| 2019-02-12 11:45:59 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19011234 |
| | ADD: 625 N FLAGLER DR. / ROOFTOP REPLACEMENT OF STEEL & |
| | MECHANICAL EQUIPMENT |
| | CONT: RPM&M GENERAL CONTRACTORS, INC. |
| | TEL: 954-649-5304 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. FEB. 12/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE THE COMPANY NAME (DBA) LISTED ON THE |
| | PERMIT APPLICATION IS RPM & M. THERE IS NO SUCH LISTING |
| | WITH THE DBPR FOR THE LICENSE NUMBER CGC1522801. THERE |
| | IS HOWEVER A DBA LISTED FOR REAVY PROPERTY MANAGEMENT & |
| | MAINTENANCE. |
| | |
| | 2) PLEASE NOTE THE WORK TO BE COMPLETED UNDER THIS |
| | PERMIT, THE BUILDING QUALIFIES AS A THRESHOLD BUILDING. |
| | FL S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY |
| | BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY |
| | CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE |
| | WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | |
| | 2A) MISSING. 109.3.6.1 THRESHOLD INSPECTION PLAN. THE |
| | ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | 2B) SEMI-COMPLIED. SUBMITTED THRESHOLD / SPECIAL |
| | INSPECTOR AGREEMENT. ONLY ONE OF THE JOBSITE INSPECTORS |
| | QUALIFIES CHARLES MOCK. THE VIRGINIA EIT SHUBHAM |
| | PUTTABOREGOWDA IS ELIGIBLE FOR THE EXAM BUT TO DATE HAS |
| | NOT PASSED THE EXAM. HE HAS BEEN STRUCK AND NOT |
| | ELIGIBLE UNDER FLORIDA STATUTE 553.79(5) AND THE 2017 |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION SECTION: |
| | 110.8.6 THE BUILDING DEPARTMENT MAY ALLOW A SPECIAL |
| | INSPECTOR TO CONDUCT THE MINIMUM STRUCTURAL INSPECTION |
| | OF THRESHOLD BUILDINGS REQUIRED BY THIS CODE, SECTION |
| | 553.73, FLORIDA STATUTES, WITHOUT DUPLICATIVE |
| | INSPECTION BY THE BUILDING DEPARTMENT. THE BUILDING |
| | OFFICIAL IS RESPONSIBLE FOR ENSURING THAT ANY PERSON |
| | CONDUCTING INSPECTIONS IS QUALIFIED AS A BUILDING |
| | INSPECTOR UNDER PART XII OF CHAPTER 468, FLORIDA |
| | STATUTES, OR CERTIFIED AS A SPECIAL INSPECTOR UNDER |
| | CHAPTER 471 OR 481, FLORIDA STATUTES. INSPECTIONS OF |
| | THRESHOLD BUILDINGS REQUIRED BY SECTION 553.79(5), |
| | FLORIDA STATUTES, ARE IN ADDITION TO THE MINIMUM |
| | INSPECTIONS REQUIRED BY THIS CODE. |
| | 2C) THE STRUCTURAL PLANS WILL ALSO NEED TO SUPPLY A |
| | STRUCTURAL INSPECTION PLAN AND MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | 2017 CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION SECTION: |
| | 110.8.1. |
| | |
| | 2D) PLEASE SHOW COMPLIANCE WITH 2017 CITY OF WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION SECTION: |
| | 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED |
| | TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| | ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| | BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS |
| | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| | THIS SECTION AND CHAPTER 633. FLORIDA STATUTES. |
| | |
| | 2E) PLEASE NOTE ONLY 2 SETS OF PLANS WERE SUBMITTED. |
| | NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE REQUIRED, |
| | (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP |
| | INSPECTORS.2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | 110.3.7 THRESHOLD BUILDINGS, GUIDELINES AND POLICIES |
| | FOR PROJECTS CONCERNING SPECIAL INSPECTORS. |
| | |
| | 2F) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL |
| | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |