Plan Review Details - Permit 19011248
Plan Review Stops For Permit 19011248
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-05-17 Cont ID  
Sent By pvalenti Date 2019-05-17 Time 09:33 Rev Time 0.00
Received By pvalenti Date 2019-05-17 Time 09:33 Sent To  
Notes
2019-05-17 09:39:17 
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED WITH PROVISO:
  
 PROVIDE THE FLAME SPREAD SPECIFICATIONS FOR FLOORING
 UNDERLAYMENT AT TIME OF FLOORING UNDERLAYMENT
 INSPECTION AS PER THE FBC B SECTION 603.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-05-07 Cont ID  
Sent By pvalenti Date 2019-05-07 Time 14:58 Rev Time 0.00
Received By pvalenti Date 2019-05-07 Time 14:52 Sent To  
Notes
2019-05-07 14:58:00***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 3RD REVIEW DENIED:
  
 1A. FAIL, ON SHEET 1?1, THE OCCUPANCY STILL SHOWS AS
 R?3; THE OCCUPANCY SHOULD BE R?2. (UNDER DESIGN
 CRITERIA OF PAGE 1-1 THE PLANS HAVE NOT CHANGED)
  
 1B. OK
  
 1C. OK
  
 2. OK
  
 3A. FAIL, SHEET 1?1 WAS CORRECTED, HOWEVER WE STILL
 NEED THE STRUCTURE?BORNE SOUND SPECIFICATIONS. PLEASE
 SUBMIT THE SOUND INSULATION IMPACT TEST
 SPECIFICATIONS/RESULTS FOR THE CHOSEN FLOORING
 UNDERLAYMENT AS PER ASTM E 492.
  
 3B. FAIL, SHEET 1?1 WAS CORRECTED, HOWEVER WE STILL
 NEED THE AIR?BORNE SOUND SPECIFICATIONS. PLEASE SUBMIT
 THE SOUND TRANSMISSION TEST SPECIFICATIONS/RESULTS FOR
 THE CHOSEN FLOORING UNDERLAYMENT AS PER ASTM E 90.
  
 3C. FAIL, SHEET 1?1 WAS CORRECTED, HOWEVER WE STILL
 NEED THE FLAME SPREAD SPECIFICATIONS. PLEASE SUBMIT THE
 FLAME SPREAD TEST SPECIFICATIONS/RESULTS AS PER ASTM E
 84 OR UL 723.
  
 4. OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-04-24 Cont ID  
Sent By pvalenti Date 2019-04-24 Time 15:50 Rev Time 0.00
Received By pvalenti Date 2019-04-24 Time 15:49 Sent To  
Notes
2019-04-24 16:17:01***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND BUILDING REVIEW DENIED:
  
 1A. FAIL, ON SHEET 1-1, THE OCCUPANCY STILL SHOWS AS
 R-3; THE OCCUPANCY SHOULD BE R-2.
 1B. OK
 1C. OK
  
 2. OK
  
 3A. FAIL, SHEET 1-1 WAS CORRECTED, HOWEVER WE STILL
 NEED THE STRUCTURE-BORNE SOUND SPECIFICATIONS. PLEASE
 SUBMIT THE SOUND INSULATION IMPACT TEST
 SPECIFICATIONS/RESULTS FOR THE CHOSEN FLOORING
 UNDERLAYMENT AS PER ASTM E 492.
 3B. FAIL, SHEET 1-1 WAS CORRECTED, HOWEVER WE STILL
 NEED THE AIR-BORNE SOUND SPECIFICATIONS. PLEASE SUBMIT
 THE SOUND TRANSMISSION TEST SPECIFICATIONS/RESULTS FOR
 THE CHOSEN FLOORING UNDERLAYMENT AS PER ASTM E 90.
 3C. FAIL, SHEET 1-1 WAS CORRECTED, HOWEVER WE STILL
 NEED THE FLAME SPREAD SPECIFICATIONS. PLEASE SUBMIT THE
 FLAME SPREAD TEST SPECIFICATIONS/RESULTS AS PER ASTM E
 84 OR UL 723.
  
 4. OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-11 Cont ID  
Sent By jwitmer Date 2019-02-11 Time 11:59 Rev Time 0.00
Received By jwitmer Date 2019-02-11 Time 11:09 Sent To  
Notes
2019-02-11 11:57:232017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19011248
 ADD: 2400 PRESIDENTIAL WAY, SUITE: 401
 CONT: SUNSTREAM BUILDING ENTERPRISE
 TEL: 954-234-0892
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 11/ 2019
 ACTION: DENIED
  
 1) SHEET 1-1 UNDER THE HEADING DESIGN CRITERIA LIST
 THE:
  
 1A) OCCUPANCY TYPE AS R-3. PLEASE NOTE UNDER THE 2017
 FBC-B SECTION 310.5 IS FOR SINGLE FAMILY DWELLINGS NOT
 FOR UNITS IN HIGHRISE BUILDINGS. SECTION 310.4 LIST
 APARTMENTS (LONG TERM NON-TRANSIENT)AND CONDOS AS R2
 UNITS, PLEASE UPDATE PLANS.
  
 1B) THIS SHEET LIST THE CONSTRUCTION TYPE AS V-B.
 PLEASE UPDATE THE PLANS, THIS BUILDING IS A HIGHRISE
 AND WILL NEED TO SHOW A CONSTRUCTION TYPE: I-A
 NON-SPRINKLERED FOOTNOTE D. 2017 FBC-B TABLE 506.2.
  
 1C) THE PLAN ALSO INDICATES AN ALTERATION LEVEL I.
 PLEASE NOTE THIS ALTERATION LEVEL IS CONSIDERED A LEVEL
 II ALTERATION. PLEASE REVIEW THE 2017 FBC-EXISTING
 BUILDING CODE SECTION 504.1 LEVEL 2 ALTERATION. LEVEL 2
 ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE, THE
 ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW, THE
 RECONFIGURATION OR EXTENSION OF ANY SYSTEM, OR THE
 INSTALLATION OF ANY ADDITIONAL EQUIPMENT.
 THE RELOCATION OF THE STOVE AND DISH WASHER WOULD BE
 THE RECONFIGURATION OR EXTENSION OF A SYSTEM.
  
 2) SHEET 1-1 UNDER THE HEADING APPLICABLE CODES THE
 2017 RESIDENTIAL CODE IS STATED. PLEASE NOTE THE ONLY
 TIME THE RESIDENTIAL CODE IS USED IS IN ONE & TWO
 FAMILY DWELLINGS NOT WHEN IN HIGH-RISES.
 2017 FBC-RESIDENTIAL CODE, R101.2 SCOPE. THE PROVISIONS
 OF THE FLORIDA BUILDING CODE, RESIDENTIAL SHALL APPLY
 TO THE CONSTRUCTION, ALTERATION, MOVEMENT, ENLARGEMENT,
 REPLACEMENT, REPAIR, EQUIPMENT, USE AND OCCUPANCY,
 LOCATION, REMOVAL AND DEMOLITION OF DETACHED ONE- AND
 TWO-FAMILY DWELLINGS AND TOWNHOUSES NOT MORE THAN THREE
 STORIES ABOVE GRADE PLANE IN HEIGHT WITH A SEPARATE
 MEANS OF EGRESS AND THEIR ACCESSORY STRUCTURES NOT MORE
 THAN THREE STORIES ABOVE GRADE PLANE IN HEIGHT.
  
 3) SHEET 1-1 UNDER THE HEADING SCOPE OF WORK LIST
 REMOVE EXISTING FLOOR TILES AND INSTALL NEW LAMINATE
 FLOOR OVER SOUND INSULATION. PLEASE SHOW CONFORMANCE
 WITH:
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-05-07 Cont ID  
Sent By jpearson Date 2019-05-07 Time 13:21 Rev Time 0.00
Received By jpearson Date 2019-05-07 Time 13:21 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-04-18 Cont ID  
Sent By jpearson Date 2019-04-18 Time 11:19 Rev Time 0.00
Received By jpearson Date 2019-04-18 Time 08:51 Sent To  
Notes
2019-04-18 11:19:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT PROVIDED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-21 Cont ID  
Sent By jpearson Date 2019-02-21 Time 15:04 Rev Time 0.00
Received By jpearson Date 2019-02-21 Time 10:30 Sent To I
Notes
2019-02-21 15:04:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-05-16 Cont ID  
Sent By pleduc Date 2019-05-16 Time   Rev Time 0.00
Received By pleduc Date 2019-05-16 Time 13:37 Sent To  
Notes
2019-05-16 13:38:205/16/19
  
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) THERE IS NO INDICATION OF A SMOKE ALARM IN TWO
 BEDROOMS, PER NFPA 101, A SMOKE ALARM IS REQUIRED IN
 EACH.
  
  
 NFPA 101, CHAPTER 31,EXISTING APARTMENT BUILDINGS
  
 31.3.4.5 SMOKE ALARMS.
  
 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED
 THROUGHOUT WITH AN
 EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM,
 SMOKE ALARMS
 SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS
 MODIFIED BY 31.3.4.5.2,
 OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY
 OF THE BEDROOMS
 AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING
 BASEMENTS.
  
 31.3.4.5.3 IN BUILDINGS OTHER THAN THOSE EQUIPPED
 THROUGHOUT WITH AN
 EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM OR
 A COMPLETE,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH 31.3.5,
 SMOKE ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA
 IN
 ACCORDANCE WITH 9.6.2.10, AS MODIFIED BY 31.3.4.5.4.
  
 31.3.4.5.4 SMOKE ALARMS REQUIRED BY 31.3.4.5.3 SHALL BE
 PERMITTED TO BE
 BATTERY POWERED.
  
  
 PLEASE INSTALL A SMOKE ALARM IN THE MASTER BEDROOM
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-04-02 Cont ID  
Sent By pleduc Date 2019-04-02 Time   Rev Time 0.00
Received By pleduc Date 2019-04-02 Time 14:00 Sent To  
Notes
2019-04-02 14:01:144/2/19
  
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) THERE IS NO INDICATION OF A SMOKE ALARM IN TWO
 BEDROOMS, PER NFPA 101, A SMOKE ALARM IS REQUIRED IN
 EACH.
  
  
 NFPA 101, CHAPTER 31,EXISTING APARTMENT BUILDINGS
  
 31.3.4.5 SMOKE ALARMS.
  
 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED
 THROUGHOUT WITH AN
 EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM,
 SMOKE ALARMS
 SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS
 MODIFIED BY 31.3.4.5.2,
 OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY
 OF THE BEDROOMS
 AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING
 BASEMENTS.
  
 31.3.4.5.3 IN BUILDINGS OTHER THAN THOSE EQUIPPED
 THROUGHOUT WITH AN
 EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM OR
 A COMPLETE,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH 31.3.5,
 SMOKE ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA
 IN
 ACCORDANCE WITH 9.6.2.10, AS MODIFIED BY 31.3.4.5.4.
  
 31.3.4.5.4 SMOKE ALARMS REQUIRED BY 31.3.4.5.3 SHALL BE
 PERMITTED TO BE
 BATTERY POWERED.
  
  
 PLEASE INSTALL A SMOKE ALARM IN THE MASTER BEDROOM
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-02-04 Cont ID  
Sent By pleduc Date 2019-02-04 Time   Rev Time 0.00
Received By pleduc Date 2019-02-04 Time 14:29 Sent To  
Notes
2019-02-04 14:30:59THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) THERE IS NO INDICATION OF A SMOKE ALARM IN TWO
 BEDROOMS, PER NFPA 101, A SMOKE ALARM IS REQUIRED IN
 EACH.
  
  
 NFPA 101, CHAPTER 31,EXISTING APARTMENT BUILDINGS
  
 31.3.4.5 SMOKE ALARMS.
  
 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED
 THROUGHOUT WITH AN
 EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM,
 SMOKE ALARMS
 SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS
 MODIFIED BY 31.3.4.5.2,
 OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY
 OF THE BEDROOMS
 AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING
 BASEMENTS.
  
 31.3.4.5.3 IN BUILDINGS OTHER THAN THOSE EQUIPPED
 THROUGHOUT WITH AN
 EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM OR
 A COMPLETE,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH 31.3.5,
 SMOKE ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA
 IN
 ACCORDANCE WITH 9.6.2.10, AS MODIFIED BY 31.3.4.5.4.
  
 31.3.4.5.4 SMOKE ALARMS REQUIRED BY 31.3.4.5.3 SHALL BE
 PERMITTED TO BE
 BATTERY POWERED.
  
  
 PLEASE INSTALL A SMOKE ALARM IN THE MASTER BEDROOM
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-05-17 Cont ID  
Sent By pvalenti Date 2019-05-17 Time 09:39 Rev Time 0.00
Received By pvalenti Date 2019-05-10 Time 13:04 Sent To  
Notes
2019-05-13 13:04:55B13

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-07 Cont ID  
Sent By pvalenti Date 2019-05-07 Time 14:58 Rev Time 0.00
Received By pvalenti Date 2019-05-01 Time 12:48 Sent To  
Notes
2019-05-02 12:48:55RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-24 Cont ID  
Sent By pvalenti Date 2019-04-24 Time 16:17 Rev Time 0.00
Received By pvalenti Date 2019-03-29 Time 13:19 Sent To  
Notes
2019-04-01 13:21:19B15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-02-21 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-29 Time 10:01 Sent To  
Notes
2019-01-31 10:01:56B18

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-05-16 Cont ID  
Sent By gjohnson Date 2019-05-16 Time 11:14 Rev Time 0.00
Received By gjohnson Date 2019-05-16 Time 07:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-09 Cont ID  
Sent By jesmith Date 2019-04-09 Time 11:33 Rev Time 0.00
Received By jesmith Date 2019-04-09 Time 11:32 Sent To  
Notes
2019-04-09 11:33:33APPROVED
 PROVISO
 1. A SEPARATE PLUMBING PERMIT IS REQUIRED
 2. SCOPE IS LIMITED TO REPLACEMENT OF EXISTING KITCHEN
 SINK AND PLUMBING CONNECTIONS TO NEW DISHWASHER AND
 REFRIGERATOR ICE MAKER, REMOVAL OF EXISTING BAR SINK
 AND CAPPING OF PLUMBING.
 3. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-02-19 Cont ID  
Sent By jesmith Date 2019-02-19 Time 14:47 Rev Time 0.00
Received By jesmith Date 2019-02-19 Time 14:32 Sent To  
Notes
2019-02-19 14:47:19APPROVED
 PROVISO
 1. A SEPARATE PLUMBING PERMIT IS REQUIRED
 2. SCOPE IS LIMITED TO REPLACEMENT OF EXISTING KITCHEN
 SINK, BAR SINK AND PLUMBING CONNECTIONS TO NEW
 DISHWASHER AND REFRIGERATOR ICE MAKER.
 3. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR?S
 APPROVAL
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved