A COMPLETE, | | | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE | | | WITH 31.3.5, | | | SMOKE ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA | | | IN | | | ACCORDANCE WITH 9.6.2.10, AS MODIFIED BY 31.3.4.5.4. | | | | | | 31.3.4.5.4 SMOKE ALARMS REQUIRED BY 31.3.4.5.3 SHALL BE | | | PERMITTED TO BE | | | BATTERY POWERED. | | | | | | | | | PLEASE INSTALL A SMOKE ALARM IN THE MASTER BEDROOM | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2019-05-17 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-05-17 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-05-10 |
Time |
13:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-05-07 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-05-07 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-05-01 |
Time |
12:48 |
Sent To |
|
|
| Notes |
| 2019-05-02 12:48:55 | RESUB ROUTED TO JPEARSON |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-04-24 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-04-24 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-03-29 |
Time |
13:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-02-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-01-29 |
Time |
10:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2019-05-16 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-05-16 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-05-16 |
Time |
07:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2019-04-09 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-04-09 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-04-09 |
Time |
11:32 |
Sent To |
|
|
| Notes |
| 2019-04-09 11:33:33 | APPROVED | | | PROVISO | | | 1. A SEPARATE PLUMBING PERMIT IS REQUIRED | | | 2. SCOPE IS LIMITED TO REPLACEMENT OF EXISTING KITCHEN | | | SINK AND PLUMBING CONNECTIONS TO NEW DISHWASHER AND | | | REFRIGERATOR ICE MAKER, REMOVAL OF EXISTING BAR SINK | | | AND CAPPING OF PLUMBING. | | | 3. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S | | | APPROVAL |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2019-02-19 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-02-19 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-02-19 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2019-02-19 14:47:19 | APPROVED | | | PROVISO | | | 1. A SEPARATE PLUMBING PERMIT IS REQUIRED | | | 2. SCOPE IS LIMITED TO REPLACEMENT OF EXISTING KITCHEN | | | SINK, BAR SINK AND PLUMBING CONNECTIONS TO NEW | | | DISHWASHER AND REFRIGERATOR ICE MAKER. | | | 3. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR?S | | | APPROVAL | | | |
|
|
|