Plan Review Details - Permit 19011234
Plan Review Stops For Permit 19011234
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-13 Cont ID  
Sent By pvalenti Date 2019-05-13 Time 16:37 Rev Time 0.00
Received By pvalenti Date 2019-05-13 Time 16:37 Sent To  
Notes
2019-05-13 16:56:52 
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND BUILDING PLAN REVIEW APPROVED:
  
 TWO COMPLETE SETS OF PLANS AND A THIRD SET OF
 STRUCTURALS HAVE BEEN SUBMITTED ALONG WITH MECHANICAL
 PAGES.
 PROVISO: AT TIME OF INSPECTION PROVIDE A WELDING
 PROCEDURE SPECIFICATION AND THE QUALIFICATION RECORDS
 OF WELDING PERSONNEL.
  
 NOTE: PLEASE PROVIDE RESUMES FOR THE THRESHOLD
 INSPECTOR (BIJAN PARSSI) AND THE THRESHOLD INSPECTOR'S
 FIELD REPRESENTATIVE (CHARLES MOCK) AND PRIOR TO
 PICKING UP PERMIT.
 ALSO THE CURRENT CONTRACTOR NEEDS TO SIGN AND COMPLETE
 THE LICENSED CONTRACTOR SECTION OF THE
 THRESHOLD/SPECIAL INSPECTOR AGREEMENT PRIOR TO PICKING
 UP PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-12 Cont ID  
Sent By jwitmer Date 2019-02-12 Time 11:46 Rev Time 0.00
Received By jwitmer Date 2019-02-11 Time 13:23 Sent To  
Notes
2019-02-12 11:45:592017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19011234
 ADD: 625 N FLAGLER DR. / ROOFTOP REPLACEMENT OF STEEL &
 MECHANICAL EQUIPMENT
 CONT: RPM&M GENERAL CONTRACTORS, INC.
 TEL: 954-649-5304
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 12/ 2019
 ACTION: DENIED
  
 1) PLEASE NOTE THE COMPANY NAME (DBA) LISTED ON THE
 PERMIT APPLICATION IS RPM & M. THERE IS NO SUCH LISTING
 WITH THE DBPR FOR THE LICENSE NUMBER CGC1522801. THERE
 IS HOWEVER A DBA LISTED FOR REAVY PROPERTY MANAGEMENT &
 MAINTENANCE.
  
 2) PLEASE NOTE THE WORK TO BE COMPLETED UNDER THIS
 PERMIT, THE BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 FL S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 2A) MISSING. 109.3.6.1 THRESHOLD INSPECTION PLAN. THE
 ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED)
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B) SEMI-COMPLIED. SUBMITTED THRESHOLD / SPECIAL
 INSPECTOR AGREEMENT. ONLY ONE OF THE JOBSITE INSPECTORS
 QUALIFIES CHARLES MOCK. THE VIRGINIA EIT SHUBHAM
 PUTTABOREGOWDA IS ELIGIBLE FOR THE EXAM BUT TO DATE HAS
 NOT PASSED THE EXAM. HE HAS BEEN STRUCK AND NOT
 ELIGIBLE UNDER FLORIDA STATUTE 553.79(5) AND THE 2017
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION SECTION:
 110.8.6 THE BUILDING DEPARTMENT MAY ALLOW A SPECIAL
 INSPECTOR TO CONDUCT THE MINIMUM STRUCTURAL INSPECTION
 OF THRESHOLD BUILDINGS REQUIRED BY THIS CODE, SECTION
 553.73, FLORIDA STATUTES, WITHOUT DUPLICATIVE
 INSPECTION BY THE BUILDING DEPARTMENT. THE BUILDING
 OFFICIAL IS RESPONSIBLE FOR ENSURING THAT ANY PERSON
 CONDUCTING INSPECTIONS IS QUALIFIED AS A BUILDING
 INSPECTOR UNDER PART XII OF CHAPTER 468, FLORIDA
 STATUTES, OR CERTIFIED AS A SPECIAL INSPECTOR UNDER
 CHAPTER 471 OR 481, FLORIDA STATUTES. INSPECTIONS OF
 THRESHOLD BUILDINGS REQUIRED BY SECTION 553.79(5),
 FLORIDA STATUTES, ARE IN ADDITION TO THE MINIMUM
 INSPECTIONS REQUIRED BY THIS CODE.
 2C) THE STRUCTURAL PLANS WILL ALSO NEED TO SUPPLY A
 STRUCTURAL INSPECTION PLAN AND MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 2017 CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION SECTION:
 110.8.1.
  
 2D) PLEASE SHOW COMPLIANCE WITH 2017 CITY OF WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION SECTION:
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633. FLORIDA STATUTES.
  
 2E) PLEASE NOTE ONLY 2 SETS OF PLANS WERE SUBMITTED.
 NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE REQUIRED,
 (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 110.3.7 THRESHOLD BUILDINGS, GUIDELINES AND POLICIES
 FOR PROJECTS CONCERNING SPECIAL INSPECTORS.
  
 2F) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-02-22 Cont ID  
Sent By jpearson Date 2019-02-22 Time 09:39 Rev Time 0.00
Received By jpearson Date 2019-02-22 Time 07:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-04-19 Cont ID  
Sent By scaldero Date 2019-04-19 Time 10:58 Rev Time 0.00
Received By scaldero Date 2019-04-19 Time 10:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-02-06 Cont ID  
Sent By scaldero Date 2019-02-06 Time 10:32 Rev Time 0.00
Received By scaldero Date 2019-02-06 Time 10:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-13 Cont ID  
Sent By pvalenti Date 2019-05-13 Time 17:40 Rev Time 0.00
Received By pvalenti Date 2019-04-17 Time 15:10 Sent To  
Notes
2019-04-18 15:10:52B34

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-26 Cont ID  
Sent By jesmith Date 2019-02-26 Time 09:47 Rev Time 0.00
Received By jesmith Date 2019-02-26 Time 09:47 Sent To  
Notes
2019-02-21 14:45:38ROUTED FROM ZONING TO PERMIT LIBRARIAN 2/21/2019 EL
2019-01-31 09:57:42B31

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-05-06 Cont ID  
Sent By ccole Date 2019-05-06 Time 11:37 Rev Time 0.00
Received By ccole Date 2019-05-06 Time 11:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-02-25 Cont ID  
Sent By ccole Date 2019-02-25 Time 17:15 Rev Time 0.00
Received By ccole Date 2019-02-25 Time 16:55 Sent To P
Notes
2019-02-25 17:23:181ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19011234
 2/25/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMISSIONING OF THE NEW HVAC SYSTEMS IS REQUIRED
 PER SECTION C408.2 FBC-17 ENERGY CONSERVATION. SUBMIT A
 COMMISSIONING PLAN AS OUTLINED IN SECTION C408.2.1 AND
 DESCRIBED IN SECTIONS C403.2.2- C408.2.3.3. PLEASE NOTE
 THAT A COPY OF THE COMMISSIONING REPORT SHALL BE
 SUBMITTED FOR REVIEW AT FINAL INSPECTION.
  
 2) SHOW THE LOCATIONS OF THE REQUIRED DUCT SMOKE
 DETECTORS IN THE SUPPLY AIR SYSTEMS OF THE NEW AIR
 HANDLERS- SECTION 606.2.1 FBC M
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-05-01 Cont ID  
Sent By thunt Date 2019-05-01 Time 08:08 Rev Time 0.00
Received By thunt Date 2019-05-01 Time 07:31 Sent To  
Notes
2019-05-01 08:09:59PLUMBING SHEETS ADDED PER JERRY SMITH PROVISO COMMENTS.
 JERRY'S APPROVAL STAMP IS STILL ON M- PAGES WITH
 PROVISO BUT ANSWER ON P SHEETS. THUNT

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-02-26 Cont ID  
Sent By jesmith Date 2019-02-26 Time 09:46 Rev Time 0.00
Received By jesmith Date 2019-02-26 Time 09:46 Sent To  
Notes
2019-02-26 09:46:53APPROVED
 PROVISO
 1. A PLUMBING PERMIT IS REQUIRED
 2. A SEPARATE PERMIT IS REQUIRED FOR THE NEW BACKFLOW
 PREVENTOR (SEE M-300 P&ID) PROVIDED FOR MAKE UP WATER
 FOR NEW CHILLED WATER SYSTEM. PROVIDE CERTIFICATION
 DOCUMENTS AT FINAL INSPECTION.
 3. REGARDING EXISTING BACKFLOW PREVENTER FOR MAKE UP
 WATER TO THE COOLING TOWERS (SEE M-201 PHOTO; EXISTING
 CONDITIONS), PROVIDE CURRENT CERTIFICATION DOCUMENTS
 PROVIDED WITHIN THE PREVIOUS TWO YEARS OR NEW DOCUMENTS
 AT FINAL INSPECTION.
 4. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR?S
 APPROVAL

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2019-05-14 Cont ID  
Sent By pvalenti Date 2019-05-13 Time 17:02 Rev Time 0.00
Received By pvalenti Date 2019-05-13 Time 16:57 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2019-02-12 Cont ID  
Sent By jwitmer Date 2019-02-12 Time 11:48 Rev Time 0.00
Received By jwitmer Date 2019-02-11 Time 13:23 Sent To  
Notes
2019-02-12 11:47:492017 FBC- BUILDING PLAN REVIEW/ THRESHOLD
 W. P. B. PERMIT: 19011234
 ADD: 625 N FLAGLER DR. / ROOFTOP REPLACEMENT OF STEEL &
 MECHANICAL EQUIPMENT
 CONT: RPM&M GENERAL CONTRACTORS, INC.
 TEL: 954-649-5304
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 12/ 2019
 ACTION: DENIED
  
 1) PLEASE NOTE THE WORK TO BE COMPLETED UNDER THIS
 PERMIT, THE BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 FL S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 1A) MISSING. 109.3.6.1 THRESHOLD INSPECTION PLAN. THE
 ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED)
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 1B) SEMI-COMPLIED. SUBMITTED THRESHOLD / SPECIAL
 INSPECTOR AGREEMENT. ONLY ONE OF THE JOBSITE INSPECTORS
 QUALIFIES CHARLES MOCK. THE VIRGINIA EIT SHUBHAM
 PUTTABOREGOWDA IS ELIGIBLE FOR THE EXAM BUT TO DATE HAS
 NOT PASSED THE EXAM. HE HAS BEEN STRUCK AND NOT
 ELIGIBLE UNDER FLORIDA STATUTE 553.79(5) AND THE 2017
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION SECTION:
 110.8.6 THE BUILDING DEPARTMENT MAY ALLOW A SPECIAL
 INSPECTOR TO CONDUCT THE MINIMUM STRUCTURAL INSPECTION
 OF THRESHOLD BUILDINGS REQUIRED BY THIS CODE, SECTION
 553.73, FLORIDA STATUTES, WITHOUT DUPLICATIVE
 INSPECTION BY THE BUILDING DEPARTMENT. THE BUILDING
 OFFICIAL IS RESPONSIBLE FOR ENSURING THAT ANY PERSON
 CONDUCTING INSPECTIONS IS QUALIFIED AS A BUILDING
 INSPECTOR UNDER PART XII OF CHAPTER 468, FLORIDA
 STATUTES, OR CERTIFIED AS A SPECIAL INSPECTOR UNDER
 CHAPTER 471 OR 481, FLORIDA STATUTES. INSPECTIONS OF
 THRESHOLD BUILDINGS REQUIRED BY SECTION 553.79(5),
 FLORIDA STATUTES, ARE IN ADDITION TO THE MINIMUM
 INSPECTIONS REQUIRED BY THIS CODE.
 1C) THE STRUCTURAL PLANS WILL ALSO NEED TO SUPPLY A
 STRUCTURAL INSPECTION PLAN AND MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 2017 CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION SECTION:
 110.8.1.
  
 1D) PLEASE SHOW COMPLIANCE WITH 2017 CITY OF WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION SECTION:
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633. FLORIDA STATUTES.
  
 1E) PLEASE NOTE ONLY 2 SETS OF PLANS WERE SUBMITTED.
 NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE REQUIRED,
 (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 110.3.7 THRESHOLD BUILDINGS, GUIDELINES AND POLICIES
 FOR PROJECTS CONCERNING SPECIAL INSPECTORS.
  
 1F) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2019-02-21 Cont ID  
Sent By aaponte Date 2019-02-21 Time 14:44 Rev Time 0.00
Received By elevesqu Date 2019-02-21 Time 14:44 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved