Plan Review Details - Permit 19010946
Plan Review Stops For Permit 19010946
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-07 Cont ID  
Sent By tklarge Date 2019-02-07 Time 06:34 Rev Time 0.00
Received By tklarge Date 2019-02-07 Time 06:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-31 Cont ID  
Sent By tklarge Date 2019-01-31 Time 05:32 Rev Time 0.00
Received By tklarge Date 2019-01-31 Time 05:21 Sent To I
Notes
2019-01-31 04:48:311) INDICATE ON THE PLANS IF NEW TILE WILL BE INSTALLED
 ON THE FLOOR IN THE BATHROOM. IF SO, SUBMIT TWO COPIES
 OF A TEST REPORT FOR THE UNDERLAYMENT FOR THE TILE
 SHOWING COMPLIANCE WITH 2017 FBC SEC. 1207.2 FOR
 AIR-BORNE SOUND TRANSMISSION AND SEC.1207.3 FOR
 STRUCTURE-BORNE SOUND TRANSMISSION,
 2) FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
 3) INDICATE ON THE PLAN THE TYPE OF BACKING BOARD THAT
 WILL BE INSTALLED FOR THE TILE. WATER-RESISTANT GYPSUM
 BACKING BOARD SHALL NOT BE USED IN AREAS WHERE THERE
 WILL BE DIRECT EXPOSURE TO WATER OR IN AREAS SUBJECT TO
 CONTINUOUS HIGH HUMIDTY. 2017 FBC-BUILDING SEC.2509.3.
 4) INDICATE ON THE PLAN IF THE BACK WALL OF THE SHOWER
 IS A TENANT SEPARATION WALL. IF SO, THE FIRE RATING OF
 THE WALL SHALL BE MAINTAINED AS REQUIRED BY 2017 FBC -
 BUILDING SEC. 420.1, 420.2, 708.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-07 Cont ID  
Sent By tklarge Date 2019-02-07 Time 06:34 Rev Time 0.00
Received By tklarge Date 2019-02-05 Time 13:32 Sent To  
Notes
2019-02-06 13:32:45RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-31 Cont ID  
Sent By tklarge Date 2019-01-31 Time 05:32 Rev Time 0.00
Received By tklarge Date 2019-01-22 Time 14:23 Sent To  
Notes
2019-01-23 14:23:49PLUMB <5K

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-02-07 Cont ID  
Sent By tklarge Date 2019-02-07 Time 06:25 Rev Time 0.00
Received By tklarge Date 2019-02-07 Time 06:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-31 Cont ID  
Sent By tklarge Date 2019-01-31 Time 05:21 Rev Time 0.00
Received By tklarge Date 2019-01-31 Time 04:27 Sent To  
Notes
2019-01-31 04:48:031) INDICATE ON THE PLAN IF THE DRAIN FROM THE TUB IS
 BEING RELOCATED. IF IT IS, SUBMIT DETAILS FOR THE FIRE
 STOPPING OF THE PENETRATION TO ENSURE THE REQUIRED FIRE
 RATING OF THE EXISTING SLAB IS MAINTAINED.
 2) INDICATE THE TYPE OF PIPE BEING INSTALLED FOR THE
 SHOWER. PVC MAY NOT BE PERMITTED DEPENDING ON WHETHER
 THE PIPING IS LOCATED IN A RETURN AIR PLENUM AND MUST
 ALSO COMPLY WITH 2017 FBC-BUILDING SEC.718.5.
 3) THE NEW SHOWER VALVE SHALL COMPLY WITH 2017
 FBC-PLUMBING SEC.424.3. THE VALVE SHALL BE BALANCED
 PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC.SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE VALVE IF AVAILABLE. IF THERE IS
 A HAND-HELD SHOWER, A BACKFLOW PREVENTION DEVICE SHALL
 BE INSTALLED IN ACCORDANCE WITH 2017 FBC-PLUMBING
 SEC.424.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved