| 2019-02-15 09:07:29 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19011008 |
| | 2/15/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 4.1: THE AC SCHEDULE INDICATES 6400 CFMS OF |
| | SUPPLY FOR THE EXISTING 7.5 TON SYSTEM. THE PLAN AC |
| | LAYOUT SHOWS 3025 CFMS OF AIR DISTRIBUITED- PLEASE |
| | CORRECT THE SCHEDULE. |
| | |
| | 2) SHEET 4.1: THE OUTSIDE AIR CALCULATIONS APPEAR TO BE |
| | INACCURATE AND SHOW THE TOTAL REQUIRED O/A TO BE 3145 |
| | CFMS WHICH IS GREATER THAN THE CAPACITY OF THE SYSTEM |
| | AND WOULD REQUIRE THE UNIT TO BE A DEDICATED OUTDOOR |
| | AIR SYSTEM DOAS. IN ACCORDANCE WITH TABLE 403.3.1.1 FBC |
| | M, HEALTHCUB/AEROBICS ROOMS ARE CALCULATED AT 40 |
| | PERSONS PER 1000 SF WHICH WOULD EQUATE TO 123 OCCUPANTS |
| | AT X 20 CFMS PER OCCUPANT = ( 2460 CFMS) + 0.06 CFMS X |
| | 3075 = (184.5) = TOTAL 2645 CFMS O/A REQUIRED. THIS |
| | CALCULATION IS BASED ON THE 3075 SQUARE FOOTAGE THAT |
| | WAS LISTED ON THE PLAN IN THE CALCULATION. THIS NUMBER |
| | CAN BE REDUCED BY ELIMINATING THE SQUARE FOOTAGE OF THE |
| | RESTROOMS. BUT ULTIMATELY IT APPEARS THAT THE EXISTING |
| | SYSTEM WOULD BE INCAPABLE OF CONDITIONING AND |
| | DEHUMIDIFYING THIS LARGE AMOUNT OF O/A. GENERALLY THE |
| | PERCENTAGE OF O/A TO TOTAL SUPPLY AIR IS ABOUT 15-25%. |
| | PLEASE PROVIDE AN AC COOLING AND HEATING CALCULATION |
| | THAT INCORPORATES THE VENTILATION CALCULATION INTO THE |
| | TOTAL HEAT LOAD. |
| | |
| | 3) THE AC SCHEDULE INDICATES THE SYSTEM IS 8.9 EER, |
| | HOWEVER THE SUBMITTED ENERGYGAUGE COMPLIANCE FORM |
| | INDICATES 14 SEER. CORRECT THE ENERGY FORM TO MATCH THE |
| | SCHEDULE. PLEASE SEE TABLE C403.2.3(1) FBC EC: SYSTEMS |
| | GREATER THAN 65,000 BUT LESS THAN 135,000 BTU/H ARE |
| | RATED BY EER. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |