Plan Review Details - Permit 19011075
Plan Review Stops For Permit 19011075
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-07-18 Cont ID  
Sent By cthroop Date 2019-07-18 Time 15:33 Rev Time 0.00
Received By cthroop Date 2019-07-18 Time 13:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-07-09 Cont ID  
Sent By cthroop Date 2019-07-09 Time 07:40 Rev Time 0.00
Received By cthroop Date 2019-07-05 Time 16:15 Sent To  
Notes
2019-07-09 07:45:07BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 2ND REQUEST
  
 1. PROVIDE PRODUCT APPROVALS FOR EACH TYPE OF WINDOW,
 WINDOW MULLIONS AND EXTERIOR DOOR. PRODUCT APPROVALS TO
 BE REVIEWED AND APPROVED BY DESIGNER OF RECORD.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW, WINDOW MULLION AND DOOR
 SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-05-30 Cont ID  
Sent By cthroop Date 2019-05-30 Time 16:56 Rev Time 0.00
Received By cthroop Date 2019-05-24 Time 17:26 Sent To  
Notes
2019-05-30 17:03:41BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. PROVIDE PRODUCT APPROVALS FOR ALL NEW WINDOWS AND
 EXTERIOR DOORS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW, MULLIONS AND DOOR
 SUBMITTALS.
  
 NOTE: THERE IS AN OPTION FOR SUBMITTING PRODUCT
 APPROVALS AT THIS TIME.
  
 107.3.4.1 DEFERRED SUBMITTALS: FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2. SCOPE OF WORK STATES WORK TO BE DONE IN BATH #2. ALL
 PLAN PAGES LIST BATH#2 AS BATH #1. PLEASE CLARIFY.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. REFERENCE PLAN PAGE A1. BUILDING CODE INFORMATION.
 CLASSIFICATION OF WORK SHOULD READ LEVEL 2 ALTERATION.
 PLEASE CLARIFY.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-08 Cont ID  
Sent By cthroop Date 2019-02-08 Time 09:27 Rev Time 0.00
Received By cthroop Date 2019-02-07 Time 07:22 Sent To  
Notes
2019-02-08 09:30:16BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
  
 1. PROVIDE SITE PLAN. PALM BEACH COUNTY PROPERETY
 APPRAISERS OFFICE SHOWS TWO STRUCTURES ON PROPERTY.
 IDENTIFY WHICH STRUCTURE SCOPE OF WORK APPLIES TO.
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY.
  
 2. PROVIDE EXISTING FLOOR PLAN AND PROPOSED FLOOR PLAN.
 CANNOT DETERMINE NEW WORK.
 PROVIDE FLOOR PLAN.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 3. VALUE CANNOT BE VERIFIED UNTIL FLOOR PLAN WITH
 COMPREHENSIVE SCOPE OF WORK HAS BEEN PROVIDED.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 4. IMPACT FEES. BASED ON THE NOTE ON THE A/C CHANGE OUT
 FORM WHICH STATES NO EXISTING MECHANICAL SYSTEM EXISTS,
 PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED BASED ON
 THE ADDITION OF CONDITIONED HABITABLE SPACE.
  
 5. DESIGNER TO PRINT NAME AND SIGN PLAN.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-07-18 Cont ID  
Sent By cthroop Date 2019-07-18 Time 15:34 Rev Time 0.00
Received By cthroop Date 2019-07-18 Time 13:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-07-09 Cont ID  
Sent By cthroop Date 2019-07-09 Time 08:19 Rev Time 0.00
Received By cthroop Date 2019-07-05 Time 16:15 Sent To  
Notes
2019-07-09 08:26:01ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THE FOLLOWING IS A RE-PEAT COMMENT FROM PREVIOUS REVIEW
  
 1. PROVIDE SERVICE OUTLET FOR MECHANICAL EQUIPMENT AT
 GUEST HOUSE.
 E3901.12
  
 THE FOLLOWING ARE NEW COMMENTS
  
 1. FEEDER SERVICE AT GUEST HOUSE REQUIRES TWO (2)
 GROUND RODS.
 E3607.3
  
 2. FEEDER SERVICE AT GUEST HOUSE REQUIRES MAIN MEANS OF
 DISCONNECT.
 E3706.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-05-30 Cont ID  
Sent By cthroop Date 2019-05-30 Time 17:20 Rev Time 0.00
Received By cthroop Date 2019-05-24 Time 17:26 Sent To  
Notes
2019-05-30 17:41:07ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. PROVIDE A RISER DIAGRAHM. INCLUDE MAIN HOUSE AND SUB
 - PANEL FOR GUEST HOUSE. DEMONSTRATE HOW GUEST HOUSE IS
 ENERGIZED.
  
 PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S).
 SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC
 107.2.1
  
 A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT. NEC 225.30
  
 PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
  
 FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32
  
 2. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS
 PERMITTED. WPB FBC 107.2.1; NEC 230.2; FBC RE E3601.2.
  
 3. GROUNDING ELECTRODE SYSTEM
 NEC 250.32; FBC RE E3607.3
 A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF
 GROUNDING ELECTRODE SYSTEM AND WIRING.
  
 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3.
  
 5. LOAD CALC.:
 PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS.
 NEC 220; FBC RE E3602.2
 PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2.
  
 5A. LOAD CALC. PROVIDED DOES NOT INCLUDE THE MECHANICAL
 SYSTEMS AND THE SUB-PANEL TO THE GUEST HOUSE.
  
 6. PROVIDE GFCI PROTECTED OUTLET FOR DISHWASHER.
 GFCI PROTECTION FOR DISHWASHERS. NEC 210.8(D); FBC RE
 E3902.10.
  
 7. PROVIDE SMOKE ALARM LAYOUT.
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
  
 8. PROVIDE OUTLETS AT KITCHEN ISLAND.
 E3902.6 KITCHEN RECEPTACLES.
  
 9. ALL LAUNDRY OUTLETS SHALL BE GFCI PROTECTED.
 RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3902.9.
  
 10. PROVIDE SERVICE OUTLETS FOR MECHANICAL EQUIPMENT.
 E3901.12 HVAC OUTLET.
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM)
 OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED
 TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING
 MEANS. (210.63)
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-08 Cont ID  
Sent By cthroop Date 2019-02-08 Time 10:20 Rev Time 0.00
Received By cthroop Date 2019-02-07 Time 07:22 Sent To  
Notes
2019-02-08 10:26:42ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
  
 1. PROVIDE EXISTING/PROPOSED FLOOR PLAN. IDENTIFY ALL
 NEW DEVICES.
 2. IF NEW CIRCUTS ARE ADDED, PROVIDE ELECTRICAL RISER
 DIAGRAHM WITH NEW LOAD CALC'S.
 3. SHOW DEDICATED SMALL APPLIANCE CIRCUTS TO KITCHEN.
 4. SHOW LOCATION OF REQUIRED KITCHEN COUNTER OUTLETS.
 5. CONTRACTOR TO PRINT NAME AND SIGN NAME.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2019-07-18 Cont ID  
Sent By fmittner Date 2019-07-18 Time 10:58 Rev Time 0.00
Received By fmittner Date 2019-07-18 Time 10:58 Sent To B
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-07-03 Cont ID  
Sent By fmittner Date 2019-07-03 Time 14:32 Rev Time 0.00
Received By fmittner Date 2019-07-03 Time 14:31 Sent To B
Notes
2019-07-03 14:32:53NO PRODUCT APPROVALS FOR CASEMENTS SUPPLIED, HOWEVER
 WINDOW SCHEDULE INDICATES CASEMENTS IN FRONT.
  
 THIS WINDOW SCOPE SHALL FOCUS JUST ON KITCHEN AREA.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2019-05-21 Cont ID  
Sent By fmittner Date 2019-05-21 Time 16:40 Rev Time 0.00
Received By fmittner Date 2019-05-21 Time 16:40 Sent To B
Notes
2019-05-21 16:42:53NEED DETAILS (FRAME MATERIAL, FRAME COLOR, GLASS COLOR,
 MUNTIN PATTERN) AND PRODUCT APPROVALS FOR WINDOWS.
 REQUIRES CONFIRMATION FOR SECOND KITCHEN ON SITE.
  
 QUESTIONS, CONTACT: FRIEDERIKE MITTNER, CITY HSITORIC
 PRESERVATION PLANNER AT (561) 822-1457

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2019-07-22 Cont ID  
Sent By cthroop Date 2019-07-22 Time 13:48 Rev Time 0.00
Received By cthroop Date 2019-07-22 Time 13:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status P Date 2019-07-22 Cont ID  
Sent By cthroop Date 2019-07-22 Time 13:45 Rev Time 0.00
Received By cthroop Date 2019-07-22 Time 13:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-07-18 Cont ID  
Sent By cthroop Date 2019-07-18 Time 15:34 Rev Time 0.00
Received By cthroop Date 2019-07-16 Time 15:30 Sent To  
Notes
2019-07-17 15:30:48RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-09 Cont ID  
Sent By cthroop Date 2019-07-09 Time 08:52 Rev Time 0.00
Received By cthroop Date 2019-06-21 Time 14:37 Sent To  
Notes
2019-06-24 14:37:19RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-30 Cont ID  
Sent By cthroop Date 2019-05-30 Time 17:41 Rev Time 0.00
Received By cthroop Date 2019-05-17 Time 13:42 Sent To  
Notes
2019-05-20 13:42:32RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2019-02-08 Cont ID  
Sent By cthroop Date 2019-02-08 Time 10:26 Rev Time 0.00
Received By cthroop Date 2019-01-24 Time 14:45 Sent To  
Notes
2019-02-08 10:30:13NO NOTES
2019-01-25 14:45:15R31

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2019-07-22 Cont ID  
Sent By cthroop Date 2019-07-22 Time 14:09 Rev Time 0.00
Received By cthroop Date 2019-07-22 Time 14:09 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-05-30 Cont ID  
Sent By cthroop Date 2019-05-30 Time 11:43 Rev Time 0.00
Received By cthroop Date 2019-05-30 Time 11:43 Sent To  
Notes
2019-05-30 11:45:41BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 GUEST HOUSE IS CHANGING FROM NON-CONDITIONED SPACE TO
 CONDITIONED SPACE. PALM BEACH COUNTY IMPACT FEES MAY
 APPLY.
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-02-08 Cont ID  
Sent By cthroop Date 2019-02-08 Time 10:31 Rev Time 0.00
Received By cthroop Date 2019-02-08 Time 10:31 Sent To  
Notes
2019-02-08 10:32:22POSSIBLE ADDITION OF CONDITIONED HABITABLE SPACE.
 ADDITIONAL INFORMATION REQUIRED. CT

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-07-18 Cont ID  
Sent By cthroop Date 2019-07-18 Time 15:34 Rev Time 0.00
Received By cthroop Date 2019-07-18 Time 13:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-07-09 Cont ID  
Sent By cthroop Date 2019-07-09 Time 07:47 Rev Time 0.00
Received By cthroop Date 2019-07-05 Time 16:16 Sent To  
Notes
2019-07-09 07:48:53MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 MECHANICAL PLAN HAS BEEN REMOVED FROM SUBMITTAL. PLEASE
 CLARIFY SCOPE OF WORK.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-05-30 Cont ID  
Sent By cthroop Date 2019-05-30 Time 16:11 Rev Time 0.00
Received By cthroop Date 2019-05-24 Time 17:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-02-08 Cont ID  
Sent By cthroop Date 2019-02-08 Time 10:09 Rev Time 0.00
Received By cthroop Date 2019-02-07 Time 07:22 Sent To  
Notes
2019-02-08 10:20:16MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
  
 1. A/C CHANGE OUT COMPLIANCE FORM INDICATES NO EXISTING
 MECH. SYSTEM EXISTS.
 2. PROVIDE MECHANICAL PLAN. IDENTIFY LOCATION OF
 PROPOSED CONDENSING UNIT AND AIR HANDLER. PROVIDE
 SUPPLY AND RETURN AIR DUCT PLAN.
 3. IF MECHANICAL SYSTEM IS NEW, PROVIDE PANEL SCHEDULE
 WITH NEW BREAKERS FOR A/C.
 4. CONTRACTOR TO PRINT NAME AND SIGN PLAN.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-07-18 Cont ID  
Sent By cthroop Date 2019-07-18 Time 15:33 Rev Time 0.00
Received By cthroop Date 2019-07-18 Time 13:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-07-09 Cont ID  
Sent By cthroop Date 2019-07-09 Time 08:52 Rev Time 0.00
Received By cthroop Date 2019-07-05 Time 16:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-05-30 Cont ID  
Sent By cthroop Date 2019-05-30 Time 17:03 Rev Time 0.00
Received By cthroop Date 2019-05-24 Time 17:27 Sent To  
Notes
2019-05-30 17:20:13PLUMBING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. PLUMBING PLANS DO NOT REFLECT WHAT IS ON FILE WITH
 THE CITY OF WEST PALM BEACH. I HAVE INCLUDED A COPY OF
 PLAN PAGE P-1 FROM PERMIT # 15120126 THAT SHOULD
 REFLECT THE EXISTING PLUMBING AT THIS RESIDENCE.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. PROVIDE A PLUMBING SANITARY SYSTEM RISER DIAGRAHM OF
 THE PROPOSED BUILDING SEWER. INCLUDE THAT PORTION OF
 THE SYSTEM THAT WILL REMAIN AS-IS.
 PLUMBING RISER - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1 ADMINISTRATION SECTION
 107.3.5.3 (12).
  
 3. PLEASE PLACE NOTE ON PLAN. THE MASTER BATH TUB
 AND/OR SHOWER VALVE SHALL COMPLY WITH FBC RES P2713.3
 BATHTUB AND WHIRLPOOL BATHTUB VALVES AND P2708.4SHOWER
 CONTROL VALVES.
 HOT WATER SUPPLIED TO BATHTUBS AND WHIRLPOOL BATHTUBS
 SHALL BE LIMITED TO A TEMPERATURE OF NOT GREATER THAN
 120?F (49?C) BY A WATER TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070 OR CSA B125.3, EXCEPT WHERE
 SUCH PROTECTION IS OTHERWISE PROVIDED BY A COMBINATION
 TUB/SHOWER VALVE IN ACCORDANCE WITH SECTION P2708.3.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-29 Cont ID  
Sent By jesmith Date 2019-01-29 Time 15:31 Rev Time 0.00
Received By jesmith Date 2019-01-29 Time 15:10 Sent To  
Notes
2019-01-29 15:31:07CODES IN EFFECT:
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 5TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 PLUMBING COMMENTS:DENIED
  
 1. PLANS DO NOT DESCRIBE PRE-EXISTING CONDITIONS.CAN
 NOT TELL IF FIXTURES HAVE BEEN RELOCATED FROM ORIGINAL
 POSITIONS REQUIRING RECONFIGURATION OF PIPING SYSTEMS.
 PROVIDE A DETAILED SCOPE OF WORK AND AN "EXISTING FLOOR
 PLAN" IF FIXTURE LOCATIONS ARE RECONFIGURED PER WPB FBC
 107.2.1. IF FIXTURES SUCH AS TOILETS, SINKS AND
 LAVATORIES ARE GOING BACK INTO SAME LOCATIONS, PROVIDE
 A NOTE STATING "CONNECT NEW FIXTURES TO EXISTING
 PLUMBING ROUGH"; FOR THE BATHTUB PROVIDE A NOTE STATING
 "PROVIDE NEW IN-WALL CONTROL VALVE AND TRIM". IF
 FIXTURE LOCATIONS ARE TO BE RECONFIGURED THEN PROVIDE A
 SANITARY RISER DIAGRAM PER WPB FBC 107.3.5.3 (12).
 2. THE PLANS SHALL BEAR THE NAME OF THE DESIGNER AND
 HIS SIGNATURE PER WPB FBC 107.2.1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 561-805-6715
 [email protected]