Plan Review Details - Permit 19010948
Plan Review Stops For Permit 19010948
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-04-10 Cont ID  
Sent By dbattles Date 2019-04-10 Time 09:28 Rev Time 0.00
Received By dbattles Date 2019-04-10 Time 09:28 Sent To  
Notes
2019-05-30 13:30:07PER FBC AMENDED 102.2(E) THE TEMPORARY TRAILERS WILL BE
 EXEMPT FROM PROVISIONS FOR OPENING PROTECTION.
 NO HURRICANE PANELS WILL NEED TO BE PROVIDED.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
 BUILDING PLANS EXAMINER PX4191
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-04-05 Cont ID  
Sent By dbattles Date 2019-03-22 Time 09:03 Rev Time 0.00
Received By dbattles Date 2019-03-22 Time 09:03 Sent To  
Notes
2019-04-05 15:00:13PROVIDE A LETTER STATING WHAT CODE VERSION THE
 BATHROOMS WERE INSTALLED (SHOULD BE 2007)
 STATE THAT THE CURRENT BATHROOMS WILL SHOW COMPLIANCE
 WITH THAT CODE FOR INSPECTION.
  
 SHEET RS-1 AND A4 ARE ENGINEERED DRAWINGS AND A HARD
 COPY SIGNED/SEALED WILL NEED TO BE PROVIDED, OR UPLOAD
 THEM DIGITALLY SIGNED WITH GRAPHIC REPRESENTATION OF
 SEAL.
  
 PROVISO:
 PROVIDE HURRICANE SHUTTERS FOR TRAILER OPENINGS.
 PRODUCT APPROVAL TO BE DEFERRED SUBMITTAL.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
 COMMERCIAL BUILDING INSPECTOR BN7557
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-20 Cont ID  
Sent By dbattles Date 2019-02-20 Time 07:57 Rev Time 0.00
Received By dbattles Date 2019-02-19 Time 14:54 Sent To  
Notes
2019-02-20 07:58:21****CORRECTIONS****
 W.P.B. PERMIT: 19010948
 REVIEWED: FEBRUARY 20, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 107.3.5 FBC[B] SHEET C8.00 SAYS SEE TRAILER PLANS FOR
 RAMPS STAIRS AND DECKS DETAILS.
 THE DETAILS ON RS-1 DO NOT MATCH THE CIVIL PLANS.
 -PLEASE PROVIDE SITE PLAN TO SHOW ACCESSIBLE PATH AND
 HOW BOTH DOORS FUNCTION FOR EGRESS.
  
 1004.1 FBC[B] DESIGN OCCUPANT LOAD. IN DETERMINING
 MEANS OF EGRESS REQUIREMENTS, THE NUMBER OF OCCUPANTS
 FOR WHOM MEANS OF EGRESS FACILITIES ARE PROVIDED SHALL
 BE DETERMINED IN ACCORDANCE WITH THIS SECTION.
 -PROVIDE THE OCCUPANT DATA.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS.
 FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE
 REQUIRED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 CONTACT ME AT 561-805-6718 (M-F 8-5) TO DISCUSS
 COMMENTS, OR E-MAIL ANYTIME [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-03-25 Cont ID  
Sent By jpearson Date 2019-03-25 Time 10:09 Rev Time 0.00
Received By jpearson Date 2019-03-25 Time 10:09 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-20 Cont ID  
Sent By jpearson Date 2019-02-20 Time 15:31 Rev Time 0.00
Received By jpearson Date 2019-02-20 Time 15:31 Sent To  
Notes
2019-02-20 15:31:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS A 208/120 VOLT SERVICE FROM FPL.
 THIS SERVICE GOES TO A METER CAN, THEN DISCONNECT, AND
 THEN FEEDS A TRANSFORMER SHOWING THAT IT BECOMES
 208/120 VOLT. IF THE SERVICE IS ALREADY 208/120 VOLT,
 WHY WOULD T HIS TRANSFORMER BE NEEDED? IS PART OF THIS
 SERVICE 480/277 VOLT? PROVIDE CLARIFICATION AND/OR
 CORRECTIONS TO RISER DIAGRAM AS NEEDED. NEC 215.5; WPB
 FBC 107.2.1
 2. ESTIMATED VALUES FOR AIC CALCULATION IS NOT
 ACCEPTABLE. PROVIDE ACCURATE AVAILABLE SHORT CIRCUIT
 CALCULATION FOR SERVICE INCLUDING INFORMATION FROM THE
 POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC
 RATING OF THE SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9,
 110.10
 3. GROUNDING OF SEPARATLEY DERIVED SYSTEMS WOULD BE
 ACCOMPLISHED AT THE TRANSFORMER. IT SHOULD NOT BE
 DUPLICATED AT THE 100 AMP DISCONNECTS FOR TR1 AND TR2.
 PROVIDE CORRECTION. NEC 250.6, NEC 250.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG-A ENGINEERING FORMAL REVIEW
Rev No 1 Status P Date 2019-04-05 Cont ID  
Sent By rrossano Date 2019-04-05 Time   Rev Time 0.00
Received By rrossano Date 2019-04-05 Time   Sent To I
Notes
2019-06-05 15:28:27E18110025 PER MG
  
2019-04-05 11:12:20REVIEWED VIA ENGINEERING SUBMITTAL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-01-25 Cont ID  
Sent By scaldero Date 2019-01-25 Time 13:28 Rev Time 0.00
Received By scaldero Date 2019-01-25 Time 12:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-04-15 Cont ID  
Sent By thunt Date 2019-04-15 Time 10:15 Rev Time 0.00
Received By thunt Date 2019-04-09 Time 09:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-01 Cont ID  
Sent By thunt Date 2019-04-01 Time 14:45 Rev Time 0.00
Received By thunt Date 2019-03-12 Time 09:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-07 Cont ID  
Sent By lmarchan Date 2019-03-07 Time 14:07 Rev Time 0.00
Received By lmarchan Date 2019-01-24 Time 10:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2019-02-19 Cont ID  
Sent By ccole Date 2019-02-19 Time 15:51 Rev Time 0.00
Received By ccole Date 2019-02-19 Time 15:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-04-15 Cont ID  
Sent By thunt Date 2019-04-15 Time 10:15 Rev Time 0.00
Received By thunt Date 2019-04-15 Time 10:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-04-01 Cont ID  
Sent By thunt Date 2019-04-01 Time 14:45 Rev Time 0.00
Received By thunt Date 2019-04-01 Time 14:45 Sent To  
Notes
2019-04-01 14:44:25PLUMBING 2ND REVIEW**DENIED**
  
 1) PROVIDE TANKLESS WATER HEATER COMPLETE INSTALLATION
 MANUAL. PROVIDE SPEC AND LISTING FOR APPROVED ASSE 1070
 TEMPERING DEVICE. FBC 107.3.5, FBC P607.1.2
  
 2)TRAILER PLANS 12 X 56 #2 NOTE CALLS OUT OF ALL
 PLUMBING, WALLS AND DOORS BE SITE INSTALLED. THE
 INTERIOR RESTROOM WOULD NOW BE REQUIRED TO COMPLY WITH
 THE FBC PLUMBING AND ACCESSIBILITY CODE 2017 6TH
 ED.PROVIDE PLANS SHOWING HOW YOU INTEND TO COMPLY WITH
 THE ACCESSIBILITY REQUIREMENTS FOR A TOILET ROOM TO
 INCLUDE CLEAR FLOOR SPACES, TURNING SPACE, ETC
  
 3) PROVIDE HOW THE CITY'S DOMESTIC AND SITE POTABLE
 WATER SUPPLY IS GOING TO BE PROTECTED AS REQUIRED IN
 FBC P 608.1
  
 4) PROVIDE HOLDING TANKS PUMP OUT SCHDULE AND CONTRACT.
 FBC 107.2.1
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-02-13 Cont ID  
Sent By gjohnson Date 2019-02-13 Time 13:24 Rev Time 0.00
Received By gjohnson Date 2019-02-13 Time 13:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-04-10 Cont ID  
Sent By dbattles Date 2019-04-10 Time 09:29 Rev Time 0.00
Received By dbattles Date 2019-04-10 Time 09:29 Sent To  
Notes
2019-04-10 09:31:28HARD COPIES OF ENGINEERING RECEIVED AND APPROVED FOR
 SIGNATURE.
2019-04-10 07:46:314/9/19 HARD COPIES ROUTED TO DBATTLES

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-03-22 Cont ID  
Sent By dbattles Date 2019-03-22 Time 09:05 Rev Time 0.00
Received By dbattles Date 2019-03-22 Time 09:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-02-20 Cont ID  
Sent By dbattles Date 2019-02-20 Time 07:58 Rev Time 0.00
Received By dbattles Date 2019-02-19 Time 14:54 Sent To  
Notes
2019-02-20 07:59:08ANY NEW SHEETS WILL NEED TO BE REVIEWED.

Review Stop Z ZONING
Rev No 2 Status P Date 2019-03-15 Cont ID  
Sent By eschneid Date 2019-03-15 Time 16:50 Rev Time 0.25
Received By eschneid Date 2019-03-15 Time 16:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-03-07 Cont ID  
Sent By eschneid Date 2019-03-07 Time 13:52 Rev Time 0.75
Received By eschneid Date 2019-03-07 Time 13:25 Sent To PC
Notes
2019-03-07 13:25:50FAILED
  
 1) SHEET C.08 IS NOT THE SITE PLAN APPROVED BY THE CITY
 COMMISSION. THE AREA NORTHWEST OF THE TRAILERS NEEDS TO
 BE CORRECTED.
  
 2) THE TEMPORARY OFFICE TRAILERS MUST BE REMOVED WITHIN
 30 DAYS OF THE COMPLETION OF THE INTERIOR RENOVATIONS
 TO THE GRACE PAVILION OR THE DOMES, WHICHEVER OCCURS
 LAST.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]