Plan Review Details - Permit 19011020
Plan Review Stops For Permit 19011020
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-03-25 Time   Rev Time 0.00
Received By lmarchan Date 2019-03-20 Time 14:08 Sent To  
Notes
2019-03-21 14:08:53RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-03-07 Time   Rev Time 0.00
Received By lmarchan Date 2019-02-25 Time 13:24 Sent To  
Notes
2019-02-26 13:24:39RESUB ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-03-25 Cont ID  
Sent By ccole Date 2019-03-25 Time 11:45 Rev Time 0.00
Received By ccole Date 2019-03-25 Time 11:45 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-03-07 Cont ID  
Sent By ccole Date 2019-03-07 Time 07:46 Rev Time 0.00
Received By ccole Date 2019-03-07 Time 07:46 Sent To  
Notes
2019-03-07 07:58:541ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19011020
 3/7/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) TTHE SUBMITTED SUMMARY LOAD CALCULATIONS MUST BE
 SIGNED AND SEALED BY A FL. REGISTERED ENGINEER. PLEASE
 PROVIDE THE AREA IN SQ. FT. OF THE ZONE ON THE
 RESUBMITTED CALCULATION.
  
 C403.2.1 CALCULATION OF HEATING AND COOLING LOADS.
 DESIGN LOADS ASSOCIATED WITH HEATING, VENTILATING AND
 AIR CONDITIONING OF THE BUILDING SHALL BE DETERMINED IN
 ACCORDANCE WITH ANSI/ASHRAE/ACCA STANDARD 183 OR ACCA
 MANUAL N OR BY AN APPROVED EQUIVALENT COMPUTATIONAL
 PROCEDURE USING THE DESIGN PARAMETERS SPECIFIED IN
 CHAPTER 3. HEATING AND COOLING LOADS SHALL BE ADJUSTED
 TO ACCOUNT FOR LOAD REDUCTIONS THAT ARE ACHIEVED WHERE
 ENERGY RECOVERY SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM
 IN ACCORDANCE WITH THE ASHRAE HVAC SYSTEMS AND
 EQUIPMENT HAND-BOOK BY AN APPROVED EQUIVALENT
 COMPUTATIONAL PROCEDURE. DESIGN LOADS SHALL BE ATTACHED
 TO THE CODE COMPLIANCE FORM SUBMITTED TO THE BUILDING
 DEPARTMENT WHEN THE BUILDING IS PERMITTED OR, IN THE
 EVENT THE MECHANICAL PERMIT IS OBTAINED AT A LATER
 TIME, THE SIZING CALCULATION SHALL BE SUBMITTED WITH
 THE APPLICATION FOR THE MECHANICAL PERMIT.
  
 EXCEPTION: WHERE MECHANICAL SYSTEMS ARE DESIGNED BY A
 REGISTERED ENGINEER, THE ENGINEER HAS THE OPTION OF
 SUBMITTING A SIGNED AND SEALED SUMMARY SHEET TO THE
 BUILDING DEPARTMENT IN LIEU OF THE COMPLETE SIZING
 CALCULATION(S). SUCH SUMMARY SHEET SHALL INCLUDE THE
 FOLLOWING (BY ZONE):
  
 1.PROJECT NAME/OWNER
  
 2.PROJECT ADDRESS
  
 3.AREA IN SQUARE FEET
  
 4.SIZING METHOD USED
  
 5.OUTDOOR DRY BULB USE
  
 6.INDOOR DRY BULB
  
 7.OUTDOOR WET BULB USED
  
 8.GRAINS WATER (DIFFERENCE)
  
 9.TOTAL SENSIBLE GAIN
  
 10.TOTAL LATENT GAIN
  
 11.RELATIVE HUMIDITY
  
 12.TOTAL COOLING REQUIRED WITH OUTSIDE AIR
  
 2) AN AIR DISTRIBUTION PLAN IS ATTACHED TO THE
 CALCULATION FORM WHICH IS NOT ACCEPTABLE FOR REVIEW PER
 SECTION 105.3.1.2 WPB WHICH REQUIRES THE PLAN TO BE
 DRAWN BY A FL. LICENSED ENGINEER OF THE INSTALLING
 CONTRACTOR.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-02-01 Cont ID  
Sent By ccole Date 2019-02-01 Time 11:34 Rev Time 0.00
Received By ccole Date 2019-02-01 Time 11:34 Sent To  
Notes
2019-02-01 11:53:441ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19011020
 2/1/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE CHANGE IN COOOLING CAPACITY FROM 15 TONS TO 10
 TONS REQUIRES SUBMITTAL OF AC LOAD CALCULATIONS IN
 ACCORDANCE WITH SECTION C403.2.1 FBC EC. SEE BELOW:
  
 C403.2.1 CALCULATION OF HEATING AND COOLING LOADS.
 DESIGN LOADS ASSOCIATED WITH HEATING, VENTILATING AND
 AIR CONDITIONING OF THE BUILDING SHALL BE DETERMINED IN
 ACCORDANCE WITH ANSI/ASHRAE/ACCA STANDARD 183 OR ACCA
 MANUAL N OR BY AN APPROVED EQUIVALENT COMPUTATIONAL
 PROCEDURE USING THE DESIGN PARAMETERS SPECIFIED IN
 CHAPTER 3. HEATING AND COOLING LOADS SHALL BE ADJUSTED
 TO ACCOUNT FOR LOAD REDUCTIONS THAT ARE ACHIEVED WHERE
 ENERGY RECOVERY SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM
 IN ACCORDANCE WITH THE ASHRAE HVAC SYSTEMS AND
 EQUIPMENT HAND-BOOK BY AN APPROVED EQUIVALENT
 COMPUTATIONAL PROCEDURE. DESIGN LOADS SHALL BE ATTACHED
 TO THE CODE COMPLIANCE FORM SUBMITTED TO THE BUILDING
 DEPARTMENT WHEN THE BUILDING IS PERMITTED OR, IN THE
 EVENT THE MECHANICAL PERMIT IS OBTAINED AT A LATER
 TIME, THE SIZING CALCULATION SHALL BE SUBMITTED WITH
 THE APPLICATION FOR THE MECHANICAL PERMIT.
  
 EXCEPTION: WHERE MECHANICAL SYSTEMS ARE DESIGNED BY A
 REGISTERED ENGINEER, THE ENGINEER HAS THE OPTION OF
 SUBMITTING A SIGNED AND SEALED SUMMARY SHEET TO THE
 BUILDING DEPARTMENT IN LIEU OF THE COMPLETE SIZING
 CALCULATION(S). SUCH SUMMARY SHEET SHALL INCLUDE THE
 FOLLOWING (BY ZONE):
  
 1.PROJECT NAME/OWNER
  
 2.PROJECT ADDRESS
  
 3.AREA IN SQUARE FEET
  
 4.SIZING METHOD USED
  
 5.OUTDOOR DRY BULB USE
  
 6.INDOOR DRY BULB
  
 7.OUTDOOR WET BULB USED
  
 8.GRAINS WATER (DIFFERENCE)
  
 9.TOTAL SENSIBLE GAIN
  
 10.TOTAL LATENT GAIN
  
 11.RELATIVE HUMIDITY
  
 12.TOTAL COOLING REQUIRED WITH OUTSIDE AIR
  
 2) PLEASE REMOVE THE AC CHANGE OUT FORM FROM THE
 SUBMITTAL- THE AC CHANGEOUT FORM IS FOR "LIKE FOR LIKE"
 REPLACEMENTS OF AC SYSTEMS. PROVIDE AN EQUIPMENT
 SCHEDULE FOR THE PROPOSED NEW 10-TON UNIT THAT LISTS
 THE MAKE AND MODEL, COOLING AND HEATING CAPACITIES,
 EFFICIENCY RATING, AND ELECTRICAL DATA. PLEASE NOTE
 THAT THE EXISTING ELECTRICAL CIRCUITRY MAY NEED TO BE
 MODIFIED TO ACCOMODATE THE NEW SYSTEM. PLEASE CONSULT
 WITH A FL. LICENSED ELECTRICIAN OR ENGINEER AND PROVIDE
 AN ELECTRICAL PLAN AND SUB-PERMIT APPLICATION IF
 NECESSARY.
  
 3) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE NEW RTU TO THE EXISTING CURB PER SECTION 301.15 FBC
 M. IF A CURB ADAPTER IS TO BE USED, PLEASE SUBMIT
 MANUFACTURER'S SPECIFICATIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  