Plan Review Details - Permit 19011247
| Plan Review Stops For Permit 19011247 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2019-06-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-06-05 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-06-05 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2019-06-05 09:40:49 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19011247 | | | ADD: 2400 PRESIDENTIAL WAY, SUITE: 1105 | | | CONT: SUNSTREAM BUILDING ENTERPRISE | | | TEL: 954-234-0892 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 5TH REVIEW | | | DATE: TUESDAY MAY 21, 2019 | | | ACTION: DENIED | | | | | | 1) OK | | | | | | 2) OK. | | | | | | 3) SHEET 1-1 UNDER THE HEADING SCOPE OF WORK LIST | | | REMOVE EXISTING FLOOR TILES AND INSTALL NEW LAMINATE | | | FLOOR OVER SOUND INSULATION. PLEASE SHOW CONFORMANCE | | | WITH: | | | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B | | | 2017) | | | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL | | | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR | | | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE | | | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A | | | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: | | | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: | | | | | | 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | RESPONSE: | | | TEST REPORT SUBMITTED IS NOT DONE IN ACCORDANCE WITH | | | ASTM E492 AS REQUIRED BY SEC. 1207.3 AND DOESN'T | | | PROVIDE THE IIC RESULTS. | | | | | | | | | | | | 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | RESPONSE: | | | NO SUBMITTED AT ALL. | | | | | | 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | RESPONSE: | | | REPEAT COMMENT. FIVE TIMES. COPY OF TESTING FOR | | | PROPOSED INSULATION WAS NOT SUBMITTED. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2019-05-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-05-21 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-05-21 |
Time |
08:41 |
Sent To |
|
|
| Notes |
| 2019-05-21 09:37:20 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19011247 | | | ADD: 2400 PRESIDENTIAL WAY, SUITE: 1105 | | | CONT: SUNSTREAM BUILDING ENTERPRISE | | | TEL: 954-234-0892 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 5TH REVIEW | | | DATE: TUESDAY MAY 21, 2019 | | | ACTION: DENIED | | | | | | 1) OK | | | | | | 2) OK. | | | | | | 3) SHEET 1-1 UNDER THE HEADING SCOPE OF WORK LIST | | | REMOVE EXISTING FLOOR TILES AND INSTALL NEW LAMINATE | | | FLOOR OVER SOUND INSULATION. PLEASE SHOW CONFORMANCE | | | WITH: | | | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B | | | 2017) | | | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL | | | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR | | | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE | | | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A | | | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: | | | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: | | | | | | 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | RESPONSE: | | | TEST REPORT SUBMITTED IS NOT DONE IN ACCORDANCE WITH | | | ASTM E492 AS REQUIRED BY SEC. 1207.3 AND DOESN'T | | | PROVIDE THE IIC RESULTS. | | | | | | | | | | | | 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | RESPONSE: | | | NO SUBMITTED AT ALL. | | | | | | 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | RESPONSE: | | | REPEAT COMMENT. FIVE TIMES. COPY OF TESTING FOR | | | PROPOSED INSULATION WAS NOT SUBMITTED. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2019-05-14 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-05-14 |
Time |
18:53 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-05-14 |
Time |
18:27 |
Sent To |
I |
|
| Notes |
| 2019-05-14 18:59:50 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19011247 | | | ADD: 2400 PRESIDENTIAL WAY, SUITE: 1105 | | | CONT: SUNSTREAM BUILDING ENTERPRISE | | | TEL: 954-234-0892 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 4TH REVIEW | | | DATE: WEDNESDAY MAY 1/2019 | | | ACTION: DENIED | | | | | | 1) SHEET 1-1 UNDER THE HEADING DESIGN CRITERIA LIST | | | THE: | | | | | | 1A) OK. | | | | | | 1B) OK. | | | | | | 1C) OK. | | | | | | 2) OK. | | | | | | 3) SHEET 1-1 UNDER THE HEADING SCOPE OF WORK LIST | | | REMOVE EXISTING FLOOR TILES AND INSTALL NEW LAMINATE | | | FLOOR OVER SOUND INSULATION. PLEASE SHOW CONFORMANCE | | | WITH: | | | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B | | | 2017) | | | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL | | | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR | | | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE | | | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A | | | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: | | | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: | | | | | | 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | RESPONSE: | | | TEST REPORT SUBMITTED IS FOR A 6" CONCRETE SLAB WITH | | | "SUSPENDED GYPSUM BOARD". TYPICALLY, BUILDINGS IN THIS | | | AREA DON'T HAVE SUSPENDED CEILINGS. PROVIDE PROOF IF | | | THIS BUILDING HAVE SUSPENDED CEILINGS AS TESTED ON | | | PRODUCT SUBMITTED OR PROVIDE COPY OF TEST THAT MATCHES | | | ACTUAL BUILDING CONSTRUCTION. | | | | | | | | | | | | 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | RESPONSE: | | | TEST REPORT SUBMITTED IS FOR A 6" CONCRETE SLAB WITH | | | "SUSPENDED GYPSUM BOARD". TYPICALLY, BUILDINGS IN THIS | | | AREA DON'T HAVE SUSPENDED CEILINGS. PROVIDE PROOF IF | | | THIS BUILDING HAVE SUSPENDED CEILINGS AS TESTED ON | | | PRODUCT SUBMITTED OR PROVIDE COPY OF TEST THAT MATCHES | | | ACTUAL BUILDING CONSTRUCTION. | | | | | | 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | RESPONSE: | | | REPEAT COMMENT. FOUR TIMES. COPY OF TESTING FOR | | | PROPOSED INSULATION WAS NOT SUBMITTED. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2019-05-01 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-05-01 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-05-01 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2019-05-01 10:08:13 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19011247 | | | ADD: 2400 PRESIDENTIAL WAY, SUITE: 1105 | | | CONT: SUNSTREAM BUILDING ENTERPRISE | | | TEL: 954-234-0892 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | DATE: WEDNESDAY MAY 1/2019 | | | ACTION: DENIED | | | | | | 1) SHEET 1-1 UNDER THE HEADING DESIGN CRITERIA LIST | | | THE: | | | | | | 1A) OK. | | | | | | 1B) OK. | | | | | | 1C) OK. | | | | | | 2) OK. | | | | | | 3) SHEET 1-1 UNDER THE HEADING SCOPE OF WORK LIST | | | REMOVE EXISTING FLOOR TILES AND INSTALL NEW LAMINATE | | | FLOOR OVER SOUND INSULATION. PLEASE SHOW CONFORMANCE | | | WITH: | | | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B | | | 2017) | | | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL | | | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR | | | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE | | | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A | | | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: | | | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: | | | | | | 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | RESPONSE: | | | REPEAT COMMENT. THREE TIMES. COPY OF TESTING FOR | | | PROPOSED INSULATION WAS NOT SUBMITTED. | | | | | | | | | 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | RESPONSE: | | | REPEAT COMMENT. THREE TIMES. COPY OF TESTING FOR | | | PROPOSED INSULATION WAS NOT SUBMITTED. | | | | | | 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | RESPONSE: | | | REPEAT COMMENT. THREE TIMES. COPY OF TESTING FOR | | | PROPOSED INSULATION WAS NOT SUBMITTED. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-04-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-04-09 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-04-08 |
Time |
18:20 |
Sent To |
|
|
| Notes |
| 2019-04-09 09:45:28 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19011247 | | | ADD: 2400 PRESIDENTIAL WAY, SUITE: 1105 | | | CONT: SUNSTREAM BUILDING ENTERPRISE | | | TEL: 954-234-0892 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: MON. FEB. 11/ 2019 | | | ACTION: DENIED | | | | | | 1) SHEET 1-1 UNDER THE HEADING DESIGN CRITERIA LIST | | | THE: | | | | | | ORIGINAL COMMENT: | | | 1A) OCCUPANCY TYPE AS R-3. PLEASE NOTE UNDER THE 2017 | | | FBC-B SECTION 310.5 IS FOR SINGLE FAMILY DWELLINGS NOT | | | FOR UNITS IN HIGHRISE BUILDINGS. SECTION 310.4 LIST | | | APARTMENTS (LONG TERM NON-TRANSIENT)AND CONDOS AS R2 | | | UNITS, PLEASE UPDATE PLANS. | | | | | | RESPONSE: | | | DESIGN CRITERIA STILL SHOWS R3 OCCUPANCY. THIS IS | | | INCORRECT AGAIN. R3 OCCUPANCY IS ONLY FOR ONE AND TWO | | | FAMILY DWELLINGS NOT CONDOMINIUMS. REVISE ORIGINAL | | | PLAN. PROVIDE CORRECT INFORMATION AND WHITE-OUT IS NOT | | | ALLOWED. SEE SEC. 310.4 FBC AND REVISE AS REQUIRED. | | | | | | 1B) OK. | | | | | | 1C) OK. | | | | | | 2) OK. | | | | | | ORIGINAL COMMENT: | | | 3) SHEET 1-1 UNDER THE HEADING SCOPE OF WORK LIST | | | REMOVE EXISTING FLOOR TILES AND INSTALL NEW LAMINATE | | | FLOOR OVER SOUND INSULATION. PLEASE SHOW CONFORMANCE | | | WITH: | | | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B | | | 2017) | | | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL | | | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR | | | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE | | | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A | | | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: | | | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: | | | | | | 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | RESPONSE: | | | NOT ADDRESSED. COPY OF TESTING FOR PROPOSED INSULATION | | | WAS NOT SUBMITTED. | | | | | | 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | RESPONSE: | | | NOT ADDRESSED. COPY OF TESTING FOR PROPOSED INSULATION | | | WAS NOT SUBMITTED. | | | | | | 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | RESPONSE: | | | NOT ADDRESSED. COPY OF TESTING FOR PROPOSED INSULATION | | | WAS NOT SUBMITTED. | | | | | | | | | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-02-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2019-02-11 |
Time |
12:35 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2019-02-11 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2019-02-11 12:35:56 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19011247 | | | ADD: 2400 PRESIDENTIAL WAY, SUITE: 1105 | | | CONT: SUNSTREAM BUILDING ENTERPRISE | | | TEL: 954-234-0892 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: MON. FEB. 11/ 2019 | | | ACTION: DENIED | | | | | | 1) SHEET 1-1 UNDER THE HEADING DESIGN CRITERIA LIST | | | THE: | | | | | | 1A) OCCUPANCY TYPE AS R-3. PLEASE NOTE UNDER THE 2017 | | | FBC-B SECTION 310.5 IS FOR SINGLE FAMILY DWELLINGS NOT | | | FOR UNITS IN HIGHRISE BUILDINGS. SECTION 310.4 LIST | | | APARTMENTS (LONG TERM NON-TRANSIENT)AND CONDOS AS R2 | | | UNITS, PLEASE UPDATE PLANS. | | | | | | 1B) THIS SHEET LIST THE CONSTRUCTION TYPE AS V-B. | | | PLEASE UPDATE THE PLANS, THIS BUILDING IS A HIGHRISE | | | AND WILL NEED TO SHOW A CONSTRUCTION TYPE: I-A | | | NON-SPRINKLERED FOOTNOTE D. 2017 FBC-B TABLE 506.2. | | | | | | 1C) THE PLAN ALSO INDICATES AN ALTERATION LEVEL I. | | | PLEASE NOTE THIS ALTERATION LEVEL IS CONSIDERED A LEVEL | | | II ALTERATION. PLEASE REVIEW THE 2017 FBC-EXISTING | | | BUILDING CODE SECTION 504.1 LEVEL 2 ALTERATION. LEVEL 2 | | | ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE, THE | | | ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW, THE | | | RECONFIGURATION OR EXTENSION OF ANY SYSTEM, OR THE | | | INSTALLATION OF ANY ADDITIONAL EQUIPMENT. | | | THE RELOCATION OF THE WASHER/ DRYER WOULD BE THE | | | ADDITION TO A SYSTEM. | | | | | | 2) SHEET 1-1 UNDER THE HEADING APPLICABLE CODES THE | | | 2017 RESIDENTIAL CODE IS STATED. PLEASE NOTE THE ONLY | | | TIME THE RESIDENTIAL CODE IS USED IS IN ONE & TWO | | | FAMILY DWELLINGS NOT WHEN IN HIGH-RISES. | | | 2017 FBC-RESIDENTIAL CODE, R101.2 SCOPE. THE PROVISIONS | | | OF THE FLORIDA BUILDING CODE, RESIDENTIAL SHALL APPLY | | | TO THE CONSTRUCTION, ALTERATION, MOVEMENT, ENLARGEMENT, | | | REPLACEMENT, REPAIR, EQUIPMENT, USE AND OCCUPANCY, | | | LOCATION, REMOVAL AND DEMOLITION OF DETACHED ONE- AND | | | TWO-FAMILY DWELLINGS AND TOWNHOUSES NOT MORE THAN THREE | | | STORIES ABOVE GRADE PLANE IN HEIGHT WITH A SEPARATE | | | MEANS OF EGRESS AND THEIR ACCESSORY STRUCTURES NOT MORE | | | THAN THREE STORIES ABOVE GRADE PLANE IN HEIGHT. | | | 3) SHEET 1-1 UNDER THE HEADING SCOPE OF WORK LIST | | | REMOVE EXISTING FLOOR TILES AND INSTALL NEW LAMINATE | | | FLOOR OVER SOUND INSULATION. PLEASE SHOW CONFORMANCE | | | WITH: | | | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B | | | 2017) | | | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL | | | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR | | | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE | | | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A | | | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: | | | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: | | | | | | 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2019-05-13 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-05-13 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-05-13 |
Time |
15:51 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2019-05-06 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-05-06 |
Time |
07:54 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-05-06 |
Time |
07:54 |
Sent To |
I |
|
| Notes |
| 2019-05-06 07:54:27 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | | 109.3 | | | 2. NO INFORMATION PROVIDED ABOUT VALUE. | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | ELECTRICAL PLANS EXAMINER / CHIEF ELECTRICAL INSPECTOR | | | 561-805-6742 | | | [email protected] | | | | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | | 109.3 (NOT ADDRESSED.) | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2019-04-16 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2019-04-16 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2019-04-16 |
Time |
09:13 |
Sent To |
|
|
| Notes |
| 2019-04-16 09:13:11 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | | 109.3 | | | 2. NO INFORMATION PROVIDED ABOUT VALUE. | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | ELECTRICAL PLANS EXAMINER / CHIEF ELECTRICAL INSPECTOR | | | 561-805-6742 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-02-21 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-02-21 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-02-21 |
Time |
10:30 |
Sent To |
I |
|
| Notes |
| 2019-04-16 09:10:25 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | | 109.3 | | | 2. NO INFORMATION PROVIDED ABOUT VALUE. | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | ELECTRICAL PLANS EXAMINER / CHIEF ELECTRICAL INSPECTOR | | | 561-805-6742 | | | [email protected] | | | | | | | | 2019-02-21 14:05:18 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | | 109.3 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2019-04-29 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-04-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-04-29 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2019-04-29 15:02:24 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) THERE IS NO INDICATION OF A SMOKE ALARM IN THE AREA | | | OF THE MASTER BEDROOM, PER NFPA 101, A SMOKE ALARM IS | | | REQUIRED. | | | | | | | | | NFPA 101, CHAPTER 31,EXISTING APARTMENT BUILDINGS | | | | | | 31.3.4.5 SMOKE ALARMS. | | | | | | 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED | | | THROUGHOUT WITH AN | | | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM, | | | SMOKE ALARMS | | | SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS | | | MODIFIED BY 31.3.4.5.2, | | | OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY | | | OF THE BEDROOMS | | | AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING | | | BASEMENTS. | | | | | | 31.3.4.5.3 IN BUILDINGS OTHER THAN THOSE EQUIPPED | | | THROUGHOUT WITH AN | | | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM OR | | | A COMPLETE, | | | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE | | | WITH 31.3.5, | | | SMOKE ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA | | | IN | | | ACCORDANCE WITH 9.6.2.10, AS MODIFIED BY 31.3.4.5.4. | | | | | | 31.3.4.5.4 SMOKE ALARMS REQUIRED BY 31.3.4.5.3 SHALL BE | | | PERMITTED TO BE | | | BATTERY POWERED. | | | | | | | | | PLEASE INSTALL A SMOKE ALARM IN THE MASTER BEDROOM | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-03-21 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-03-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-03-21 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2019-03-21 15:24:13 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) THERE IS NO INDICATION OF A SMOKE ALARM IN THE AREA | | | OF THE MASTER BEDROOM, PER NFPA 101, A SMOKE ALARM IS | | | REQUIRED. | | | | | | | | | NFPA 101, CHAPTER 31,EXISTING APARTMENT BUILDINGS | | | | | | 31.3.4.5 SMOKE ALARMS. | | | | | | 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED | | | THROUGHOUT WITH AN | | | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM, | | | SMOKE ALARMS | | | SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS | | | MODIFIED BY 31.3.4.5.2, | | | OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY | | | OF THE BEDROOMS | | | AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING | | | BASEMENTS. | | | | | | 31.3.4.5.3 IN BUILDINGS OTHER THAN THOSE EQUIPPED | | | THROUGHOUT WITH AN | | | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM OR | | | A COMPLETE, | | | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE | | | WITH 31.3.5, | | | SMOKE ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA | | | IN | | | ACCORDANCE WITH 9.6.2.10, AS MODIFIED BY 31.3.4.5.4. | | | | | | 31.3.4.5.4 SMOKE ALARMS REQUIRED BY 31.3.4.5.3 SHALL BE | | | PERMITTED TO BE | | | BATTERY POWERED. | | | | | | | | | PLEASE INSTALL A SMOKE ALARM IN THE MASTER BEDROOM | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2019-02-04 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-02-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-02-04 |
Time |
13:33 |
Sent To |
|
|
| Notes |
| 2019-02-04 13:44:35 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) THERE IS NO INDICATION OF A SMOKE ALARM IN THE AREA | | | OF THE MASTER BEDROOM, PER NFPA 101, A SMOKE ALARM IS | | | REQUIRED. | | | | | | | | | NFPA 101, CHAPTER 31,EXISTING APARTMENT BUILDINGS | | | | | | 31.3.4.5 SMOKE ALARMS. | | | | | | 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED | | | THROUGHOUT WITH AN | | | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM, | | | SMOKE ALARMS | | | SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS | | | MODIFIED BY 31.3.4.5.2, | | | OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY | | | OF THE BEDROOMS | | | AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING | | | BASEMENTS. | | | | | | 31.3.4.5.3 IN BUILDINGS OTHER THAN THOSE EQUIPPED | | | THROUGHOUT WITH AN | | | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM OR | | | A COMPLETE, | | | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE | | | WITH 31.3.5, | | | SMOKE ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA | | | IN | | | ACCORDANCE WITH 9.6.2.10, AS MODIFIED BY 31.3.4.5.4. | | | | | | 31.3.4.5.4 SMOKE ALARMS REQUIRED BY 31.3.4.5.3 SHALL BE | | | PERMITTED TO BE | | | BATTERY POWERED. | | | | | | | | | PLEASE INSTALL A SMOKE ALARM IN THE MASTER BEDROOM | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2019-06-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-06-05 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-06-03 |
Time |
15:25 |
Sent To |
I |
|
| Notes |
| 2019-06-04 15:25:29 | RESUB ROUTED TO JGOMEZ |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2019-05-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-05-21 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-05-17 |
Time |
14:53 |
Sent To |
I |
|
| Notes |
| 2019-05-20 14:53:29 | RESUB ROUTED TO JGOMEZ |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2019-05-14 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-05-14 |
Time |
19:00 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-05-10 |
Time |
13:08 |
Sent To |
I |
|
| Notes |
| 2019-05-13 13:08:58 | RESUB ROUTED TO JPEARSON |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-05-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-04-22 |
Time |
10:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-04-16 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2019-04-16 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2019-03-19 |
Time |
14:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-02-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-01-29 |
Time |
10:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2019-04-04 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-04-04 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-04-04 |
Time |
15:44 |
Sent To |
|
|
| Notes |
| 2019-04-04 15:48:19 | APPROVED | | | ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S | | | APPROVAL | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-02-19 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-02-19 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-02-19 |
Time |
15:05 |
Sent To |
|
|
| Notes |
| 2019-02-19 15:05:32 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | 1ST REVIEW: DENIED | | | | | | 1. PER PER WPB FBC 107.2.1, PROVIDE A CODE COMPLIANT | | | SANITARY RISER DIAGRAM (TWO COPIES) SIGNED BY YOUR | | | PLUMBING CONTRACTOR ALONG WITH HIS CONTRACTOR NUMBER, | | | SHOWING WHERE AND HOW THE CLOTHES WASHER FIXTURE DRAIN | | | WILL CONNECT TO THE EXISTING SANITARY SOIL/WASTE STACK, | | | AND THE VENT SHOWING WHERE AND HOW IT WILL CONNECT TO | | | THE EXISTING VENT SYSTEM. | | | 2. PER PER WPB FBC 107.2.1, SHOW THE ROUTING OF THE NEW | | | FIXTURE DRAIN AND VENT AS WELL AS THE LOCATIONS OF THE | | | EXISTING SOIL/WASTE STACK AND VENT STACK ON THE FLOOR | | | PLAN. | | | 3. PER PER WPB FBC 107.2.1, PROVIDE A NOTE ON THE PLAN | | | DESCRIBING WHERE THE CLOTHES WASHER WATER SUPPLY IS TO | | | BE CONNECTED TO. | | | | | | SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS, | | | ESPECIALLY AS A RESULT OF RESPONSE TO BUILDING REVIEW | | | COMMENTS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 |
|
|
|